3-WAY SYSTEM
Trouble Diagnosis
4. 3-WAY Alarm Codes
E06 Alarm
Alarm code
E06
Alarm meaning
Outdoor unit failed to receive serial communication signals from indoor unit.
Alarm conditions
Outdoor unit failed to receive serial communication signals from indoor unit.
Probable cause
(1) The indoor unit power was cut OFF after initial communications were completed.
(2) An open circuit or short circuit occurred in the inter-unit control wiring after initial
communications were completed.
Check
Check the power at the indoor and outdoor units, and check the inter-unit control wiring.
Correction
—
Example
—
Notes
This alarm is detected after initial communications are completed. Therefore, it does not occur in
cases of “disconnected serial connector,” “no terminal unit set,” or other trouble that occurs
before initial communications are completed. If initial communications have not been completed,
alarm E04 occurs.
E12 Alarm
Alarm code
E12
Alarm meaning
Automatic address setting start is prohibited.
Alarm conditions
Automatic address setting was started when automatic address setting was in progress at
another outdoor unit in the same link.
Probable cause
Automatic address setting is in progress at another outdoor unit.
Check
This alarm is not displayed on the remote controller. Therefore check the blinking on the outdoor
unit PCB.
Correction
Wait for automatic address setting to be completed at the outdoor unit where it is currently in
progress. Then start automatic address setting again.
Example
—
Notes
—
E15 Alarm
Alarm code
E15
Alarm meaning
Automatic address setting alarm (too few units)
Alarm conditions
The number of indoor units was too few when automatic address setting was performed.
Probable cause
(1) The number of indoor units set at the indoor unit quantity setting SW (S004, S005) on the
outdoor unit PCB is too many.
(2) The inter-unit control wiring between indoor units has been cut.
Check
(1) Refer to the test run servicing materials and check the indoor unit quantity setting SW (S004,
S005).
(2) Check the inter-unit control wiring at the indoor and outdoor units.
Correction
After correcting the indoor unit quantity setting or the inter-unit control wiring, perform automatic
address setting again.
Example
—
Notes
3-WAY System switch position
S004
S005
SM830188-01̲3WAY.indb 9
SM830188-01̲3WAY.indb 9
2011/11/15 23:04:29
2011/11/15 23:04:29
Содержание U-10MF1E8
Страница 44: ...MEMO 1 38 SM830188 00 3WAY indb 38 SM830188 00 3WAY indb 38 2011 03 01 11 55 23 2011 03 01 11 55 23...
Страница 98: ...MEMO 3 14 SM830188 00 3WAY indb 14 SM830188 00 3WAY indb 14 2011 03 01 11 56 28 2011 03 01 11 56 28...
Страница 148: ...MEMO 5 32 SM830188 01 3WAY indb 32 SM830188 01 3WAY indb 32 2011 11 15 23 04 33 2011 11 15 23 04 33...
Страница 149: ...201111 SM830188 01 3WAY indb 1 SM830188 01 3WAY indb 1 2011 11 15 23 23 06 2011 11 15 23 23 06...