3-WAY SYSTEM
Remote Controller Functions
4
- 10
2. Detailed Settings Function
4
Item code
Item
Description
03
Central control address
Set when using a central control device.
Used when setting the central control address manually from the
remote controller.
04
Operating mode priority change
Note (1)
NOTE
(1) Explanation of operation mode priority change
Enabled only in 2WAY System heat-pump models.
<Function>
With indoor units that are installed in combination with an outdoor unit model where either heating or cooling
operation can be selected, the operating mode of the indoor unit that starts first takes priority. The first indoor unit
to operate can select any operating mode. When any mode other than fan mode is selected, then the operating
modes that cannot be selected are not displayed on all remote controllers that are subsequently operated.
“Operation change control in progress” is displayed, indicating that there are restrictions on the operating
modes that can be selected.
Controlling the operating mode from a specific remote controller
- When there are multiple remote controllers in the same refrigerant system, it is possible to set one remote
controller as the priority remote controller (the remote controller which is given priority for selecting the
operating mode). (If 2 or more remote controllers are set as priority remote controllers, an alarm will occur at
the remote controllers, and operation will not be possible.)
- When the priority remote controller is set to the operating mode for control, then all other remote controllers can
select only the permitted operating mode, regardless of whether the priority remote controller is operating or
stopped.
- When a controlled remote controller is operated, “Operation change control in progress” is displayed.
Set mode at priority remote controller
Modes that can be selected at other remote controllers
Cooling or dry
Cooling, dry, fan
Heating
Heating, fan
Fan
Whichever mode (heating/cooling) is selected fi rst
NOTE
There are other methods to avoid control in which the mode selected first takes priority.
Methods of remotely controlling the operating mode
(1) Use the central functions of a central control device.
(2) Use a remote control relay PCB at the outdoor unit.
•
SM830188-00̲3WAY.indb 10
SM830188-00̲3WAY.indb 10
2011/03/01 11:56:45
2011/03/01 11:56:45
Содержание U-10MF1E8
Страница 44: ...MEMO 1 38 SM830188 00 3WAY indb 38 SM830188 00 3WAY indb 38 2011 03 01 11 55 23 2011 03 01 11 55 23...
Страница 98: ...MEMO 3 14 SM830188 00 3WAY indb 14 SM830188 00 3WAY indb 14 2011 03 01 11 56 28 2011 03 01 11 56 28...
Страница 148: ...MEMO 5 32 SM830188 01 3WAY indb 32 SM830188 01 3WAY indb 32 2011 11 15 23 04 33 2011 11 15 23 04 33...
Страница 149: ...201111 SM830188 01 3WAY indb 1 SM830188 01 3WAY indb 1 2011 11 15 23 23 06 2011 11 15 23 23 06...