P092
:
Output RY function select
Used to set the functions of the relay output (control terminals A, B and C).
Setting data
ON when timer operates one cycle (only output during wait time)
End of timer's
one cycle
operation
r9
9
ON when timer's operation ends (when "tEnd" is displayed)
End of timer's
operation
r10
10
ON when the inverter is in the fault trip state
Fault alarm (1)
r7
7
ON when the inverter is in the normal state
(OFF when the inverter is in the fault trip state)
Fault alarm (2)
r8
8
ON when output current is lower than detect current level
(parameter P095 setting )
Current
detect (2)
r6
6
5
4
3
2
1
0
Energize
in
on-state
r5
r4
r3
r2
r1
r0
Non
energize
in on-state
Current
detect (1)
Frequency
detect
Overload
alarm
Arrival signal
Reverse
run signal
Run signal
Function
ON when output current is higher than detect current level
(parameter P095 setting)
ON when the inverter is running in reverse
ON when the output frequency is within the setting
frequency
±
2Hz
ON when the output current is 140% of the rated current or
higher or when the electronic thermal level is reached.
ON when output frequency is higher than detect frequency
(parameter P094 setting )
ON when run signal is ON or during inverter output
Conditions for relay to turn ON
・
Energize in ON-state: The relay is turned ON when the coil is excited.
(The signal ON-state= Across terminals A-C: ON, across terminals B-C: OFF)
・
Non energize in ON-state: The relay is turned ON when the coil is not excited.
(The signal ON-state= Across terminals A-C: OFF, across terminals B-C: ON)
・
Retardation time of current detect signal set to "5" and "6" can be set with "P096: Retardation
time of current detect".
Note
・
Setting data "10" is used to output the time set with "P070: Continuous wait time of timer's operation".
106
P070
P094
~
P096
Related
parameters