9
temperature in the main window of all
thermostats.
7.11.2
Thermostat settings
This parameter enables or disables operation
of particular Room Control thermostats.
Enabling or disabling thermostat 2
or 3 is possible only in case when
there
are
additional
external
temperature sensors connected to
the Room Control room panel.
When thermostat 2 or 3 is disabled,
its main screen is not displayed.
7.11.3
Hysteresis.
This parameter defines hysteresis of room
temperature. It decides of room temperature
at which the room thermostat will inform the
boiler regulator to heat. The boiler regulator
will start heating when the room temperature
drops under the
current preset temperature
minus hysteresis
. It will finish heating when
the current preset room temperature is
reached.
7.11.4
Temperature correction
This parameter enables to make corrections
of measured thermostat temperature within
a range of -3.
0°C to +3
.
0°C.
Warning!
The changes are not
visible immediately. Wait 5 minutes
to adjustment was taken into
account.
7.11.5
Language change
In order to change menu language, select:
MENU
Æ
Settings
Æ
Language
and select required language from the list.
7.11.6
Sound alarm
This parameter decided whether during the
alarm there will be a sound signal generated
in the Room Control panel.
7.11.7
Clock settings
In order to set time and date, select:
MENU
Æ
Settings
Æ
Clock
According to set date, the device will
automatically set an appropriate weekday.
The Room Control panel is equipped with a
system clock which is independent of the
boiler regulator clock, and therefore both
clocks have to be set on the same hour.
Programmed
schedule
works
according to the scoSTER200 panel
clock.
7.11.8
Brightness screen setting
The panel has the ability to set three
separate
levels
of
screen
brightness
separately for day, night and when editing
parameters. To adjust the brightness for the
selected level, go to the
MENU
Æ
Settings
Æ
Brightness
, and then set [%] intensity.
The panel based on the internal
system clock settings independently
activates the programmed level of
brightness in daylight hours and
night.
7.11.9
Information
In this window you can obtain information
concerning software version of the Room
Control panel and connected S.Control,
R.Control boiler regulator.
8.
Instructions for panel assembly
8.1
Technical data
Power source
+5V..12VCC
Current consumed by the device
I = 0.1 A
Protection level of the regulator
IP20
Ambient temperature
0...50 °C
Storage temperature
0...65 °C
Temperature measurement range
0...50 °C
Temperature regulation range
5...35 °C
Hysteresis
0.
2…5 °C
Relative humidity
5
–
85% without
condensation
Terminals
Elastic clamps
0.25
–
2.5mm
2
Display
Graphic 128x64
External dimensions
164x90x40 mm
Complete weight
0.2 kg
Standards
PN-EN 60730-2-9
PN-EN 60730-1
Software class
A
Содержание KSR Beta Pelet 16
Страница 1: ...Operation and maintenance manual for KSR Beta Pelet series boilers with feeders ...
Страница 20: ......
Страница 21: ......
Страница 23: ......
Страница 25: ......
Страница 26: ......
Страница 27: ...3 This sign indicates relation to safety issues This sign indicates relations to module functional features ...
Страница 54: ......
Страница 55: ......
Страница 56: ......
Страница 57: ...1 ...
Страница 58: ...2 ...
Страница 72: ...16 ...
Страница 73: ...17 ...
Страница 74: ...18 ...
Страница 75: ...19 ...
Страница 76: ...20 ...
Страница 77: ......
Страница 78: ......
Страница 90: ......
Страница 91: ......
Страница 92: ......
Страница 93: ......
Страница 94: ......
Страница 98: ......
Страница 99: ...USER MANUAL OF THE CONTROLLER S Control ...
Страница 109: ...17 CONTROLLER INSTALLATION AND SERVICE SETTINGS S Control ...
Страница 135: ...43 ...
Страница 136: ......
Страница 137: ...1 ...
Страница 138: ......
Страница 142: ......
Страница 143: ...USER MANUAL OF THE CONTROLLER S Control TOUCH ...
Страница 153: ...17 ...
Страница 154: ......
Страница 155: ...USER MANUAL OF CONTROLLER INSTALLATION AND SERVICE SETTINGS S Control TOUCH ...
Страница 183: ......
Страница 184: ......