P117
:
Torque boost level 2
2
nd
characteristics select button can be used to select and set the torque boost level 2.
A larger value causes a higher the output voltage and stronger boost.
0
Output
frequency (Hz)
Base frequency
2 (P116)
100
[Constant torque mode]
Output
voltage
(%)
Boost
level
0
Output
frequency (Hz)
100
[Square torque mode]
Output
voltage
(%)
Boost
level
0 to 40
Data setting range (%)
Note
・
If the boost level is too high, an overcurrent fault, overload fault or motor overheating could
occur or the noise could increase.
・
The motor current will increase when the value of boost level is increased. Carefully consider
the settings for "P118: Electronic thermal select 2"and "P119: Thermal current setting 2".
・
Under control of vector (P129= "1"), torque boost level 2 is invalid.
Base frequency
2 (P116)
120
P005, P008, P036
~
P040
P116, P118
~
P123
相关
参数
Related