For VF100, the Following Three Operating Methods Are Available.
Use communication command sent by external machine through RS485 to
operate the inverter.
(Refer to page 63, page 134, and pages154 to 195)
Use control circuit terminal to operate the inverter (Refer to page 63).
Use buttons and potentiometer on operation panel to operate the inverter.
1. Operation panel
2. External control operation
3. Communication (RS485)
There are following two methods for setting the frequency with the operation panel.
7-1. Setting the Frequency with the Operation Panel
①
Potentiometer setting method (Parameter P004 set to "0": factory setting)
Set with the rotation angle of the frequency setting dial on the panel. The operation
will stop at the Min. position (OV stop: refer to page111), and the maximum frequency
will be attained at the Max. position.
②
Digital setting method (Parameter P004 set to "1")
Press the MODE button on the panel to enter the frequency setting mode (display:
Fr). Press the SET button, display the frequency to be set with the UP button and
DOWN button, and then press the SET button to enter the data.
The following MOP function can also be used to set frequency during operation.
「
MOP function
」
The frequency can be changed by holding down the UP button or DOWN
button during operation. This MOP function cannot be used when parameter
P003 is set to "1".
There are following two methods for setting forward/reverse run operation with
the operation panel.
7-2. Setting Forward/Reverse Run Operation with the Operation Panel
①
Forward run/reverse run method (Parameter P003 set to "1")
Press the UP (forward run) button or DOWN (reverse run) button on the panel to
select the rotation direction. Operation will start when the RUN button is pressed.
* The inverter will not start running just by pressing the RUN button.
* The MOP function cannot be used if the frequency is set with the digital method.
27