SYSTEM START-UP AND CONFIGURATION
50
Parker Automation Controller Installation Guide
Configure EtherCAT_Master Node
1.
In the Devices tree, double click the EtherCAT_Master node to bring up the EtherCAT_Master
Configuration dialog.
2.
Ensure that the Autoconfig Master/Slave checkbox is checked.
3.
Change the Distributed Clock Cycletime to the EtherCAT cycle time that you wish to achieve.
(2000 usec in this example). For an EtherCAT network that includes a Compax3, the Distributed
Clock Cycletime should not be lower than 500 usec and must be a multiple of 250 usec. A
Distributed Clock Cycletime of 1000 usec is a reasonable starting point.
4.
Check the Sync Window Monitoring checkbox and set the Sync window to 50.
Configuration of the PACIO (Online Method)
1.
Ensure that you are connected to the PAC (See Connection to the PAC).
2.
Right-
EtherCAT_Master (PAC320 EtherCAT Master)
ee and select
.
Содержание PAC
Страница 11: ...CHAPTER 1 Product Overview...
Страница 18: ......
Страница 19: ...CHAPTER 2 Installation...
Страница 33: ...CHAPTER 3 System Start up and Configuration...
Страница 69: ...CHAPTER 4 PACIO Modules...
Страница 143: ...2 After adding the device and code to the project you will configure the IO map as displayed...
Страница 155: ...PAC with 400XR series...
Страница 156: ...PACIO MODULES 156 Parker Automation Controller Installation Guide...
Страница 157: ...PAC with 400LXR...
Страница 158: ...PACIO MODULES 158 Parker Automation Controller Installation Guide PAC with SMH sensors...
Страница 159: ...CHAPTER 5 Communication Interfaces Optional...
Страница 176: ......
Страница 177: ...CHAPTER 6 Troubleshooting...
Страница 188: ...TROUBLESHOOTING 188 Parker Automation Controller Installation Guide...
Страница 189: ...APPENDIX A PAC System Specifications...
Страница 195: ...APPENDIX B Additional Information...