PACIO-443-01 - AI4-Pt/Ni100 16 Bit
PACIO-443-03 - AI4-Pt/Ni1000 16 Bit
The PACIO AI4-Pt/Ni100 16 Bit Module has 4 analog inputs for Pt100 or Ni100 temperature sensors. It also
can measure resistances between 70 and 330
. The PACIO AI4-Pt/Ni1000 16 Bit Module has 4 analog
inputs for Pt1000 or Ni1000 temperature sensors. It also can measure resistances between 700 and 3000
.
Technical Data
PACIO AI4-Pt/Ni100 16 Bit
Part Number
PACIO-443-01
Analog inputs
4
Resolution
16 bit (resistance 0.01 temperature 0.1°C)
Pt100 measuring range
-
Ni100 measuring range
-
Resistance
Temperature drift
< ± 50ppm/°C regarding range limit
Critical frequency
typical 2 Hz
Measurement current
< 0.50 mA
Sampling frequency
> 7.75 Hz (if all channels are enabled)
Connector IO/Power
Plug 18-pole (43-026591-01)
Controller
ASIC ET1200
Baud rate
100 Mbit/s
Power supply
24 VDC -20% +25%
E-Bus load
150mA
Содержание PAC
Страница 11: ...CHAPTER 1 Product Overview...
Страница 18: ......
Страница 19: ...CHAPTER 2 Installation...
Страница 33: ...CHAPTER 3 System Start up and Configuration...
Страница 69: ...CHAPTER 4 PACIO Modules...
Страница 143: ...2 After adding the device and code to the project you will configure the IO map as displayed...
Страница 155: ...PAC with 400XR series...
Страница 156: ...PACIO MODULES 156 Parker Automation Controller Installation Guide...
Страница 157: ...PAC with 400LXR...
Страница 158: ...PACIO MODULES 158 Parker Automation Controller Installation Guide PAC with SMH sensors...
Страница 159: ...CHAPTER 5 Communication Interfaces Optional...
Страница 176: ......
Страница 177: ...CHAPTER 6 Troubleshooting...
Страница 188: ...TROUBLESHOOTING 188 Parker Automation Controller Installation Guide...
Страница 189: ...APPENDIX A PAC System Specifications...
Страница 195: ...APPENDIX B Additional Information...