NOTE: Make sure that configuring on the EtherCAT side and the PROFIBUS side must be
implemented identically.
PROFIBUS
To configure the PROFIBUS you need Park6943.GSD. This is to be imported into the PROFIBUS-master
configurator.
Four Modules with a maximum data area length of 160 bytes for each direction can be selected. The
individual Modules are consistent for itself. The Module provides the following Module-specific diagnosis
data "Ext_Diag_Data".
Octet
Value
Meaning
1..4
Standard diagnosis
5
0x43
Standard diagnosis: Module Id.# 6943
6
0x69
7
3
3 (1+2) Byte extended Diagnose
8
0
EtherCAT is running
6
EtherCAT Error
9
0x11
Revision 1
0x12
Revision 2 (with DP-address change)
EtherCAT
For EtherCAT configuration, import the file ParkerEtherCATModules.xml into the PAC320 master
configurator. See also Chapter 4: System Set-up and Configuration.
NOTE: Online-configuration (Scan Boxes = Reading of the configuration data from the connected
EtherCAT devices) is not possible because of the large amount of data.
For the configuration of the EtherCAT, appropriate PDOs are available.
Index
Input variable
Index
Output variable
0x1601
Module Control
0x1A01
Module Status
0x1602
Module Specific Messages
0x1A02
SPC3address_Adress
0x1603
Profibusdata_InByteM1_0 . _15
0x1A03
Profibusdata_OutByteM1_0 . _15
0x1604
Profibusdata_InByteM2_0 . _31
0x1A04
Profibusdata_OutByteM2_0 . _31
0x1605
Profibusdata_InByteM3_0 . _47
0x1A05
Profibusdata_OutByteM3_0 . _47
0x1606
Profibusdata_InByteM4_0 . _63
0x1A06
Profibusdata_OutByteM4_0 . _63
Selection of the PROFIBUS Address
The PROFIBUS address is written into the variable "Address" of the PLC program and transmitted as PDO
1602 to the PROFIBUS-DP-Slave Module.
Содержание PAC
Страница 11: ...CHAPTER 1 Product Overview...
Страница 18: ......
Страница 19: ...CHAPTER 2 Installation...
Страница 33: ...CHAPTER 3 System Start up and Configuration...
Страница 69: ...CHAPTER 4 PACIO Modules...
Страница 143: ...2 After adding the device and code to the project you will configure the IO map as displayed...
Страница 155: ...PAC with 400XR series...
Страница 156: ...PACIO MODULES 156 Parker Automation Controller Installation Guide...
Страница 157: ...PAC with 400LXR...
Страница 158: ...PACIO MODULES 158 Parker Automation Controller Installation Guide PAC with SMH sensors...
Страница 159: ...CHAPTER 5 Communication Interfaces Optional...
Страница 176: ......
Страница 177: ...CHAPTER 6 Troubleshooting...
Страница 188: ...TROUBLESHOOTING 188 Parker Automation Controller Installation Guide...
Страница 189: ...APPENDIX A PAC System Specifications...
Страница 195: ...APPENDIX B Additional Information...