Setting signal of analog input terminal 2 (control circuit terminal No.16) can be selected.
P125
:
Analog input signal select 2
Terminals No.16 and 15 (16 : + , 15 : - ) 200
Ω,
is connected
between 16 and 15.
Terminals No.16 and 15 (16 : + , 15 : - )
4~20mA(Current signal)
5
Terminals No.16 and 15 (16 : + , 15 : - ) 200
Ω,
is connected
between 16 and 15.
0~20mA(Current signal)
6
Terminals No.16 and 15 (16 : + , 15 : - )
0~10V(voltage signal)
4
0~5V(voltage signal)
3
Operation method and control terminal connection diagram
Details on setting signal
Data
setting
value
Note
・
If 4~20mA or 0~20mA signals are used, always connect a "200
Ω
, resistance" between terminals
No.16 and 15.
(If the 200
Ω
, resistance is not connected, the inverter could be damaged.)
・
Start or stop of operation is divided by setting value of "P101: 0V Stop function select".
If 0V stop function is set to be invalid, parameter P101 should be set to "0000"
(0V stop function select: Refer to page 111)
124
P101, P124
P126, P127