Operation and maintenance manual for the KSR Beta Pelet series boilers with feeders. The producer reserves the right to introduce technical modifications.
3.5. Filling the system with water
3.5.1. Filling the boiler with water
before
fi
rst start-up
1. Flush heating system and boiler before
fi
lling it with water to
remove all contaminations.
2. Fill the system with water through the drain cock using the
fl
exible hose. Water intended for feeding the heating boil-
er should meet the requirements of the PN-93/C-04607
standard. Quality of water
fi
lling the central heating system
in
fl
uences its durability therefore this water should be free
from the contaminations, oil and aggressive chemical sub-
stances. Water hardness should not exceed 2°tn (1°tn = 0.71
mval/l). Too hard water causes deposition of sediment in the
boiler and heating system what decreases e
ffi
ciency and
may damage the boiler.
3. Water re
fi
lling process in the system should be stopped
when the system is full. In such case the water will
fl
ow out
from the signalling pipe of the expansion vessel, which is
located at the highest point of the system. Additional mea-
suring instrument – pressure gauge, will indicate approx.
0.8-1.2 bar. Re
fi
lling should take several seconds to make
sure that the water
fl
ows down from the vessel.
4. Close boiler drain cock and disconnect
fl
exible hose from the
boiler when the system is
fi
lled.
3.5.2. Re
fi
lling system with water
Heating system with open container allows direct contact of
heating water with the air what results in evaporation and ne-
cessity to re
fi
ll it.
NOTE! It is forbidden to add cold water to the hot system.
Adding water to hot components of the boiler may dam-
age it and is synonymous with loss of warranty.
The system can be re
fi
lled with water only when the boiler is
cold. Firing up should be restarted after
fi
lling the system.
3.5.3. Draining water from the system
It is not recommended to drain the water from the system after
the heating season because it increases the risk of occurrence
of the corrosion and formation of boiler scale. The exception
is a time needed to carry out necessary repair and long-term
standstills of the boiler during strong frosts. In the latter case it is
recommended to drain the water from the system to avoid freez-
ing and therefore damages and re
fi
lling it when the frost is over.
Содержание KSR Beta Pelet 16
Страница 1: ...Operation and maintenance manual for KSR Beta Pelet series boilers with feeders ...
Страница 20: ......
Страница 21: ......
Страница 23: ......
Страница 25: ......
Страница 26: ......
Страница 27: ...3 This sign indicates relation to safety issues This sign indicates relations to module functional features ...
Страница 54: ......
Страница 55: ......
Страница 56: ......
Страница 57: ...1 ...
Страница 58: ...2 ...
Страница 72: ...16 ...
Страница 73: ...17 ...
Страница 74: ...18 ...
Страница 75: ...19 ...
Страница 76: ...20 ...
Страница 77: ......
Страница 78: ......
Страница 90: ......
Страница 91: ......
Страница 92: ......
Страница 93: ......
Страница 94: ......
Страница 98: ......
Страница 99: ...USER MANUAL OF THE CONTROLLER S Control ...
Страница 109: ...17 CONTROLLER INSTALLATION AND SERVICE SETTINGS S Control ...
Страница 135: ...43 ...
Страница 136: ......
Страница 137: ...1 ...
Страница 138: ......
Страница 142: ......
Страница 143: ...USER MANUAL OF THE CONTROLLER S Control TOUCH ...
Страница 153: ...17 ...
Страница 154: ......
Страница 155: ...USER MANUAL OF CONTROLLER INSTALLATION AND SERVICE SETTINGS S Control TOUCH ...
Страница 183: ......
Страница 184: ......