EI65 OPERATOR’S AND CALIBRATION MANUAL
L-B B5L0082/PAT 031-300-190-015 REVISION D 04/15/99
16
STEP 5
For verification of the previously set values the Maximum and Minimum Boom Radius Preset
is displayed.
Push Button “OK” (10) for next step.
STEP 6
The Setting Procedure for the Boom Radius Presets is completed. The display shows the
actual crane data. To remind the crane operator of the activated Boom Radius Preset the
display of the actual boom radius shows a intermitted colon.
3.1.2 Setting of Boom Height Presets
STEP 1
This message appears after pushing the Button “LIMIT” (8). For activating the Setting
Procedure of Boom Height Limits the operator has to push Button “DOWN” (11) three times
to skip the length, angle and radius preset setting procedure.
Push Button “DOWN” (11) 3 times for next step.
STEP 2
To select the Boom Height Preset Programming Procedure push the button “OK” (10).
Push Button “OK” (10) for next step.
To skip the high preset limit push the button “DOWN” (11).
Step 3 to 6 will be skipped, when the Button DOWN is pressed. The system continues with
Load Limit Preset Programming Procedure (see Section 4.3.5)
STEP 3
The actual value of the Minimum Boom Height Preset is displayed.
To enter a new value of the Minimum Boom Preset, the operator has to push the button “UP”
(12) for increase and the button “DOWN” (11) for decrease the displayed value.
If the crane operator wants to continue with the displayed value, he has to confirm by
pushing the button “OK” (10).
Push Button “OK” (10) for next step.
STEP 4
The actual value of the Maximum Boom Height Preset is displayed.