11
x
Standard mode operation
If the boiler’s temperature reach preset one
then the controller switches to SUPERVISION
mode.
Controller is equipped with boiler’
s power
modulation mechanism
–
which allows for
gradual power reduction when approaching
the preset temperature.
There are three power burner levels:
maximal, medium, minimum. Values of the
individual power levels can be set in the
below menu:
Boiler settings
→
Output modulation
The controller determines the burner power
to be used by the boiler depending on the
preset boiler temperature and the pre-
defined hysteresis values
H2 hysteresis
,
H1
hysteresis
and settings parameters:
Blow-in
revision
–
max./med./min. power
.
It is possible to configure H1 and H2 values
so that the modulation will be done with no
medium power level, i.e. by changing the
level from maximum directly to minimum
and skipping the medium power value (right
part of the illustration).
Pic. 7 Hystereses H1 and H2 of power modulation
x
Operation in Fuzzy Logic mode
In Fuzzy Logic mode the controller
automatically regulates burner power to
allow boiler operation in such a way to
maintain its temperature on preset level. The
controller uses power levels defined in
Standard mode. In this mode the parameters
Hysteresis H2
and
Hysteresis H1
do not have
to be set.
The Fuzzy Logic mode unlike the Standard
mode is not faulty in respect of failing to
reach the preset boiler temperature due to
incorrect adjustment of
Hysteresis H2
and
Hysteresis H.
It also allows for quicker reach
the preset temperature.
Attention: If the boiler operates
without heat buffer and controller is
switched into SUMMER mode than
Standard mode operation of the
controller is recommended.
After exceeding the preset temperature by
5
º
C
the
controller
switches
into
SUPERVISION mode.
8.7
SUPERVISION
SUPERVISION mode is applicable either in
regulation in STANDARD and Fuzzy Logic
mode.
The controller switches into SUPERVISION
mode
automatically
without
user’s
intervention: - in Standard regulation mode
-
after
reaching
the
boiler
preset
temperature, - in Fuzzy Logic steering
–
after
exceeding boiler preset temperature by 5
º
C.
In SUPERVISION mode the controller
oversees the furnace, keeping it from
burning off. To do so, the burner operates
with very low power, what together with
properly adjusted parameters do not cause
further increase in te
mperature. Burner’s
power in SUPERVISION mode and other
parameters of Supervision are grouped in
menu:
Service settings
→
Burner settings
→
Supervision
Maximum time of boiler’s operating in
supervision mode is defined in parameter
Supervision time
. If after this time (in
Supervision mode) there is no need to
restart the boiler then the controller starts
the process of boiler’s burning off.
For setting
Supervision time
= 0 the
controller omits SUPERVISION mode
and goes directly to BURNING OFF.
8.8
BURNING OFF
In the BURNING OFF mode, remains of the
pellet are burnt out and the boiler is
prepared for standstill or deactivation.
Содержание KSR Beta Pelet 16
Страница 1: ...Operation and maintenance manual for KSR Beta Pelet series boilers with feeders ...
Страница 20: ......
Страница 21: ......
Страница 23: ......
Страница 25: ......
Страница 26: ......
Страница 27: ...3 This sign indicates relation to safety issues This sign indicates relations to module functional features ...
Страница 54: ......
Страница 55: ......
Страница 56: ......
Страница 57: ...1 ...
Страница 58: ...2 ...
Страница 72: ...16 ...
Страница 73: ...17 ...
Страница 74: ...18 ...
Страница 75: ...19 ...
Страница 76: ...20 ...
Страница 77: ......
Страница 78: ......
Страница 90: ......
Страница 91: ......
Страница 92: ......
Страница 93: ......
Страница 94: ......
Страница 98: ......
Страница 99: ...USER MANUAL OF THE CONTROLLER S Control ...
Страница 109: ...17 CONTROLLER INSTALLATION AND SERVICE SETTINGS S Control ...
Страница 135: ...43 ...
Страница 136: ......
Страница 137: ...1 ...
Страница 138: ......
Страница 142: ......
Страница 143: ...USER MANUAL OF THE CONTROLLER S Control TOUCH ...
Страница 153: ...17 ...
Страница 154: ......
Страница 155: ...USER MANUAL OF CONTROLLER INSTALLATION AND SERVICE SETTINGS S Control TOUCH ...
Страница 183: ......
Страница 184: ......