
Installing an Optional AC Power Supply
PAC Systems operate on 24 VDC input nominal power. You can purchase an optional PS-60W Power
Supply available from Parker to provide 24VDC input power if DC machine power is not available.
The optional Parker PS-60W power supply has the following ratings:
Parker PS-60W AC/DC Power Supply Specifications
INPUT
AC Voltage, Nominal
115/230 VAC Auto Select
AC Voltage Range
85-264 VAC
Frequency Range
47-63 Hz
Nominal Current
1.3A / 0.7A
Inrush Current (max)
Typ. < 25A
OUTPUT
DC Voltage, Nominal
24VDC, (22.5 28.5VDC adj.)
DC Current, Nominal
2.5A (60W)
Overvoltage Protection
>30VDC, but <33VDC, auto recovery
GENERAL
Environmental Rating
IP20, Indoor Use Only
Pollution Degree 2
Agency Certifications
Class 2 per UL 1310, CSA C22.2 No. 223
UL508, CSA C22.2 No. 107.1
CE Low Voltage Directive, IEC/EN60950-1, 2nd
Edition
RoHS Compliant
Temperature, Storage
-25°C to +85°C
Temperature, Operating
-10°C to +60°C Convection cooling, no forced
air required
Operation up to 50% load permissible with
sideways or front side up mounting orientation.
Relative Humidity
<90% RH, non-condensing IEC 68-2-3, 68-2-3
Overvoltage
Category II
Protection/Safety
Protected against continuous short-circuit,
overload, open-circuit.
Protection Class 1 (IEC536), degree of
protection IP20 (IEC 529)
Safe low voltage: SELV (acc. EN60950)
INSTALLATION
Fusing, Input
Internally Fused, External 10A slow acting fuse
recommended
Mounting
Snap-on system to DIN Rail EN 50022, 35 x 7.5
or 35 x 15
Input Connections
16-10 AWG (1.5 6 mm
2
) Solid Conductors
16 -12 AWG (0.5 4 mm
2
) Flexible Conductors
Output Connections
16-10 AWG (1.5 6 mm
2
) Solid Conductors
16 -12 AWG (0.5 4 mm
2
) Flexible Conductors
Clearance, cooling
25mm above and below, 25mm left and right,
10mm front
Dimensions H, W, D in. (mm)
4.88 x 1.97 x 4.55 (124 x 50 x 116mm)
If you provide your own machine power or a separate AC/DC power supply, the nominal input to the PAC
Controller and up to approximately 20 PACIO Modules is 24VDC @ 1.2A or a total of 29 Watts.
CAUTION: Do not apply AC line input power directly to the PAC Controller,
or damage may occur.
Содержание PAC
Страница 11: ...CHAPTER 1 Product Overview...
Страница 18: ......
Страница 19: ...CHAPTER 2 Installation...
Страница 33: ...CHAPTER 3 System Start up and Configuration...
Страница 69: ...CHAPTER 4 PACIO Modules...
Страница 143: ...2 After adding the device and code to the project you will configure the IO map as displayed...
Страница 155: ...PAC with 400XR series...
Страница 156: ...PACIO MODULES 156 Parker Automation Controller Installation Guide...
Страница 157: ...PAC with 400LXR...
Страница 158: ...PACIO MODULES 158 Parker Automation Controller Installation Guide PAC with SMH sensors...
Страница 159: ...CHAPTER 5 Communication Interfaces Optional...
Страница 176: ......
Страница 177: ...CHAPTER 6 Troubleshooting...
Страница 188: ...TROUBLESHOOTING 188 Parker Automation Controller Installation Guide...
Страница 189: ...APPENDIX A PAC System Specifications...
Страница 195: ...APPENDIX B Additional Information...