5
5
- 29
3-WAY SYSTEM
Trouble Diagnosis
6. Inspection of Parts
(1) High-pressure switch (63PH1, 63PH2, 63PH3)
•
63PH1: Disconnect the CN042 connector (3P, WHT) from the outdoor unit control panel. Measure the resis-
tance between socket pins 1 and 3. The resistance is OK if the result is 0
Ω
.
•
63PH2: Disconnect the CN044 connector (3P, RED) from the outdoor unit control panel. Measure the resis-
tance between socket pins 1 and 3. The resistance is OK if the result is 0
Ω
.
•
63PH3: Disconnect the CN233 connector (3P, YEL) from the outdoor unit control panel. Measure the resis-
tance between socket pins 1 and 3. The resistance is OK if the result is 0
Ω
.
(2) Electronic control valve (MOV1, MOV2, MOV3, MOV4)
After removing the connector from the PCB, use the following methods to check the valves.
•
MOV1: Measure the voltage between plug pin 5 and pins 1 through 4 at the CN015 connector (6P, WHT) on
the outdoor unit control PCB. (Because of the pulse output, a simplified measurement method is used. Set
the tester to the 12 V range; if the value displayed is approximately 4 V, then the voltage is normal.)
When the voltage is normal, measure the resistance between each pair of pins on the electronic control valve
connector. The connector is normal if all results (pin 5 – pin 1, pin 5 – pin 3, pin 6 – pin 2, pin 6 – pin 4) are
approximately 46
Ω
. (If the results are 0
Ω
or
∞
, replace the coil.)
•
MOV2: Measure the voltage between plug pin 5 and pins 1 through 4 at the CN016 connector (6P, RED) on
the outdoor unit control PCB. (Because of the pulse output, a simplified measurement method is used. Set
the tester to the 12 V range; if the value displayed is approximately 4 V, then the voltage is normal.)
When the voltage is normal, measure the resistance between each pair of pins on the electronic control valve
connector. The connector is normal if all results (pin 5 – pin 1, pin 5 – pin 3, pin 6 – pin 2, pin 6 – pin 4) are
approximately 46
Ω
. (If the results are 0
Ω
or
∞
, replace the coil.)
•
MOV3: Measure the voltage between plug pin 5 and pins 1 through 4 at the CN229 connector (6P, BLK) on
the outdoor unit control PCB. (Because of the pulse output, a simplified measurement method is used. Set
the tester to the 12 V range; if the value displayed is approximately 4 V, then the voltage is normal.)
When the voltage is normal, measure the resistance between each pair of pins on the electronic control valve
connector. The connector is normal if all results (pin 5 – pin 1, pin 5 – pin 3, pin 6 – pin 2, pin 6 – pin 4) are
approximately 46
Ω
. (If the results are 0
Ω
or
∞
, replace the coil.)
•
MOV4: Measure the voltage between plug pin 5 and pins 1 through 4 at the CN230 connector (6P, BLU) on
the outdoor unit control PCB. (Because of the pulse output, a simplified measurement method is used. Set
the tester to the 12 V range; if the value displayed is approximately 4 V, then the voltage is normal.)
When the voltage is normal, measure the resistance between each pair of pins on the electronic control valve
connector. The connector is normal if all results (pin 5 – pin 1, pin 5 – pin 3, pin 6 – pin 2, pin 6 – pin 4) are
approximately 46
Ω
. (If the results are 0
Ω
or
∞
, replace the coil.)
(3) Crank case heater
•
Connect a clamp meter to 1 of the 2 crank case heater wires and measure the current. The current is normal
if the result is 0.15 A or higher. (As a guide, the current should be 0.14 A (180 V) – 0.17 A (220 V).)
SM830188-01̲3WAY.indb 29
SM830188-01̲3WAY.indb 29
2011/11/15 23:04:32
2011/11/15 23:04:32
Содержание U-10MF1E8
Страница 44: ...MEMO 1 38 SM830188 00 3WAY indb 38 SM830188 00 3WAY indb 38 2011 03 01 11 55 23 2011 03 01 11 55 23...
Страница 98: ...MEMO 3 14 SM830188 00 3WAY indb 14 SM830188 00 3WAY indb 14 2011 03 01 11 56 28 2011 03 01 11 56 28...
Страница 148: ...MEMO 5 32 SM830188 01 3WAY indb 32 SM830188 01 3WAY indb 32 2011 11 15 23 04 33 2011 11 15 23 04 33...
Страница 149: ...201111 SM830188 01 3WAY indb 1 SM830188 01 3WAY indb 1 2011 11 15 23 23 06 2011 11 15 23 23 06...