11
Standard mode operation:
If the boiler’s temperature reach
es preset
one then the controller switches of to
SUPERVISION mode.
Controller is equipped with boiler’
s power
modulation mechanism
–
which allows for
gradual power reduction when approaching
the preset temperature.
There are three power levels:
-
Maximal power 100
-
Medium power 50
-
Minimum power 30
Values for the individual power levels can be
set in the menu:
Service settings
→
Burner settings
→
Operation
The controller regulates burner’s power
with
which it operates depending on preset
temperature
and
defined
hysteresis
Hysteresis H2
and
Hysteresis
H1. Pic. 4
Hystereses H1
and
H2 of
power modulationIt
is possible to configure volumes H1 and H2
in such a way that modulation is done
without intermediate position. That means
switching from 100% to 30% with omission
of 50% power.
Pic. 4 Hystereses H1 and H2 of power modulation
Operation in Fuzzy Logic mode:
In Fuzzy Logic mode the controller
automatically regulates burner power to
allow boiler operation in such a way to
maintain its temperature on preset level. The
controller uses power levels defined in
Standard mode. In this mode the parameters
Hysteresis H2
and
Hysteresis H1
do not have
to be set.
The Fuzzy Logic mode unlike the Standard
mode is not faulty in respect of failing to
reach the preset boiler temperature due to
incorrect adjustment of
Hysteresis H2
and
Hysteresis H.
It also allows for quicker reach
the preset temperature.
Attention: If the boiler operates
without heat buffer and controller is
switched into SUMMER mode than
Standard mode operation of the
controller is recommended.
After exceeding the preset temperature by 5
C degrees the controller switches into
SUPERVISION mode.
8.6
SUPERVISION
SUPERVISION mode is applicable either in
regulation in STANDARD and Fuzzy Logic
mode.
The controller switches into SUPERVISION
mode
automatically
without
user’s
intervention: - in Standard regulation mode
–
after
reaching
the
boiler
preset
temperature, - in Fuzzy Logic steering
–
after
exceeding boiler preset temperature by 5 C
degrees.
In SUPERVISION mode the controller
oversees the furnace, keeping it from
burning off. To do so, the burner operates
with very low power, what together with
properly adjusted parameters do not cause
further increase in temperature. Burner’s
power in SUPERVISION mode and other
parameters of Supervision are grouped in
menu:
Service settings
→
Burner settings
→
Supervision
Maximum time of boiler’s operating in
supervision mode is defined in parameter
Supervision time
. If after this time (in
Supervision mode) there is no need to
restart the boiler then the controller starts
the process of b
oiler’s burning off.
For setting
Supervision time
= 0
the controller omits SUPERVISION
mode and goes directly to BURNING
OFF.
Содержание KSR Beta Pelet 16
Страница 1: ...Operation and maintenance manual for KSR Beta Pelet series boilers with feeders ...
Страница 20: ......
Страница 21: ......
Страница 23: ......
Страница 25: ......
Страница 26: ......
Страница 27: ...3 This sign indicates relation to safety issues This sign indicates relations to module functional features ...
Страница 54: ......
Страница 55: ......
Страница 56: ......
Страница 57: ...1 ...
Страница 58: ...2 ...
Страница 72: ...16 ...
Страница 73: ...17 ...
Страница 74: ...18 ...
Страница 75: ...19 ...
Страница 76: ...20 ...
Страница 77: ......
Страница 78: ......
Страница 90: ......
Страница 91: ......
Страница 92: ......
Страница 93: ......
Страница 94: ......
Страница 98: ......
Страница 99: ...USER MANUAL OF THE CONTROLLER S Control ...
Страница 109: ...17 CONTROLLER INSTALLATION AND SERVICE SETTINGS S Control ...
Страница 135: ...43 ...
Страница 136: ......
Страница 137: ...1 ...
Страница 138: ......
Страница 142: ......
Страница 143: ...USER MANUAL OF THE CONTROLLER S Control TOUCH ...
Страница 153: ...17 ...
Страница 154: ......
Страница 155: ...USER MANUAL OF CONTROLLER INSTALLATION AND SERVICE SETTINGS S Control TOUCH ...
Страница 183: ......
Страница 184: ......