Control Functions
1
8. Outdoor Fan Control
8-1. Fan mode
These outdoor units utilize a DC fan motor that can be controlled in a maximum of 16 steps (16 modes).
However, fan modes 15 and 16 can only be used if high static-pressure mode has been set.
* For information concerning EEPROM settings, refer to the field application functions.
8-2. Outdoor Fan Min. Fan Mode and Max. Fan Mode
Min. fan mode
Max. fan mode
Cooling operation
Outdoor air temp.
>
15°C: 1
Outdoor air temp.
≤
15°C: 0
14
Heating operation
1
14
* Even if the fan mode is 0 during cooling operation, the fan mode may change to 1 at regular intervals for
temperature protection of the inverter hybrid IC.
8-3. Fixed Initial Fan Mode
For the first 30 seconds after operation starts, the mode is fixed at the initial mode which was calculated from the
relationship between the outdoor air temperature and the outdoor unit horsepower.
If the outdoor unit horsepower changes dramatically, the initial mode may be recalculated and may be again fixed
for 30 seconds.
8-4. Operation after Fixed Initial Fan Mode
After the fixed initial fan mode, the fan mode is increased or decreased according to the operating conditions.
(1) Cooling mode at all indoor units, or else mixed heating/cooling operation when the outdoor unit is functioning
as a condenser
(A) Fan mode is increased when the pressure sensor temperature is high, and is decreased when the pressure
sensor temperature is low.
* The fan mode is always increased when the pressure sensor temperature is 50°C or higher.
(B) The fan mode may be decreased when symptoms of insufficient gas are detected at an indoor unit.
(2) Heating mode at all indoor units, or else mixed heating/cooling operation when the outdoor unit is functioning
as an evaporator
(A) If the condensation temperature is low, the fan mode is increased at regular intervals.
(B) If the condensation temperature is high, the fan mode is decreased in order to prevent excessive loads.
(C) The fan mode may be increased when the outdoor liquid temperature drops to 7°C or below.
8-5. Snow Removal Control
(1) When the outdoor air temperature is 10°C or below, the fan operates for 30 seconds every 2 hours in fan mode
8, even when the outdoor unit is stopped or the heat exchanger is not in use. This control is intended to prevent
snow from accumulating on stopped fans. (Because the outdoor air temperature cannot be accurately detected
when the unit is stopped, a higher outdoor air temperature is used for the control condition, in order to ensure
correct operation.)
(2) If the fan mode becomes 0 during cooling operation, the fan mode is changed to 1.
* This control is predictive control. Use a snowfall sensor as necessary according to the installation conditions.
8-6. When the Compressor Magnet Switch Seizing Alarm Occurs
Because there is the possibility that the high pressure has increased, the fan operates in Max. fan mode.
8-7. Other
This unit includes settings for high static-pressure and for Quiet mode.
For information about these settings, refer to the field application functions.
SM830188-00̲3WAY.indb 21
SM830188-00̲3WAY.indb 21
2011/03/01 11:55:20
2011/03/01 11:55:20
Содержание U-10MF1E8
Страница 44: ...MEMO 1 38 SM830188 00 3WAY indb 38 SM830188 00 3WAY indb 38 2011 03 01 11 55 23 2011 03 01 11 55 23...
Страница 98: ...MEMO 3 14 SM830188 00 3WAY indb 14 SM830188 00 3WAY indb 14 2011 03 01 11 56 28 2011 03 01 11 56 28...
Страница 148: ...MEMO 5 32 SM830188 01 3WAY indb 32 SM830188 01 3WAY indb 32 2011 11 15 23 04 33 2011 11 15 23 04 33...
Страница 149: ...201111 SM830188 01 3WAY indb 1 SM830188 01 3WAY indb 1 2011 11 15 23 23 06 2011 11 15 23 23 06...