3-WAY SYSTEM
Control Functions
1
10. Indoor Unit Control of the Electronic Control Valve
10-1. Normal Control
(1) Except Type E1
(1) Type E1
*1 The SH target value is controlled so that the difference [E3 - E1] can become 2 - 6°C, depending on the
operation conditions. However, a decline in the required level may cause the SH target value to increase.
Be aware that in this case, the electronic control valve is intended to close and this will be wrongly identified
as gas shortages.
*2 The SC target value is controlled so that the difference [pressure temp. sensor E1] can become 5 - 20°C,
depending on the operating conditions.
*3 In the case of the common use electronic valve kit and more than one (1) indoor unit in the heating mode
within the same electronic valve kit, performs the control of returning the liquid refrigerant
gradually into the outdoor unit in the range of 55 - 80 pulses.
*4 The SC target value is controlled so that the difference [pressure temp. sensor - E1] can become 5 - 20°C,
depending on the operating conditions. However, if installation is combined with the except type E1,
the value is controlled so that the difference [pressure temp. sensor - E1] can become 5 - 40°C.
Remote
Controller
Mode
Position of electronic control valve
Outdoor unit operation
Outdoor unit
stopped
Thermostat ON
Thermostat OFF
Thermostat ON
Thermostat OFF
Thermostat ON
Thermostat OFF
Thermostat ON
Thermostat OFF
Fan
Stop
Cooling
Heating
Auto
Auto. Cooling
Auto. Heating
Performs SH control in the range of 55 - 480 pulses. *1
20 pulses
20 pulses
Performs SC control in the range of 55 - 480 pulses. *2
Returns the liquid refrigerant gradually into the outdoor
unit in the range of 55 - 80 pulses.
Performs SH control in the range of 55 - 480 pulses. *1
20 pulses
Performs SC control in the range of 55 - 480 pulses. *2
Returns the liquid refrigerant gradually into the outdoor
unit in the range of 55 - 80 pulses.
20 pulses *3
20 pulses *3
85 pulses
20 pulses
20 pulses
85 pulses
85 pulses
20 pulses
20 pulses
Remote
Controller
Mode
Position of electronic control valve
Outdoor unit operation
Outdoor unit
stopped
Thermostat ON
Thermostat OFF
Thermostat ON
Thermostat OFF
Thermostat ON
Thermostat OFF
Thermostat ON
Thermostat OFF
Fan
Stop
Cooling
Heating
Auto
Auto. Cooling
Auto. Heating
Performs SH control in the range of 55 - 480 pulses. *1
20 pulses
20 pulses
Performs SC control in the range of 55 - 480 pulses. *4
20 pulses
Performs SH control in the range of 55 - 480 pulses. *1
20 pulses
Performs SC control in the range of 55 - 480 pulses. *4
20 pulses
20 pulses
20 pulses
20 pulses
20 pulses
20 pulses
85 pulses
20 pulses
20 pulses
20 pulses
SM830188-00̲3WAY.indb 23
SM830188-00̲3WAY.indb 23
2011/03/01 11:55:21
2011/03/01 11:55:21
Содержание U-10MF1E8
Страница 44: ...MEMO 1 38 SM830188 00 3WAY indb 38 SM830188 00 3WAY indb 38 2011 03 01 11 55 23 2011 03 01 11 55 23...
Страница 98: ...MEMO 3 14 SM830188 00 3WAY indb 14 SM830188 00 3WAY indb 14 2011 03 01 11 56 28 2011 03 01 11 56 28...
Страница 148: ...MEMO 5 32 SM830188 01 3WAY indb 32 SM830188 01 3WAY indb 32 2011 11 15 23 04 33 2011 11 15 23 04 33...
Страница 149: ...201111 SM830188 01 3WAY indb 1 SM830188 01 3WAY indb 1 2011 11 15 23 23 06 2011 11 15 23 23 06...