3-WAY SYSTEM
Control Functions
1
- 12
1
4. Special Controls
4-2-3. Flow of system refrigerant oil recovery control
(1) Simplified flow of system refrigerant oil recovery control
System refrigerant oil recovery control follows this flow:
Normal operation
3-minute stop (May stop for 6 minutes.) System refrigerant oil recovery control (Max. 3
minutes)
3-minute stop
Normal operation
(2) Cooling cycle
Control time
Maximum 3 minutes (Stops once before and once after control.)
Outdoor units
All outdoor units operate at maximum horsepower.
Indoor
units
Electronic control valve Valves at all indoor units operate at a fixed pulse according to the indoor unit capacity.
RAP valve kit
Valve kits at all indoor units operate in Cooling mode (OFF status.)
Fan
Fan operates at the set fan speed, stops, or operates at L speed, depending on the
indoor unit operation mode.
(3) Heating cycle
Control time
Maximum 3 minutes (Stops once before and once after control.)
Outdoor units
All outdoor units operate at maximum horsepower.
Indoor
units
Electronic control valve Valves at all indoor units operate at 480 pulses.
RAP valve kit
Valve kits at all indoor units operate in Heating mode (ON status).
Fan
Fan operates at the set fan speed, stops, or operates at L speed, depending on the
indoor unit operation mode.
4-3. Defrost Control
4-3-1. Defrost control method
This system uses the following 2 defrost methods.
(1) If there is 1 outdoor unit in the refrigerant system: Reverse cycle defrost
(2) If there are 2 or more outdoor units in the refrigerant system: Outdoor unit cycle defrost
4-3-2. Constraint conditions
(1) Frost detection does not occur for 5 minutes after operation starts.
(2) Defrost does not begin again for 35 minutes of A/C operation after defrost was once completed.
(3) If all indoor units are stopped while defrost control is in effect, or if the outdoor unit is stopped due to protection
control or another reason, then defrost control will not start for a minimum of 10 minutes after restart occurs.
4-3-3. Frost detection
(A) Frost detection does not occur for 5 minutes after operation starts.
(B) Frost is detected when either condition 1 or 2 below is met.
Condition 1: L2 line or below is detected twice, each time continuously for 4 minutes, when the compressor is
operating.
Condition 2: L1 line or below is detected for a total of 60 minutes when the compressor is operating.
–25
–23
–10
L2
L1
–3
–21.4
–8
–1
6
10
Heat exchange liquid temperature °C
Defrosting operation
end temperature
(The end temperature is different from the
above detection temperature.)
External temperature °C
The frost detection area is
located under the thick lines
SM830188-00̲3WAY.indb 12
SM830188-00̲3WAY.indb 12
2011/03/01 11:55:19
2011/03/01 11:55:19
Содержание U-10MF1E8
Страница 44: ...MEMO 1 38 SM830188 00 3WAY indb 38 SM830188 00 3WAY indb 38 2011 03 01 11 55 23 2011 03 01 11 55 23...
Страница 98: ...MEMO 3 14 SM830188 00 3WAY indb 14 SM830188 00 3WAY indb 14 2011 03 01 11 56 28 2011 03 01 11 56 28...
Страница 148: ...MEMO 5 32 SM830188 01 3WAY indb 32 SM830188 01 3WAY indb 32 2011 11 15 23 04 33 2011 11 15 23 04 33...
Страница 149: ...201111 SM830188 01 3WAY indb 1 SM830188 01 3WAY indb 1 2011 11 15 23 23 06 2011 11 15 23 23 06...