Max. output frequency is the setting value
of parameter P005 (V/F mode) or parameter
P008 (Max. output frequency).
P116
:
Base frequency 2
2
nd
characteristics select button can be used to select and set base frequency 2.
(It is valid when Parameter P005 is set to "FF" or "3C".)
[Parameter P116: Base frequency 2]
Base frequency 2
(P116)
0
100
Max. output frequency
(P008)
Output frequency(Hz)
(%)
Output
voltage
45.0 to 400.0
Data setting range (Hz)
Note
・
If "P005: V/F mode" is set to "50" or "60", the max. output frequency and base frequency are
fixed value.
・
A frequency higher than "P100: upper frequency clamp" cannot be output.
・
If a general-purpose motor with a rated frequency of 50 or 60Hz is run at a frequency exceeding
the rated frequency, the motor may be damaged. Always set the frequency to match the motor
characteristics.
・
If the base frequency is required to be changed together with the max. output frequency for a
high-speed exclusive motor, etc., such change is done with this parameter.
・
When running a general-purpose motor with a frequency higher than the universal frequency,
the base frequency will be set to the normal motor's rated output frequency(50 or 60Hz).
・
When using the general-purpose motor at a level higher than the base frequency (normally
50 or 60Hz), the motor will enter the constant output characteristics, and the generated torque
will drop in inverse proportion to the frequency.
119
P005, P008, P036
~
P040
P100, P117, P120
~
P123
相关
参数
Related
parameters
(Parameter P005 is valid only when "FF" or "3C" is set.)