3-WAY SYSTEM
Control Functions
1
- 32
1
17. Backup Operation
[2] Disabling operation of 1 compressor
At the S010 switch on the PCB of the failed outdoor unit, turn ON the switch for the compressor to disable, and
turn ON the “backup” switch.
<S010 switch>
• In order to perform simultaneous backup operation for 2 or more compressors, use a combination of the switch
settings shown above.
INV
AC1
AC2
Backup
ON
OFF
(A) Compressor 1 backup
(B) Compressor 2 backup
(C) Compressor 3 backup