Outdoor Unit Repair Procedures
2
10. Compressor
(14)
(15)
(1)
(1)
CAUTION
Re-install all components that were removed. Re-install the electrical component box in the same position as
it was before.
• Be sure to securely re-install the thermal insulation and clamps for the capillary
tube assembly in their original conditions, as shown in Fig 28.
• Be sure to check for looseness of the power terminal connection at the compres-
sor terminal plate, and to check by pulling vertically on the connections. If the
terminals become disconnected easily, replace the wiring Assy.
Follow the instructions in “ 7. Evacuating System ” and apply vacuum to the outdoor unit where the compres-
sor was replaced.
(D) Replacing multiple compressors
Removal
Follow the instructions in “(A) Replacing the inverter compressor,” “(B) Replacing constant-speed compressor 1,”
and “(C) Replacing constant-speed compressor 2,” and remove the compressors.
* There is no predetermined sequence for removal; any compressor may be removed first.
Installation
Follow the instructions in “(A) Replacing the inverter compressor,” “(B) Replacing constant-speed compressor 1,”
and “(C) Replacing constant-speed compressor 2,” and install the compressors.
* There is no predetermined sequence for installation; any compressor may be installed first.
SM830188-00̲3WAY.indb 37
SM830188-00̲3WAY.indb 37
2011/03/01 11:56:00
2011/03/01 11:56:00
Содержание U-10MF1E8
Страница 44: ...MEMO 1 38 SM830188 00 3WAY indb 38 SM830188 00 3WAY indb 38 2011 03 01 11 55 23 2011 03 01 11 55 23...
Страница 98: ...MEMO 3 14 SM830188 00 3WAY indb 14 SM830188 00 3WAY indb 14 2011 03 01 11 56 28 2011 03 01 11 56 28...
Страница 148: ...MEMO 5 32 SM830188 01 3WAY indb 32 SM830188 01 3WAY indb 32 2011 11 15 23 04 33 2011 11 15 23 04 33...
Страница 149: ...201111 SM830188 01 3WAY indb 1 SM830188 01 3WAY indb 1 2011 11 15 23 23 06 2011 11 15 23 23 06...