P120
:
2
nd
change point frequency 1
P121
:
2
nd
change point voltage 1
P122
:
2
nd
change point frequency 2
P123
:
2
nd
change point voltage 2
Used to set change points 1 and 2 set with 3C mode in "P005: V/F mode".
(These parameters are valid only when parameter P005 is set to "3C".)
[Parameter P120: 2
nd
change point frequency 1]
[Parameter P121: 2
nd
change point voltage 1]
0.5 to 400.0
Data setting range (Hz)
0 to 100
Data setting range (%)
[Parameter P122: 2
nd
change point frequency 2]
[Parameter P123: 2
nd
change point voltage 2]
0.5 to 400.0
Data setting range (Hz)
0 to 100
Data setting range (%)
100
Output
voltage
(%)
Output frequency (Hz)
Max. output frequency (P008)
2
nd
change point frequency 2
(P122)
2
nd
change point
frequency 1
(P120)
2
nd
change point
voltage 1 (P121)
Base frequency 2 (P116)
2
nd
change point
voltage 2 (P123)
0
Note
・
Read carefully details on "P005: V/F mode" before setting.
・
If 2
nd
change point frequencies 1 and 2 are set to be higher than base frequency, 2
nd
change
point frequencies 1 and 2 will operate according to setting value of base frequency.
・
If 2
nd
change point frequency 2 is set to be lower than 2
nd
change point frequency 1, 2
nd
change
point frequency 2 will operate according to setting value of 2nd change point frequency 1.
・
When setting "P117: Torque boost level 2", if 2
nd
change point voltage 1 and 2 is set to be lower
than torque boost level 2, 2
nd
change point voltage1 and 2 will operate according to setting
value of torque boost level 2.
・
If 2
nd
change point voltage 2 is set to be lower than 2
nd
change point voltage 1, 2
nd
change point
voltage 2 will operate according to setting value of 2
nd
change point voltage 1.
122
P005, P008, P036
~
P040
P116, P117
相关
参数
Related
parameters