PROFINET Settings
This section is the primary requirement for appending PROFINET communication to existing systems.
Note: Acquire the PROFINET related CoDeSys GSD file for use with CoDeSys product. The file is
called GSDML-V2.1-3S - Smart Software Solutions GmbH-CoDeSys PLC-20120822.xml and by
default, it is installed at this file location:
C:\Program Files(x86)\Parker Hannifin\ParkerAutomationManager\Communication Interface
Files\Profinet GSD Files.
1.
Select PROFINET IO.
2.
Right-click on the PN-IO (X2 Port) of the PLC grid in the upper left.
3.
Click
PROFINET
.
4.
(You will see a network branch appear in the graphical display. This will allow you to add the PAC.
PROFINET device to the configuration).
5.
In the right window listing devices, select the PROFINET
.
6.
Select Additional Field Devices.
7.
Select IO.
8.
Select PAC.
9.
Select PAC PN Device and drag it to the PROFINET network branch you just created.
10.
Double click the new node.
11.
12.
13.
Assign the IP to 192.168.0.1 (note: The IP Address and the Station Name has to match the IP
Address and Device Name on the PROFINET Network within the Siemens Step 7 Software.
14.
Click OK.
15.
Click OK
16.
Expand the PAC PN Device node from the tree on the right
17.
Drag 1 Byte Digital Input to Slot 1 on the green grid on the left
18.
Drag 1 Word Digital Input to Slot 2 on the green grid on the left.
19.
Save the project.
Содержание PAC
Страница 11: ...CHAPTER 1 Product Overview...
Страница 18: ......
Страница 19: ...CHAPTER 2 Installation...
Страница 33: ...CHAPTER 3 System Start up and Configuration...
Страница 69: ...CHAPTER 4 PACIO Modules...
Страница 143: ...2 After adding the device and code to the project you will configure the IO map as displayed...
Страница 155: ...PAC with 400XR series...
Страница 156: ...PACIO MODULES 156 Parker Automation Controller Installation Guide...
Страница 157: ...PAC with 400LXR...
Страница 158: ...PACIO MODULES 158 Parker Automation Controller Installation Guide PAC with SMH sensors...
Страница 159: ...CHAPTER 5 Communication Interfaces Optional...
Страница 176: ......
Страница 177: ...CHAPTER 6 Troubleshooting...
Страница 188: ...TROUBLESHOOTING 188 Parker Automation Controller Installation Guide...
Страница 189: ...APPENDIX A PAC System Specifications...
Страница 195: ...APPENDIX B Additional Information...