6. Mode Settings
■
Setting mode 2
<Operating procedure>
➀
Press and hold the
(CHECK) button,
button, and
button
simultaneously for 4 seconds or longer.
➁
Use the temperature setting
and
buttons to change the item
code. The item codes and setting data are shown in the table below.
➂
Use the timer time
and
buttons to change the setting data.
To confirm the changed setting data, press the
button.
(At this time, “
” stops blinking and remains lit.)
➃
During this mode, “
” is displayed, blinking. The display shows the set
outdoor unit address “System XX-YY” (System XX = System address, YY =
Address at outdoor unit sub-bus), item code number (DN value in the table
below), and the setting data (8 digits).
(The setting data is displayed in 8 digits. The display changes between the first 4 digits (Fig.
A
) and the last 4
digits (Fig.
B
). When the first 4 digits are displayed, the bottom dot of the colon is lit.)
➄
To end the setting mode, press the
(CHECK) button. The display returns to the normal display mode.
A
B
1
5
3
2
List of Item Codes
DN
Parameter
Description
81
Outdoor unit capacity
0 = Disabled 224 = 8 hp 280 = 10 hp 355 = 12 hp 400 = 14 hp
450 = 16 hp
1
2
5
3
Display of fi rst 4 digits
<Refrigerant type>
A
and
B
are displayed alternately. (Example
shows 0000 0410 (R410A).)
Display of last 4 digits
Fig. 6
SM830188-00̲3WAY.indb 13
SM830188-00̲3WAY.indb 13
2011/03/01 11:56:26
2011/03/01 11:56:26
Содержание U-10MF1E8
Страница 44: ...MEMO 1 38 SM830188 00 3WAY indb 38 SM830188 00 3WAY indb 38 2011 03 01 11 55 23 2011 03 01 11 55 23...
Страница 98: ...MEMO 3 14 SM830188 00 3WAY indb 14 SM830188 00 3WAY indb 14 2011 03 01 11 56 28 2011 03 01 11 56 28...
Страница 148: ...MEMO 5 32 SM830188 01 3WAY indb 32 SM830188 01 3WAY indb 32 2011 11 15 23 04 33 2011 11 15 23 04 33...
Страница 149: ...201111 SM830188 01 3WAY indb 1 SM830188 01 3WAY indb 1 2011 11 15 23 23 06 2011 11 15 23 23 06...