Module-Specific Messages
Apart from the Module error messages, the set of messages below contains details about the current
state of the PACIO AO4-VDC/mA 12 Bit Module. These messages are automatically reset when the state
concerned has returned to normal. They are combined into a single "Specific_Error" state of the Module
and output to the IO LED as "Module-
Variable
Data type Explanation
Channel_n_Shortcut
BOOL
Voltage mode: channel n load is < 600
Specific_Error = TRUE
Channel_n_Open
BOOL
Current mode: channel n load is > 500
Specific_Error = TRUE
Channel_n_Overtemp BOOL
Temperature of output driver of channel n is > 140°C (automatic switch-off)
Outputs_Active_Shortcut = TRUE
Undervoltage_24
BOOL
Power supplied to Module is < 19.2V
Outputs_Active_Undervoltage = TRUE
Conversion Time
The PACIO AO4-VDC/mA 12 Bit Module has a set cycle time of 320µs that is not affected by the number of
active channels. The cycle time is the time between receipt of the output values and the start of the D/A
converters.
Содержание PAC
Страница 11: ...CHAPTER 1 Product Overview...
Страница 18: ......
Страница 19: ...CHAPTER 2 Installation...
Страница 33: ...CHAPTER 3 System Start up and Configuration...
Страница 69: ...CHAPTER 4 PACIO Modules...
Страница 143: ...2 After adding the device and code to the project you will configure the IO map as displayed...
Страница 155: ...PAC with 400XR series...
Страница 156: ...PACIO MODULES 156 Parker Automation Controller Installation Guide...
Страница 157: ...PAC with 400LXR...
Страница 158: ...PACIO MODULES 158 Parker Automation Controller Installation Guide PAC with SMH sensors...
Страница 159: ...CHAPTER 5 Communication Interfaces Optional...
Страница 176: ......
Страница 177: ...CHAPTER 6 Troubleshooting...
Страница 188: ...TROUBLESHOOTING 188 Parker Automation Controller Installation Guide...
Страница 189: ...APPENDIX A PAC System Specifications...
Страница 195: ...APPENDIX B Additional Information...