background image

85464849352001

REFERENCE NO

SM830252-01

TECHNICAL DATA

 

& SERVICE MANUAL

Outdoor Unit

Indoor Unit

S-100PU2E5A, S-125PU2E5A

Type U2

S-200PE2E5, S-250PE2E5

Type E2

High Static Pressure

Ducted Type

4-Way Cassette Type

U-200PE2E8A, U-250PE2E8A

Order No. SBPAC1607004CE

SM830252-01_欧州_Single_8・10HP_TD_SM.indb   1

16/10/07   18:27:32

AMP Air Conditioning

www.ampair.co.uk | [email protected]

Содержание S-100PU2E5A

Страница 1: ...oor Unit S 100PU2E5A S 125PU2E5A Type U2 S 200PE2E5 S 250PE2E5 Type E2 High Static Pressure Ducted Type 4 Way Cassette Type U 200PE2E8A U 250PE2E8A Order No SBPAC1607004CE SM830252 01_欧州_Single_8 10HP_TD_SM indb 1 16 10 07 18 27 32 AMP Air Conditioning www ampair co uk sales ampair co uk ...

Страница 2: ...ctions and inadequate grounding can cause accidental injury or death Connect all wiring tightly Loose wiring may cause overheating at connection points and a possible fire hazard Provide a power outlet to be used exclusively for each unit Provide a power outlet exclusively for each unit and full disconnection means having a contact separation in all poles must be incorporated in the fixed wiring i...

Страница 3: ...stbite When Servicing Turn the power OFF at the main power box mains before opening the unit to check or repair electrical parts and wiring Keep your fingers and clothing away from any moving parts Clean up the site after you finish remembering to check that no metal scraps or bits of wiring have been left inside the unit being serviced WARNING WARNING This product must not be modified or disassem...

Страница 4: ...r effective use of floor space individual control and energy conservation by curtailing heat and carrying power etc Most importantly the multi air conditioner system is able to replenish a large amount of refrigerant compared to conventional individual air conditioners If a single unit of the multi air conditioner system is to be installed in a small room select a suitable model and installation p...

Страница 5: ...tion and stop 5 7 Table of Thermistor Characteristics 5 8 How to Remove the Compressor 5 9 How to Remove the Electrical Component Box 5 10 Symptom Thermostat in OFF continues cycles OFF ON too frequently 6 1 6 2 6 2 Section 6 OUTDOOR UNIT MAINTENANCE REMOTE CONTROLLER 6 3 6 8 6 10 6 11 6 1 Overview 6 2 Functions 6 3 Normal Display Operations and Functions 6 4 Monitoring Operations Display of Indoo...

Страница 6: ...8 8 8 8 8 9 8 9 8 9 8 11 8 12 8 13 8 14 8 14 8 16 8 20 8 22 60 B ὒᕞࢩࣥࢢࣝኳᇙ60 LQGE 8 1 Names and Functions 8 2 Installing Batteries 8 3 Setting the Current Time 8 4 Operation 8 5 Timer Operation 8 6 Adjusting the Wind Direction 8 7 Operating Multiple In Outdoor Units Simultaneously Group Control 8 8 Using the Remote Controller 8 9 For Best Results 8 10 Addresses 8 11 Emergency Operation 8 12 Miscell...

Страница 7: ...10 SELECTING THE INSTALLATION SITE 1 57 11 HOW TO INSTALL THE INDOOR UNIT Type U2 1 58 1 4 Dimensional Data 1 5 Refrigerant Flow Diagram 1 6 Operating Range 1 7 Capacity Correction Graph According to Temperature Condition 1 8 Noise Criterion Curves 1 26 1 25 1 9 Airflow Distance Chart 1 10 Fresh Air Intake 1 11 ELECTRICAL WIRING 1 12 Installation Instructions 1 13 HOW TO PROCESS TUBING 1 14 VACUUM...

Страница 8: ...40 Heating m3 min m3 h 164 9840 Refrigerrant type amount g oz R410A 56 0k 197 5 Product dimension Height mm inch 479 18 27 32 1500 59 1 16 Width mm inch 1453 57 7 32 980 38 37 64 Depth mm inch 1205 47 7 16 370 14 9 16 Packing dimension Height mm inch 614 24 3 16 1642 64 41 64 Width mm inch 1536 60 15 32 1095 43 7 64 Depth mm inch 1339 52 23 32 529 20 53 64 Weight NET kg lb 100 221 127 280 GROSS kg...

Страница 9: ...m3 h 160 9600 Refrigerrant type amount g oz R410A 6 4k 225 8 Product dimension Height mm inch 479 18 27 32 1500 59 1 16 Width mm inch 1453 57 7 32 980 38 37 64 Depth mm inch 1205 47 7 16 370 14 9 16 Packing dimension Height mm inch 614 24 3 16 1642 64 41 64 Width mm inch 1536 60 15 32 1095 43 7 64 Depth mm inch 1339 52 23 32 529 20 53 64 Weight NET kg lb 104 230 138 304 GROSS kg lb 136 300 150 331...

Страница 10: ...A 5 60k 197 5 Product dimension Height mm inch 319 12 9 16 1500 59 1 16 Width mm inch 840 33 5 64 980 38 37 64 Depth mm inch 840 33 5 64 370 14 9 16 Product dimension Panel H W D mm inch 33 5 950 950 1 11 32 37 13 32 37 13 32 Packing dimension Height mm inch 365 14 3 8 1642 64 41 64 Width mm inch 898 35 3 8 1095 43 7 64 Depth mm inch 898 35 3 8 529 20 53 64 Weight NET kg lb 25 55 127 280 GROSS kg ...

Страница 11: ...0A 6 40k 225 8 Product dimension Height mm inch 319 12 9 16 1500 59 1 16 Width mm inch 840 33 5 64 980 38 37 64 Depth mm inch 840 33 5 64 370 14 9 16 Product dimension Panel H W D mm inch 33 5 950 950 1 11 32 37 13 32 37 13 32 Packing dimension Height mm inch 365 14 3 8 1642 64 41 64 Width mm inch 898 35 3 8 1095 43 7 64 Depth mm inch 898 35 3 8 529 20 53 64 Weight NET kg lb 25 55 138 304 GROSS kg...

Страница 12: ...ance Ambient temperature 20 C Ω VAC µF Run capacitor Electronic expansion valve Coil Coil resistance at 20 C Ω Valve body Heat exchanger Coil mm Rows fin pitch m Face area 2 S 200PE2E5 220 230 240V single phase 50Hz CR 280ME2E5 SIROCCO 2 ø250 DMUB6D1AC 560W DMUB6D2AC 560W 100 391 VDC 8P 860 Aluminium plate fin Copper tube 3 1 8 0 648 SM830252 01_欧州_Single_8 10HP_TD_SM indb 6 16 10 14 13 57 05 AMP ...

Страница 13: ...erature 20 C Ω VAC µF Run capacitor Electronic expansion valve Coil Coil resistance at 20 C Ω Valve body Heat exchanger Coil mm Rows fin pitch m Face area 2 S 250PE2E5 220 230 240V single phase 50Hz CR 280ME2E5 SIROCCO 2 ø250 DMUB8D1AC 560W DMUB8D2AC 560W 100 391 VDC 8P 1020 Aluminium plate fin Copper tube 4 1 8 0 648 SM830252 01_欧州_Single_8 10HP_TD_SM indb 7 16 10 14 13 57 05 AMP Air Conditioning...

Страница 14: ...ium plate fin Copper tube mm 3 1 15 Face area m2 0 560 CZ KPU3 MSBPC20A20 Coil resistance Ω 300 Ω 7 phase PMD 12D13ST 7 V W DC 13 V 4 2 W Drain piping rise height from unit bottom capacity 850 mm 400 cc min Safety device Model No Model Nominal output W Power source No of pole r p m 230V High Run capacitor Rows fin pitch Heat exchanger Coil Rated Auto louver motor Drain pump Panel Model No SM830252...

Страница 15: ...ium plate fin Copper tube mm 3 1 15 Face area m2 0 560 CZ KPU3 MSBPC20A20 Coil resistance Ω 300 Ω 7 phase PMD 12D13ST 7 V W DC 13 V 4 2 W Drain piping rise height from unit bottom capacity 850 mm 400 cc min Safety device Model No Model Nominal output W Power source No of pole r p m 230V High Run capacitor Rows fin pitch Heat exchanger Coil Rated Auto louver motor Drain pump Panel Model No SM830252...

Страница 16: ...5 0 2 MPa ON Fan mm Number diameter m3 h Air circulation Fan speeds Max Fan motor Model No Source No of pole W Nominal output Safety device Operating temperature Open C Close C VAC µF Heat exchanger Coil mm Rows fin pitch m2 U 200PE2E8A 380 400 415V 3 Phase 50Hz ACXA73C07280 30A 5JD650XDB22 520V DC MOTOR 4 200 2 050 Discharge temperature control 230V 36W 2 ø540 164 NFD 81FW D8120 1 NFD 81FW D8120 ...

Страница 17: ...5 0 2 MPa ON Fan mm Number diameter m3 h Air circulation Fan speeds Max Fan motor Model No Source No of pole W Nominal output Safety device Operating temperature Open C Close C VAC µF Heat exchanger Coil mm Rows fin pitch m2 U 250PE2E8A 380 400 415V 3 Phase 50Hz ACXA73C07260 30A 5JD650XDB22 520V DC MOTOR 5 500 2 050 Discharge temperature control 230V 36W 2 ø540 160 NFD 81FW D8120 1 NFD 81FW D8120 ...

Страница 18: ...nsor TH5 Resistance kΩ 60 C 1 593 2 85 C 0 7598 2 65 C 1 363 2 90 C 0 6623 2 70 C 1 171 2 95 C 0 5793 2 75 C 1 010 2 100 C 0 5083 2 80 C 0 8746 2 105 C 0 4473 2 Relay Comp Magnetic Contactor VAC Coil rated VAC A Contact rating Coil resistance at 20 C Ω Sol Control Valve 4 way valve 4 way valve Electro magnetic coil Thermal cut off temperature Sol control valve Magnetic coil U 200PE2E8A UKV32D322 S...

Страница 19: ...kΩ 60 C 1 593 2 85 C 0 7598 2 65 C 1 363 2 90 C 0 6623 2 70 C 1 171 2 95 C 0 5793 2 75 C 1 010 2 100 C 0 5083 2 80 C 0 8746 2 105 C 0 4473 2 Relay Comp Magnetic Contactor VAC Coil rated VAC A Contact rating Coil resistance at 20 C Ω Sol Control Valve 4 way valve 4 way valve Electro magnetic coil Thermal cut off temperature Sol control valve Magnetic coil U 250PE2E8A UKV32D322 SHF 35B 67 03 SQ A252...

Страница 20: ...e Type 200 Connection Tubing ø12 7 ø12 7 ø9 52 2 Refrigerant gas tubing Brazing ø25 4 3 Power supply port 4 Communication wiring port 5 Port for optional wiring part 6 Drain port 25A 7 Air intake duct connecting side flange 8 Air discharge duct connecting side flange For communication wiring port For power supply wiring port Min 800 Space for service Electrical component box Space for removing dra...

Страница 21: ...low the lower surface of the main unit as shown in the figure at right If the suspension bolt is too long it will contact the ceiling panel and the unit cannot be installed Raise dimension of drain tube unit mm View X View XX X Z Y Detailed view Z Detailed view Y 113 80 64 80 64 4 M4 Tapping screw holes 162 115 105 105 115 4 M4 Tapping screw holes Over 30 Over 18 122 Less than 666 Less than 850 Le...

Страница 22: ...ake 7 5 6 4 8 Z VIEW 42 74 100 120 173 16 51 35 47 Air discharge Air intake When using a drain pipe install the drain socket field supply onto the drain port Seal the other drain port with the rubber cap 43 2 3 Air intake B Outdoor Unit U 200PE2E8A Specification for pipe connecting indoor unit to outdoor unit U 200PE2E8A Model name Piping Connections 2 5 9 ø e d i s d i u q i L 25 4 ø e d i s s a ...

Страница 23: ...Z VIEW 42 74 100 120 173 16 51 35 47 Air discharge Air intake When using a drain pipe install the drain socket field supply onto the drain port Seal the other drain port with the rubber cap Air intake Air intake Gas piping connection While the main gas side pipe is ø25 4 since connecting the outdoor unit s 3 way valve requires a ø19 05 flare please be sure to use standard accessories joint piping ...

Страница 24: ...pressure switch Heat exchanger Heat exchanger Heat exchanger Heat exchanger Accumulator Accumulator 4 way valve 2 way valve 2 way valve 4 way valve Liquid line service valve Liquid line service valve Outdoor air Temp Thermistor Outdoor air Temp Thermistor Heat exchanger Temp Thermistor Heat exchanger Temp Thermistor Defrost Temp Thermistor Defrost Temp Thermistor Suction Temp Thermistor Suction Te...

Страница 25: ...ure switch Heat exchanger Heat exchanger Heat exchanger Heat exchanger Accumulator Accumulator 4 way valve 2 way valve 2 way valve 4 way valve Liquid line service valve Liquid line service valve Outdoor air Temp Thermistor Outdoor air Temp Thermistor Heat exchanger Temp Thermistor Heat exchanger Temp Thermistor Defrost Temp Thermistor Defrost Temp Thermistor Suction Temp Thermistor Suction Temp Th...

Страница 26: ...ting Maximum 30 C DB 24 C DB Minimum 16 C DB 20 C DB S 100PU2E5A 2 U 200PE2E8A S 125PU2E5A 2 U 250PE2E8A Temperature Indoor air intake temp Outdoor air intake temp Cooling Maximum 32 C DB 46 C DB Minimum 18 C DB 15 C DB Heating Maximum 30 C DB 24 C DB Minimum 16 C DB 20 C DB SM830252 01_欧州_Single_8 10HP_TD_SM indb 20 16 10 14 13 57 11 AMP Air Conditioning www ampair co uk sales ampair co uk ...

Страница 27: ...m power consumption under the JIS condition Maximum capacity indicates the maximum value in the parentheses of the specifications cooling and heating capacity 3 The characteristic of heating capacity excludes the decline of capacity when frosting including defrost drive NOTE 1 Indoor air intake temp C WB Indoor air intake temp C WB 0 88 0 88 0 88 0 88 0 88 0 88 0 88 0 86 0 88 0 83 0 83 0 82 0 82 0...

Страница 28: ...ng defrost drive NOTE 2 0 20 40 60 80 100 120 140 Power consumption ratio Capacity W Rated capacity ratio for cooling Rated capacity ratio for heating 㻜㻌㻌㻌㻌㻌㻌㻌㻌㻌㻌㻡㻜㻜㻜㻌㻌㻌㻌㻌㻌㻝㻜㻜㻜㻜㻌㻌㻌㻌㻌㻝㻡㻜㻜㻜㻌㻌㻌㻌㻌㻌㻞㻜㻜㻜㻜㻌㻌㻌㻌㻌㻞㻡㻜㻜㻜 0 20 40 60 80 100 120 140 Power consumption ratio Capacity W 㻜㻌㻌㻌㻌㻌㻌㻌㻌㻌㻌㻡㻜㻜㻜㻌㻌㻌㻌㻌㻌㻝㻜㻜㻜㻜㻌㻌㻌㻌㻌㻝㻡㻜㻜㻜㻌㻌㻌㻌㻌㻌㻞㻜㻜㻜㻜㻌㻌㻌㻌㻌㻞㻡㻜㻜㻜㻌㻌㻌㻌㻌㻟㻜㻜㻜㻜 0 20 40 60 80 100 120 140 Power consumption ratio Capacity W 㻜...

Страница 29: ...ssure level dB 0dB 0 0002µbar minimum audible limit for continuous noise Approximate NC 70 NC 60 NC 50 NC 40 NC 30 NC 20 4 Way Cassette Type REMARKS NOTE 1 Value obtained in the actual place where the unit is installed may be slightly higher than the values shown in this graph because of the conditions of operation the structure of the building the background noise and other factors 2 The test res...

Страница 30: ... NC 70 60 70 80 90 50 40 30 20 10 4000 0 0 0 8 0 5 2 5 2 1 3 6 2000 1000 500 MODEL SOUND LEVEL CONDITION U 200PE2E8A 60 dB A COOLING 1 m in front at height of 1 5 m Approximate minimum audible limit for continuous noise Overall Frequency at center of sound pressure band Hz Octave Band Level dB 0dB 0 0002 µbar COOLING NC 20 NC 30 NC 40 NC 50 NC 60 NC 70 60 70 80 90 50 40 30 20 10 4000 0 0 0 8 0 5 2...

Страница 31: ... 3m s Vertical air fl ow distance m Horizontal air flow distance m Strong wind Discharge angle approx 65 Room temperature approx 20 C 5 4 3 2 1 0 1 2 3 4 5 0 1 2 3 0 1 2 3 33 27 24 30 Vertical air fl ow distance m Horizontal air flow distance m Strong wind Discharge angle approx 65 Room temperature approx 20 C 5 4 3 2 1 0 1 2 3 4 5 0 1 2 3 0 1 2 3 1 5m s 1 0m s 0 5m s 0 3m s Vertical air fl ow dis...

Страница 32: ...n 3 When used in combination with humidifiers External air must always be processed when the external air temperature reaches freezing point to prevent the risk of the humidifier freezing 4 Arranging Ducts and Filters in the Field External air intake ducting must be arranged in the field External air filters must also be installed without fail in order to prevent the intake of dust and grit 5 Ther...

Страница 33: ...ount of external air that is possible to feed when it is fed directly into the unit ø100 Type 100 125 Permissible Air Intake Volume m h 18 18 NOTE The operation noise for models that use small units is lower so use values that are within the range shown in the above table Using values that exceed these will result in noise when only external air is fed being louder than the noise emitted from the ...

Страница 34: ...s a result of such unauthorized changes Regulations on wire diameters differ from locality to locality For field wiring rules please refer to your LOCAL ELECTRICAL CODES before beginning You must ensure that installation complies with all relevant rules and regulations To prevent malfunction of the air conditioner caused by electrical noise care must be taken when wiring as follows The remote cont...

Страница 35: ...g U2 U1 SG SG Shows the ground for the shielded cable R2 R1 L N 2 1 D B L N 2 1 L1 L2 L3 N C L1 L2 L3 N U2 U1 SG Power supply 220 230 240V 50 Hz Remote controller WHT BLK Ground Ground Outdoor unit INV unit Power supply 380 400 415V 3 N 50 Hz Indoor unit L N U1 U2 R1 R2 7P terminal board Type E2 Remote control wiring U1 U2 N L R1 R2 4P terminal board 2P terminal board Unit control line Remote cont...

Страница 36: ...ig 1 3 Outdoor unit Indoor unit Indoor unit Indoor unit Indoor unit NO Branch point 5 Use shielded wires for inter unit control wiring c and ground the shield on both sides otherwise misoperation from noise may occur Fig 1 4 Connect wiring as shown in Section Wiring System Diagrams 6 Connecting cable between indoor unit and outdoor unit shall be approved polychloroprene sheathed 5 or 3 1 5 mm2 fle...

Страница 37: ...d 3 Using a ring connector fastener or pliers securely clamp each stripped wire end with a ring pressure terminal 4 Place the ring pressure terminal and replace and tighten the removed terminal screw using a screwdriver Fig 1 6 Examples of shield wires 1 Remove cable coat not to scratch braided shield Fig 1 7 2 Unbraid the braided shield carefully and twist the unbraided shield wires tightly toget...

Страница 38: ...op connection terminal block Earth lead wire Earth terminal Power line Thermal insulating piping materials Please fix all electrical lines firmly with cord clamps Carry out wiring so that wires are not stretched Insulate the terminal portion earth included with insulation sleeves Please tie the insulation piping securely so that no electrical lines do come into contact with the compressor or expos...

Страница 39: ...nal wiring regulations If capacity of power supply circuit and enforcement are not enough it can causes the electric shock and a fire This equipment complies with EN IEC 61000 3 12 provided that the short circuit power Ssc is greater than or equals to 1850 kVA at the interface point between the user s supply and the public system It is the responsibility of the installer or user of the equipment t...

Страница 40: ...ng length L m Height Differential of Indoor Outdoor Units H1 Outdoor unit is placed higher m Outdoor unit is placed lower m Max allowable tubing length at m t n e m p i h s 120 30 30 5 30 Required additional refrigerant m g 50 80 Refrigerant charged at shipment g k 5 60 6 40 No additional charge of compressor oil is necessary If the total tubing length exceeds 30 m charge the amount of refrigerant...

Страница 41: ...IN Branch pipe 1 CZ P680BK2 Branch pipe 2 CZ P155BK1 TRIPLE CZ P3HPC2 SYMBOLS SPEC TWIN TRIPLE DOUBLE TWIN m 0 2 1 f L e L d L c L b L a L L c L b L a L L b L a L L h t g n e l e p i p l a t o T c L r o b L r o a L b L r o a L h t g n e l e p i p h c n a r b m u m i x a M La Lc or La Ld or Lb Le or Lb Lf Less than 15m Maximum branch pipe length difference La Lb La Lb La Lb Lc La Lb Lb Lc La Lc Lb ...

Страница 42: ... each type so add it to the amount that is charged at the field For the refrigerant charge amount at shipment refer to the unit s nameplate Minimum indoor volume floor area relative to the amount of refrigerant are roughly as given in the following table Pay special attention to any location such as a basement or recessed area etc where leaked refrigerant can collect since refrigerant gas is heavi...

Страница 43: ...15 88 5 8 Liquid tube 9 52 3 8 Size of connection point on each part shown is inside diameter of tubing Size Part A Part B Part C Part D Part E mm ø19 05 ø15 88 ø12 7 ø9 52 ø6 35 Unit mm Distribution Joint Insulation for gas tube Distribution Joint Insulation for liquid tube Unit mm Liquid distribution joint for liquid tube Gas distribution joint for gas tube Dowel pin position 3 locations Liquid ...

Страница 44: ... is not necessary If the reducer that was supplied in the package is used perform brazing on site Do not cut in such a way that applies excessive force and causes deformation of the tube This will prevent insertion of the connecting tube Cut at a position that is as far away as possible from the dowel pin After cutting the tube be sure to remove any burrs and to finish the end surface correctly If...

Страница 45: ...ground The collective tubes are vertical with respect to the ground The collective tube and distribution joint are horizontal with respect to the ground Collective tube Gas tube side Distribution joint Only the distribution joints are horizontal with respect to the ground The collective tubes are vertical with respect to the ground The collective tube and distribution joint are horizontal with res...

Страница 46: ...ith suitable roofing which shelters the unit from snow 4 Avoid installing the unit in locations where there are petroleum products such as machine oil saline content such as coastal areas sulphurous gas and where high frequency noise is generated 5 Place the indoor and outdoor unit power cords and indoor outdoor unit connection cables at a minimum distance of 1 meter or more away from televisions a...

Страница 47: ... 250 More than 250 More than 250 More than 150 More than 200 More than 150 More than 300 Where there are obstacles on the intake and discharge Upper part and both side faces are open 1 Separate location installation More than 150 More than 1000 2 Multiple units more than 2 units More than 300 More than 250 More than 250 More than 1500 Caution Please ensure that the height of obstacles at either th...

Страница 48: ...he even where the roof is at risk of receiving oscillations or vibrations secure the unit with a seismic isolating mount or vibration absorbing rubber 5 The drain water will be discharged from the unit during heating or defrosting operation mode Select an appropriate location with good drainage system In the winter there is risk of slipping due to freezing and depending on the installation set up ...

Страница 49: ...rust protection Ensure to install pipe panels to prevent rain water from getting into the unit Close the gap at the pipe connected area with putty or heat insulator locally supplied If an insect or small animal enters the outdoor unit there is the risk of shorting in the product electronic casing Remove the front panel 1 Remove the 2 mounting screws 2 Slide the front panel using your hands downwar...

Страница 50: ...om occurring Gas side Opening Open the valve cap pull out the knob and use pliers etc to turn the knob 90 counter clockwise Closing Open the valve cap pull out the knob and use pliers etc to turn the knob 90 clockwise Liquid side Opening Open the valve cap and turn the Allen wrench counter clockwise until it stops Closing Open the valve cap and turn the Allen wrench clockwise until it stops Use an...

Страница 51: ...s when adding flare nuts and the tightening torque Precautions for flare nut installation Piping size Tightening torque Flare section dimensions A Flare configuration ø 6 35 14 0N m 18 0N m 140kgf cm 180kgf cm 8 7 9 1 90 2 4 5 1 ø 9 52 34 0N m 42 0N m 340kgf cm 420kgf cm 12 8 13 2 ø 12 7 49 0N m 55 0N m 500kgf cm 560kgf cm 16 2 16 6 ø 15 88 68 0N m 82 0N m 690kgf cm 830kgf cm 19 3 19 7 ø 19 05 100...

Страница 52: ...t piping A to the necessary length 3 Braze the machined cut joint piping A to the bottom edge of joint piping B 4 In order to protect wiring and parts in the unit please carry out brazing outside the unit since each type of joint piping is differently oriented carry out brazing according to the orientations shown in the connection pipe process diagrams 5 Connect the brazed connection pipes to the ...

Страница 53: ...ortest run to the outdoor unit Allow room for operation and maintenance as well as unrestricted airflow around the unit Install the unit within the maximum elevation difference above or below the outdoor unit and within a total tubing length L from the outdoor unit as detailed in Table 1 1 Allow room for mounting the remote controller about 1 m off the floor in an area that is not in direct sunlig...

Страница 54: ...Flare Type 200 Connection Tubing ø12 7 ø12 7 ø9 52 2 Refrigerant gas tubing Brazing ø25 4 3 Power supply port 4 Communication wiring port 5 Port for optional wiring part 6 Drain port 25A 7 Air intake duct connecting side flange 8 Air discharge duct connecting side flange For communication wiring port For power supply wiring port Min 800 Space for service Electrical component box Space for removing...

Страница 55: ... into position for connection to the unit before placing the unit inside the ceiling 2 Screw in the suspension bolts allowing them to protrude from the ceiling as shown in Fig 1 11 Cut the ceiling material if necessary 3 Suspend and fix the indoor unit using the 2 hexagonal nuts field supply and special washers supplied with the unit as shown in Fig 1 12 The top of the unit must be installed horiz...

Страница 56: ...oths Longer screw Cover plate The Type 200 indoor unit comes with a tube connector that is for liquid tubing Configure as shown in the illustration and connect it When flaring the tube put the flare nut onto it first and then flare it Remove the ø12 7 flare nut from the liquid tubing of the indoor unit and use it To Indoor unit Flare the tubing Tube connector for Type 200 Accessory Braze ø 9 52 To...

Страница 57: ... 8 When the drain piping is completed perform the water leak test and check for a water leak If detected it may result in water leakage or condensation 9 When the drain piping is completed perform the drainage test if the water drains smoothly If not draining smoothly it may result in water leakage or condensation 10 When the drain piping work is finished securely wrap the insulation material arou...

Страница 58: ...ld supply Inspection opening Ceiling panel Indoor unit Thermal insulation Thermal insulation Air discharge Air intake Canvas connection Sound absorbing chamber Airflow control damper Fig 1 16 Use incombustible duct materials Use thermal insulation to prevent duct condensation An air filter field supply must be installed at the air intake side If not installed the heat exchanger will get dirty and ...

Страница 59: ...cancelled c Manual setting will be activated if selected but b Manual setting takes precedence when the power is switched back on after power outages etc Make sure the external static pressure is in a range of specifications Then proceed the external static pressure setting Improper settings can cause noise a shortage of airflow volume and water leakage Refer to Fig 1 18 for the external static pr...

Страница 60: ...set this parameter may result in decreased airflow and condensation 9 6 2 Operating the Timer Remote Controller CZ RTC4 How to set the external static pressure Indoor Unit control PC board ON Fig 1 17 A 1 Press and hold down the and buttons simultaneously for 4 or more seconds the Unit No Item Code and Detailed Data will blink on the LCD display 2 The indoor unit numbers in the group control will ...

Страница 61: ... no Set data 10 3 1 0006 Sel Next 20 30 THU 3 Select the Code no by pressing the or button Change the Code no to 5D by pressing the or button or keeping it pressed Detailed settings Unit no Code no Set data 1 0 0 0 1 3 Sel Next 20 30 THU 5D 4 START 20 30 THU Select the Set data by pressing the or button Select one of the Set data among 0006 0003 or 0001 according to the desired external static pre...

Страница 62: ...ernal static pressure Airflow Volume m3 min Airflow Volume m3 min L i m i t l i n e Limit line Limit line Limit line Limit line Limit line Type 250 0 20 40 60 80 100 120 140 160 180 200 220 240 260 280 300 320 45 50 55 60 65 70 75 80 85 90 5 3 1 9 7 4 8 6 2 L L L M M M H H H Pa External static pressure L i m i t l i n e Limit line Limit line L i m i t l i n e Limit line Limit line Fig 1 18 SM83025...

Страница 63: ...can be uniformly cooled select a location where the ceiling is strong enough to support the weight of the unit select a location where tubing and drain pipe have the shortest run to the outdoor unit allow room for operation and maintenance as well as unrestricted air flow around the unit the limitation of the tubing length between the indoor and the outdoor units should be referred to the Installa...

Страница 64: ...rant tubing joint liquid side Refrigerant tubing joint gas side 184 mm 134 mm 33 5 mm 177 mm Type 100 140 319 mm Type 36 71 256 mm 127 mm Indoor Unit View from top A 700 mm A 780 mm B 860 910 mm A suspension bolt pitch B ceiling opening dimension B 860 910 mm 2 Follow the diagram to make the holes in the ceiling 3 Determine the pitch of the suspension bolts using the supplied full scale installati...

Страница 65: ...d 2 washers onto each of the 4 suspension bolts Use 1 nut and 1 washer for the upper side and 2 nuts and 1 washer for the lower side so that the unit will not fall off the suspension lugs Nuts and washers use for upper and lower Double nut 12 17 mm Notch Suspension lug Suspension bolt 4 Adjust so that the distance between the unit and the ceiling bottom is 12 to 17 mm Tighten the nuts on the upper...

Страница 66: ...t is not operating Do not install an air bleeder as this may cause water to spray from the drain pipe outlet Do not provide U trap or bell shaped trap in the middle of the drain pipe Doing so will cause abnormal sound Indoor unit Air bleeder prohibited Trap prohibited Upward gradient prohibited Make sure the drain pipe has a downward gradient 1 100 or more downward from drain port connection Indoo...

Страница 67: ...e without connection of the hard PVC socket and the hard PVC pipe joint VP25 in the local supply 6 Connect the drain hose and the hard PVC pipe joint so that the adhesive area of both sides can be overlapped Wipe off the protrusion adhesive with a soft cloth Drain port Do not use adhesive here Drain port may possibly be damaged and cause the water leakage if PVC adhesive is used After checking the...

Страница 68: ...r and outdoor units panels and electrical wiring check the following items CAUTION Important Note for Wiring 4 Way Cassette Type 1 The power supply inlet is located at the lower area of the refrigerant tubing side of the unit The electrical component box is located at the air intake of the bottom of the unit 2 Before installing the panel for cassette be sure to carry out the wiring connection 3 Re...

Страница 69: ...s Tightly 1 Apply a sealing cap or water proof tape to prevent dust or water from entering the tubes before they are used 2 Be sure to apply refrigerant lubricant ether oil to the inside of the flare nut before making piping connections This is effective for reducing gas leaks Apply refrigerant lubricant 3 For proper connection align the union tube and flare tube straight with each other then scre...

Страница 70: ...ke sure you allow sufficient space to access the valves and to allow the panels to be attached and removed Taping the flare nuts Wind the white insulating tape around the flare nuts at the gas tube connections Then cover up the tubing connections with the flare insulator and fill the gap at the union with the supplied black insulating tape Finally fasten the insulator at both ends with the supplie...

Страница 71: ... putty to seal off the hole in the wall to prevent rain and draft from entering Apply putty here Tubing 6 HOW TO INSTALL THE TIMER REMOTE CONTROLLER OR HIGH SPEC WIRED REMOTE CONTROLLER OPTIONAL PART NOTE Refer to the Operating Instructions attached to the optional Timer Remote Controller or optional High spec Wired Remote Controller 7 HOW TO INSTALL THE PANEL FOR CASSETTE 4 Way Cassette Type Type...

Страница 72: ... sliding it in the direction shown by the arrow 2 Reattach the air intake grille after installation of the panel for cassette 2 4 Way Cassette Type Type U2 Accessories Panel for cassette 1 Screws 4 4 12 Preparation for Panel for Cassette Installation 1 Checking the unit position 1 Check that the ceiling hole is within this range 860 mm 860 mm to 910 mm 910 mm 2 Confirm that the position of the ind...

Страница 73: ... make sure that there are no gaps between the unit and the panel for cassette or between the panel for cassette and the ceiling surface If there is a gap between the panel and the ceiling leave the panel for cassette attached and make fine adjustments to the installation height of the unit to eliminate the gap with the ceiling CAUTION If the screws are not sufficiently tightened trouble such as th...

Страница 74: ... to customer s requests When attaching the air intake grille be careful that the flap lead wire does not become caught Be sure to attach the safety cord that prevents the air intake grille from dropping off to the panel for cassette unit as shown in the figure below With this panel for cassette the directions of the air intake grille lattices when installing multiple units and the position of the ...

Страница 75: ...ling height m Indoor unit type 36 45 50 60 71 100 125 140 Standard factory setting 2 7 3 0 3 6 High ceiling setting 1 3 2 3 3 4 3 High ceiling setting 2 3 5 3 6 5 0 Air flow blocking kit for 3 way air flow 3 8 3 8 4 7 Air flow blocking kit for 2 way air flow 4 2 4 2 5 0 1 When setting on the P C Board Procedure Stop the system before performing these steps 1 Open the electrical component box cover...

Страница 76: ...t press the button to set At this time the fan at the indoor unit begins and select the address unit No of the indoor unit operating 3 Designate the item code by adjusting the Temperature Setting buttons 4 Press the timer time buttons to select the desired setting data For item codes and setting data refer to Table for DC Fan Motor Tap Settings 5 Press the button The display stops blinking and rem...

Страница 77: ...rical component box XX YYYY 5 Select the Set data by pressing the or button Select one of the Setting Data YYYY by pressing the or button Then press the button XX YYYY Flap position 1 2 3 4 5 Setting data Setting data Flap position during operation Without separate setting Swing Move to position 1 and stay Move to position 2 and stay Move to position 3 and stay Move to position 4 and stay Move to ...

Страница 78: ...Flap position 1 2 3 4 5 Setting data Setting data Flap position during operation Without separate setting Swing Move to position 1 and stay Move to position 2 and stay Move to position 3 and stay Move to position 4 and stay Move to position 5 and stay NOTE The flap swings during the operation under Setting the Flap Separately At this time the unselected flaps are moved to the position 1 A 1 5 6 2 ...

Страница 79: ...ocal source you will need 1 Deoxidized annealed copper tube for refrigerant tubing 2 Foamed polyethylene insulation for copper tubes as required to precise length of tubing Wall thickness of the insulation should be not less than 8 mm 3 Use insulated copper wire for field wiring Wire size varies with the total length of wiring Refer to 4 ELECTRICAL WIRING for details CAUTION Check local electrical...

Страница 80: ...ection area the sensor cannot occasionally detect properly The Floor Temperature Sensor detects within the sensor area of Human Detection Sensor Human Detection Sensor Floor Temperature Sensor Detection area of Human Detection Sensor 1 m above floor visual range Installation height 2 7 5 m Detection area of Floor Temperature Sensor Approx ø7 9 m Criteria of human detection sensor area Installation...

Страница 81: ... for Panel for Cassette Installation 1 Checking the unit position 1 Check that the ceiling hole is within this range 860 860 mm to 910 910 mm 2 Confirm that the position of the indoor unit and the ceiling as shown in the diagram If the positions of the ceiling surface and unit do not match air leakage water leakage flap operation failure or other problems may occur Main unit Ceiling side Ceiling o...

Страница 82: ...ling surface If there is a gap between the panel and the ceiling leave the panel for cassette attached and make fine adjustments to the installation height of the unit to eliminate the gap with the ceiling CAUTION If the screws are not sufficiently tightened trouble such as that shown in the figure below may occur Be sure to tighten the screws securely If a gap remains between the ceiling surface ...

Страница 83: ... Attaching the air intake grille To install the air intake grille follow the steps for Removing the grille in the reverse order By rotating the air intake grille it is possible to attach the grille onto the panel for cassette from any of 4 directions Coordinate the directions of the air intake grilles when installing multiple units and change the directions according to customer s requests When at...

Страница 84: ... Ceiling height m Indoor unit type 36 45 50 60 71 100 125 140 Standard factory setting 2 7 3 0 3 6 High ceiling setting 1 3 2 3 3 4 3 High ceiling setting 2 3 5 3 6 5 0 Air flow blocking kit for 3 way air flow 3 8 3 8 4 7 Air flow blocking kit for 2 way air flow 4 2 4 2 5 0 1 When setting on the P C Board Procedure Stop the system before performing these steps 1 Open the electrical component box c...

Страница 85: ...in effect press the button to set At this time the fan at the indoor unit begins and select the address unit No of the indoor unit operating 3 Designate the item code by adjusting the Temperature Setting buttons 4 Press the timer time buttons to select the desired setting data For item codes and setting data refer to Table for DC Fan Motor Tap Settings 5 Press the button The display stops blinking...

Страница 86: ...93 Electrical component box 5 Select the Set data by pressing the or button Select one of the Setting Data YYYY by pressing the or button Then press the button Flap position 1 2 3 4 5 Setting data Setting data Flap position during operation Without separate setting Swing Move to position 1 and stay Move to position 2 and stay Move to position 3 and stay Move to position 4 and stay Move to position...

Страница 87: ...ata Flap position 1 2 3 4 5 Setting data Setting data Flap position during operation Without separate setting Swing Move to position 1 and stay Move to position 2 and stay Move to position 3 and stay Move to position 4 and stay Move to position 5 and stay NOTE The flap swings during the operation under Setting the Flap Separately At this time the unselected flaps are moved to the position 1 A 5 Pr...

Страница 88: ...n operating mode If operation is in fan mode is not displayed Set in any operating mode other than fan mode is displayed when setting the ECONAVI function NOTE After operating Step 2 the following messages may occasionally appear on the screen Display message Contents Disabled in default mode After a while select 0 ECONAVI info again If no status changes even after 10 minutes make auto address set...

Страница 89: ...unit is without ECONAVI panel Not connected appears Sensor 1 means optional ECONAVI sensor CZ CENSC1 If not connected Not connected appears besides Sensor 1 on the screen 5 If the sensor status shows other than Normal Preparing If the sensor status shows Error or Not connected although the panel for cassette ECONAVI type is connected the following symptom may have occurred Specify the applicable i...

Страница 90: ... 5 6 OPTION white Relay DC 12V field supply Note Indoor unit control PCB CR1 Note The relay must be installed at a distance of 2 m or less from the PCB Fan signal DC 12V Heat start signal Cool start signal Thermostat signal Defrost signal NOTE The external output signal from the air conditioner is supplied for the purpose of controlling the external devices If the air conditioner does not operate ...

Страница 91: ... affects environment Repair it as quickly as possible Drain Check 11 Has the adhesive been applied to the drain connecting portion resin portion of the indoor unit The resin portion cracks after a few months and it may cause water drain 12 Is there water leakage Since there is a possibility of water drain repair the drain pipe if the drain failure or water drain occurs 13 Indoor unit drain pipe ha...

Страница 92: ... instructions Air intake chamber Screws Washers Black sealant Indoor unit Fig 1 19 2 1 Accessory parts 2 Mounting procedure 1 4 4 Before proceeding with the mounting remove the cushions which have been inserted into the air outlets in 4 places 1 Mounting Air intake chamber Fig 1 Place the black sealant side of Air intake chamber toward the indoor unit Air intake chamber can be mounted correctly in...

Страница 93: ...nt box Cover Clamp Ceiling panel 22P cable connector white Through hole for 22P cable connector white Fig 1 20 Mounting procedure continued SM830252 01_欧州_Single_8 10HP_TD_SM indb 87 16 10 14 13 58 03 AMP Air Conditioning www ampair co uk sales ampair co uk ...

Страница 94: ...N position TP6 TP3 TP1 1 ON 2 3 DIP switch ON position TP6 TP3 TP1 ON 3 6 1 In the example shown in the figure above DIP switch 1 is OFF DIP switch 2 is ON DIP switch 3 is OFF On Table 1 6 check out the Item code 5D setting data that corresponds to the intended application and the optional parts to be used 3 When setting the fan speed using a wired remote controller optional parts CZ RTC4 On Table...

Страница 95: ...slit Fig 1 22 For Air outlet 2 Air flow blocker B can be used as is For Air outlet 3 or 4 Air flow blocker A can be used as is 1 2 3 4 A B A 2 B 1 Drain pan Drain pan Adjust the position of packing and attach it so that a can be 10mm and more a a a a Corner metal Fold the protruding parts of the sealer over the side panel and adhere them into place Ensure that the sealer does not come into contact...

Страница 96: ...re to prevent cold air leaks and deficient insulation while performing the air outlet duct connection flange Φ150 field supply work in order to prevent condensation from forming It should be borne in mind that any air outlet blocking pattern with the hatching mark will make it impossible for the nanoe nano technology fine particle function to work When the air flow blocker has been provided in any...

Страница 97: ...3 6 1 In the example shown in the figure above DIP switch 1 is OFF DIP switch 2 is ON DIP switch 3 is OFF On Table 1 7 check out the Item code 5D setting data that corresponds to the intended application and the optional parts to be used 3 When setting the fan speed using a wired remote controller optional parts CZ RTC4 On Table 1 7 check out the Item code 5d setting data that corresponds to the i...

Страница 98: ...ing the side panel insulator to the small unit attach it after cutting along its perforations of the parts 1 to 5 1 Align the slits of the side panel insulators 1 to 4 with the hanger and attach the parts to the side panels of the indoor unit Fig 1 27 2 Now attach the side panel insulator 5 to the side panel of the indoor unit Fig 1 27 3 Align the side panel insulator 6 with the piping cover and a...

Страница 99: ... overlap Side insulators 1 to 5 In 4 places Fig 1 28 Fig 1 29 Parts installed on the indoor unit continued 2 1 3 6 5 7 8 9 10 Fig 1 27 4 SM830252 01_欧州_Single_8 10HP_TD_SM indb 93 16 10 14 13 58 08 AMP Air Conditioning www ampair co uk sales ampair co uk ...

Страница 100: ... piping side Datum for attaching the parts Datum for attaching the parts Used to block the square hole of the 15 insulator Insulator that has been cut out along its perforations Refrigerant piping side 15 16 11 14 12 13 3 2 1 Receiver used for ECONAVI Receiver used for wireless remote controller 2 2 11 12 13 14 15 16 1 1 1 1 Befo indo the refe The or im The P U These Insulator that has been cut ou...

Страница 101: ... important and should be done carefully to make a good flare Be sure to keep any contaminants moisture dirt metal filings etc from entering the tubing Figs 1 33 and 1 34 When reaming hold the tube end downward and be sure that no copper scraps fall into the tube Fig 1 34 3 Remove the flare nut from the unit and be sure to mount it on the copper tube After Before Deburring Copper tubing Reamer Fig ...

Страница 102: ...g 1 38 If the flare nuts are over tightened the flare may be damaged which could result in refrigerant leakage and cause injury or asphyxiation to room occupants For the flare nuts at tubing connections be sure to use the flare nuts that were supplied with the unit or else flare nuts for R410A Type 2 The refrigerant tubing that is used must be of the correct wall thickness as shown in the table In...

Страница 103: ... side Fig 1 40 Insulation material The material used for insulation must have good insulation characteristics be easy to use be age resistant and must not easily absorb moisture After a tube has been insulated never try to bend it into a narrow curve because it can cause the tube to break or crack Never grasp the drain or refrigerant connecting outlets when moving the unit 4 Taping the Tubes 1 At ...

Страница 104: ...30m If the equivalent pipe length used will be 30m or less no additional charging will be necessary If the equivalent pipe length will be between 30 and 120m charge with additional refrigerant according to the equivalent length given in the table below For standard type Pump down operation Please refer to the service manual for pump down method Liquid refrigerant Model name Add gas amount Equivale...

Страница 105: ...asure the insulation Do not use the mega tester for any other circuit except for voltage of 220 240V or 380 415V Are the wire connections for the indoor outdoor units connected as described in the instructions Are there any looped wires Was the N phase surely connected when connecting the power supply wire on the three phase model If N phase is not connected only the fan may repeat turning ON OFF ...

Страница 106: ... insulation material properly installed Is the earth wire securely connected Is the front panel and the indoor unit air conditioner firmly fixed and was the installation completed without any leakage from the refrigerant Are the indoor and outdoor units secured firmly installed with bolts at secured locations 1 18 REGARDING DELIVERY TO THE CUSTOMER Request the customer to review the instruction ma...

Страница 107: ...ion fixture t0 8 2 7 2 1 1 1 1 6 1 1 12 Q ty t0 8 t0 8 t0 8 t0 8 t0 8 t0 8 t1 0 Upward Louver 1 1 1 4 Downward Air discharge support 5 5 5 5 5 5 Downward Right side installation fixture Downward Left side installation fixture Downward Louver Downward Upward installation fixture Downward Downward installation fixture Tapping Screw 4mm x 12mm 2 3 6 7 8 9 10 11 A SEC A A SPOT WELDING 28 POSITION A 58...

Страница 108: ...nce diagram for Upward Louver field supply C L 585 0 2 605 608 2 13 5 6 5 20 72 8 2 1 2 R 3 2 ø5 HOLE 2 1 77 1 6 1 6 1 6 1 6 2 R3 2 R3 10 30 2 0 8 2 2 9 2 4 2 3 10 65 5 66 6 63 4 2 3 610 4 0 2 4 R3 8 Supplement SM830252 01_欧州_Single_8 10HP_TD_SM indb 102 16 10 14 13 58 16 AMP Air Conditioning www ampair co uk sales ampair co uk ...

Страница 109: ... 39 A 36 45 2 R3 7 17 612 616 2 ø5 HOLE 2 R 3 2 R3 DTL A S 1 1 2 POSITION ø3 3 0 05 ø6 5 2 7 1 5 90 A A SPOT WELDING 4 POSITION SPOT WELDING 10 POSITION SEC A A SPOT WELDING 24 POSITION 637 624 0 2 7 13 5 43 35 12 6 4 5 10 11 3 48 9 74 4 53 8 6 7 9 3 7 9 100 100 15 4 5 5 5 5 1 5 4 5 P74 4 5 372 9 6 7 8 10 615 0 2 278 5 121 5 627 5 59 2 8 Supplement SM830252 01_欧州_Single_8 10HP_TD_SM indb 103 16 10...

Страница 110: ... supply 2 1 77 5 627 120 509 6 96 1 2 4 4 7 1 2 4 5 2 R 3 615 0 2 6 6 6 12 5 6 2 ø5 HOLE A 1 6 2 R 3 A C T U A L S I Z E R3 DTL A S 1 2 1 6 96 1 2 1 7 7 5 627 120 509 6 96 1 2 4 4 7 124 5 2 R 3 615 0 2 6 6 6 12 5 6 2 ø5 HOLE A R3 2 R3 ACTUAL SIZE DTL A S 1 2 1 6 96 1 8 Supplement SM830252 01_欧州_Single_8 10HP_TD_SM indb 104 16 10 14 13 58 16 AMP Air Conditioning www ampair co uk sales ampair co uk ...

Страница 111: ...for Downward Upward installation fixture field supply 2 6 55 2 R3 610 4 0 2 2 6 2 6 605 2 10 6 6 2 R 3 59 2 1 6 6 6 2 6 2 6 605 2 10 30 2 0 8 2 2 9 2 4 2 3 10 65 5 66 6 63 4 2 3 610 4 0 2 4 R3 8 Supplement SM830252 01_欧州_Single_8 10HP_TD_SM indb 105 16 10 14 13 58 16 AMP Air Conditioning www ampair co uk sales ampair co uk ...

Страница 112: ...Downward installation fixture field supply 1 0 87 5 85 5 81 5 1 2 4 5 232 236 238 10 220 4 550 4 610 4 0 2 55 8 R10 A 4 R3 DTL A S 1 2 2 5 2 5 1 3 8 Supplement SM830252 01_欧州_Single_8 10HP_TD_SM indb 106 16 10 14 13 58 16 AMP Air Conditioning www ampair co uk sales ampair co uk ...

Страница 113: ...arge Air discharge Air discharge Air discharge 616 41 5 322 5 980 1500 Wind proof Duct Wind proof Duct 370 300 670 630 45 31 164 630 2 ø6 0 hole 624 30 550 530 630 2 637 SPOT WELDING 2 POSITION SPOT WELDING 2 POSITION 300 2 10 6 3 20 6 3 20 530 5 5 10 10 8 3 300 2 637 SPOT WELDING 4 POSITION SPOT WELDING 4 POSITION 4 ø5 0 hole 8 Supplement SM830252 01_欧州_Single_8 10HP_TD_SM indb 107 16 10 14 13 58...

Страница 114: ... 0 t 1 0 t 1 0 t 1 0 t 5 Q ty Air discharge Right side Air discharge Left side Snow proof Top side 1 Snow proof Rear side 1 Snow proof Right side 1 Snow proof Left side 1 Snow proof Top side 2 Snow proof Rear side 2 Snow proof Right side 2 Snow proof Left side 2 Packing Tapping screw 4x12 1 2 3 4 5 6 7 8 9 10 11 12 13 1 8 4 A A 616 608 640 6 ø5 HOLE 2 R2 ACTUAL SIZE 2 R 2 2 R2 SEC A A S 1 1 9 15 6...

Страница 115: ...5 23 3 1 7 25 14 615 15 6 615 2 8 12 3 1 7 615 2 100 200 1 7 1 5 0 1 7 20 12 18 3 98 3 2 R3 M4 FUNNEL EXTRUDED HOLE THIS SURFACE 凹 20 12 1 1 5 5 9 5 2 R3 5 584 3 1 0 7 2 M4 FUNNEL EXTRUDED HOLE THIS SURFACE 凹 2 ø5 HOLE 2 R 2 2 R2 R 2 2 R2 DTL FUNNEL EXTRUDED HOLE S 1 1 3 POSITION ø3 3 0 05 ø6 5 2 7 1 5 90 2 Reference diagram for Air discharge Right side field supply 3 Reference diagram for Air dis...

Страница 116: ...303 5 6 15 9 5 14 5 OVAL HOLE R2 5 SEC A A S 1 1 135 10 30 2 8 7 2 1 3 5 101 2 18 2 21 1 1 9 7 1 4 5 4 Reference diagram for Snow proof Top side 1 field supply 5 Reference diagram for Snow proof Rear side 1 field supply 8 Supplement SM830252 01_欧州_Single_8 10HP_TD_SM indb 110 16 10 14 13 58 18 AMP Air Conditioning www ampair co uk sales ampair co uk ...

Страница 117: ...0 2 2 98 5 16 23 2 R 3 588 10 9 18 12 M4 FUNNEL EXTRUDED HOLE THIS SURFACE 凹 2 R 3 98 16 2 2 8 2 8 2 1 3 2 R 3 18 12 3 M4 FUNNEL EXTRUDED HOLE THIS SURFACE 凹 5 13 5 552 5 261 261 2 R3 2 R 2 A C T U A L S I Z E 2 R 2 1 4 5 1 5 1 1 5 1 8 1 2 1 0 2 M4 FUNNEL EXTRUDED HOLE THIS SURFACE 凹 4 R 3 1047 5 555 5 1247 5 300 2 86 502 R 2 5 2 R 3 5 R 2 5 2 R 3 5 2 R 3 R 2 5 5 2 R 3 R 2 5 5 DTL FUNNEL EXTRUDED ...

Страница 118: ...1 9 7 1 4 5 690 711 M4 FUNNEL EXTRUDED HOLE THIS SURFACE 凹 2 R 3 5 261 261 18 559 2 R2 6 ø5 HOLE DLT FUNNEL EXTRUDED HOLE S 1 1 1 POSITION ø3 3 0 05 ø6 5 2 7 1 5 90 8 Reference diagram for Snow proof Top side 2 field supply 9 Reference diagram for Snow proof Rear side 2 field supply 8 Supplement SM830252 01_欧州_Single_8 10HP_TD_SM indb 112 16 10 14 13 58 19 AMP Air Conditioning www ampair co uk sal...

Страница 119: ...ZE 4 R 3 DLT FUNNEL EXTRUDED HOLE S 1 1 5 POSITION ø3 3 0 05 ø6 5 2 7 1 5 90 11 Reference diagram for Snow proof Left side 2 field supply 2 R 3 5 5 98 100 2 4 R 2 5 8 R 3 16 60 6 588 16 2 98 12 18 M4 FUNNEL EXTRUDED HOLE THIS SURFACE 凹 555 5 300 100 200 755 5 18 12 2 8 2 8 2 R3 2 22 2 R3 2 R3 1247 5 2 2 8 2 8 86 502 2 531 1 3 M4 FUNNEL EXTRUDED HOLE THIS SURFACE 凹 13 5 552 5 261 261 1 4 5 2 1 3 1 ...

Страница 120: ...STEM 8 Supplement Unit mm ADHESIVE 610 6 10 2 5 SEPARATOR EPT SEAL 12 Reference diagram for Packing field supply SM830252 01_欧州_Single_8 10HP_TD_SM indb 114 16 10 14 13 58 19 AMP Air Conditioning www ampair co uk sales ampair co uk ...

Страница 121: ...8 9 85 32 2 10 6 11 9 30 2 9 8 11 7 27 7 8 9 11 1 26 0 8 2 10 3 25 16 30 6 24 1 9 39 27 7 22 8 11 5 25 8 21 8 11 3 23 2 20 5 10 7 21 6 19 8 9 87 19 32 8 19 3 9 62 30 0 18 0 11 7 28 0 17 2 11 5 25 5 16 2 10 9 23 8 15 4 10 1 22 35 1 14 4 9 85 32 2 13 3 11 9 30 2 12 5 11 7 27 7 11 6 11 1 26 0 11 0 10 3 27 16 30 6 27 0 9 39 27 7 25 5 11 5 25 8 24 6 11 3 23 2 23 2 10 7 21 6 21 7 9 87 19 32 8 22 0 9 62 ...

Страница 122: ... 11 9 30 2 10 5 11 6 27 7 9 5 11 1 26 0 8 9 10 3 25 16 30 6 25 2 9 33 27 7 23 8 11 4 25 8 22 9 11 2 23 2 21 6 10 6 21 6 21 0 9 81 19 32 8 20 2 9 56 30 0 18 9 11 6 28 0 18 1 11 4 25 5 17 1 10 8 23 8 16 3 10 0 22 35 1 15 2 9 79 32 2 14 1 11 9 30 2 13 3 11 6 27 7 12 3 11 1 26 0 11 7 10 3 27 16 30 6 28 1 9 33 27 7 26 7 11 4 25 8 25 8 11 2 23 2 23 2 10 6 21 6 21 6 9 81 19 32 8 23 1 9 56 30 0 21 8 11 6 ...

Страница 123: ...e the Test Run 2 4 Test Run Using the Remote Controller 2 5 Precautions 2 6 Table of Self Diagnostic Functions and Corrections 2 7 System Control 2 8 Caution for Pump Down 2 9 Indoor Units 2 TEST RUN 2 TEST RUN SM830252 01_欧州_Single_8 10HP_TD_SM indb 1 16 10 07 18 35 58 AMP Air Conditioning www ampair co uk sales ampair co uk ...

Страница 124: ...connected to 1 indoor unit The indoor and outdoor unit control PCB utilizes a semiconductor memory element EEPROM The settings required for operation were made at the time of shipment Only the correct combinations of indoor and outdoor units can be used This test run section describes primarily the procedure when using the wired remote controller Power must be turned ON at least 12 hours before at...

Страница 125: ...lay TEST 20 30 THU COOL MODE START 20 30 THU CZ RTC5A CZ RTC4 Timer remote controller 1 2 3 4 Press the remote controller button for 4 seconds or longer Then press the button appears on the LCD display while the test run is in progress The temperature cannot be adjusted when in Test Run mode This mode places a heavy load on the machines Therefore use it only when performing the test run The test r...

Страница 126: ...door unit control PCB fuse will blow in order to protect the PCB Correct the wiring connections then disconnect the 2P connectors that are connected to the PCB and replace them with 2P connectors If operation is still not possible after changing the brown connectors try cutting the varistor Be sure to turn the power OFF before performing this work Fig 2 4 8 10 HP LED 2 LED 1 SW 2 SW 1 A ADD CHK PU...

Страница 127: ...Control and make the correct settings E15 displayed Indoor unit capacity is too low Same at left Same at left Check that the total capacities of the indoor and outdoor units are appropriate E16 displayed Indoor unit capacity is too high E20 displayed No serial signal is being received at all from the indoor units Check that the indoor unit power is ON and that the inter unit control wiring is conn...

Страница 128: ...inal plates 1 2 on the other indoor units Remote controller communication wiring 4 Turn ON both the indoor and outdoor unit power and perform automatic address setting from the remote controller For the automatic address setting procedure refer to 2 8 3 Models with auxiliary heaters cannot be used for communication wiring of the indoor unit power wires Use a pull box to divide the wiring Be sure t...

Страница 129: ...trol PCB 8 10 HP System address No System address 10s digit 2P DIP switch System address 1s place Rotary switch 0 Automatic address Setting at shipment 0 Both OFF ON 1 2 0 setting 1 If outdoor unit is No 1 Both OFF ON 1 2 1 setting ON OFF ON OFF LED 2 LED 1 SW 2 SW 1 A ADD CHK PUMPDOWN STOP RUN MODE CN SILENT CN ROM CN OC CN EMG CN RC CN TERMINAL SM830252 01_欧州_Single_8 10HP_TD_SM indb 7 16 10 07 ...

Страница 130: ...roller This message disappears when auto address setting is completed Repeat the same steps to perform auto address setting for each successive system Select the O D unit no by pressing the or button Select one of the O D unit no for auto address by pressing the or button Approximately about 10 minutes are required When auto address setting is completed the units return to normal stopped status ST...

Страница 131: ...ng number of indoor units at the time of auto address setting Simultaneously Alternating 4 C T R Z C 5A C T R Z C Blinking indicator Cancel Auto address 1 Assigning Request concerning recording the indoor outdoor unit combination Nos After auto address setting has been completed be sure to record them for future reference List the outdoor main unit system address and the addresses of the indoor un...

Страница 132: ...ndoor unit that is connected to the remote controller Only the address of the indoor unit that is connected to the remote controller can be checked 3 Press the button again to return to normal remote controller mode CZ RTC5A High spec wired remote controller Keep pressing the and buttons simultaneously for 4 or more seconds The Maintenance func screen appears on the LCD display Maintenance func 1 ...

Страница 133: ...rminal plate for remote controller wiring switch main Optional Optional Remote controller switch sub Ground Ground Indoor unit Outdoor unit Remote controller Remote controller setting mode Press and hold the 2 buttons for several seconds simultaneously A Select the Code no 1 2 3 Select the Set data The indicator illuminates after blinking Press Code no Item Set data 0000 0001 01 Main sub Sub Main ...

Страница 134: ... circuit This outdoor unit cannot collect more than the rated refrigerant amount as shown by the nameplate on the back If the amount of refrigerant is more than that recommended do not conduct a pump down In this case use another refrigerant collecting system CAUTION 1 2 3 4 5 SM830252 01_欧州_Single_8 10HP_TD_SM indb 12 16 10 07 18 36 01 AMP Air Conditioning www ampair co uk sales ampair co uk ...

Страница 135: ...ctric Wiring Diagram 3 2 3 2 Indoor Units Electric Wiring Diagram 3 3 High Static Pressure Ducted Type 3 3 4 Way Cassette Type 3 4 SM830252 01_欧州_Single_8 10HP_TD_SM indb 1 16 10 19 18 48 17 AMP Air Conditioning www ampair co uk sales ampair co uk ...

Страница 136: ...3 2 3 3 1 Outdoor Units Electric Wiring Diagram U 200PE2E8A U 250PE2E8A SM830252 01_欧州_Single_8 10HP_TD_SM indb 2 16 10 05 18 58 10 AMP Air Conditioning www ampair co uk sales ampair co uk ...

Страница 137: ...2 Indoor Units High Static Pressure Ducted Type S 200PE2E5 S 250PE2E5 Electric Wiring Diagram SM830252 01_欧州_Single_8 10HP_TD_SM indb 3 16 10 05 18 58 10 AMP Air Conditioning www ampair co uk sales ampair co uk ...

Страница 138: ... 0A L250V 㹋 DRAIN PUMP ECONAVI PANEL CONTROL BOARD MOTION SENSOR Y BL R ECONAVI PANEL CONTROL BOARD FLOOR TEMP SENSOR B BL R 1 1 1 4 3 1 5 1 1 1 2 3 6 3 1 3 1 2 TM1 1 1 5 1 5 1 5 1 5 2 1 2 1 2 1 3 1 1 2 3 1 1 5 1 1 6 5 6 10 11 15 16 20 21 22 4 5 6 7 1 6 1 6 1 8 1 1 2 3 6 2 1 1 7 EMG BRN FS WHT E2 E3 BLK E1 RED TA YEL ACIN BLK OC BLU RC BLU HUS RED OP1 YEL DP WHT PMV WHT 3WAY BLK TOOL BLK OPTION WH...

Страница 139: ...or Unit Control PCB ACXA73 04770 ACXA73 04750 4 8 4 3 Outdoor Unit HIC Board ACXA73 04760 4 12 4 4 Indoor Unit Control PCB Switches and Functions 4 13 SM830252 01_欧州_Single_8 10HP_TD_SM indb 1 16 10 07 18 46 45 AMP Air Conditioning www ampair co uk sales ampair co uk ...

Страница 140: ...n the remote controller 1 Once the thermostat has been switched on it cannot be switched off again by indoor air temperature control for a period of 10 minutes 2 Once the thermostat has been switched off it cannot be switched on again for a period of 3 minutes 3 When in the test run operation mode the thermostat will not be switched off by indoor air temperature control and the operation will cont...

Страница 141: ...w approximately 1 0 or less in the cooling mode or approximately 1 0 or more in the heating mode Controlled so that the inverter frequency is decreased or kept The compressor s inverter frequency is controlled in accordance with the model and operation mode The maximum and minimum frequencies for each model are shown in the table below There are cases in which frequency is limited with other contr...

Страница 142: ...mal β 54 α 52 X Setting No EEPROM setting in outdoor unit Outdoor EEPROM Amendment of X values can be made due to 4B Outdoor EEPROM Amendment of X values can be made due to 4B CODE 4B X C 2 52 1 56 5 0 58 5 1 PE type Setting at factory shipment 1 1 PEY type Setting at factory shipment 2 PE type Setting at factory shipment 1 PEY type Setting at factory shipment 2 2 60 C max E2 E1 Outdoor unit opera...

Страница 143: ...after 3 minutes If this start stop activity is repeated 5 times the alarm P03 abnormal discharge temperature occurs min E1 E2 Frequency increased Frequency increases prevented Frequency decreased 5 β 2 α Setting No EEPROM setting in outdoor unit CODE 3F for α setting α 15 15 0 0 Setting at factory shipment 9 9 Setting No CODE 40 for β setting β 15 15 0 0 9 9 TD Discharge Temperature Outdoor unit o...

Страница 144: ...ced No No No Frost adherence detection If the following conditions are satisfied during heating operations it is regarded as frost adherence is detected Frost adherence detection is performed in accordance with the ambient temperature TO and the outdoor heat exchanger temperature sensor min C1 C2 Frost adherence detection conditions a c Following satisfied condition is detected for accumulation of...

Страница 145: ...re the aperture opens wider than normal operation if the discharge temperature increases 2 Cooling Mode Heating Mode Controlled so that the suction temperature TS outdoor heat exchanger temperature C1 is between 0 degree and 2 degrees under normal conditions There are cases where the aperture opens wider than normal operation if the discharge temperature increases 11 Demand Control The operational...

Страница 146: ...4 2 Outdoor Unit Control PCB U 200PE2E8A ACXA73 04770 LED2 LED1 SW1 SW2 A ADD CHK STOP TEST MODE PUMPDOWN RUN 60 SM830252 01_欧州_Single_8 10HP_TD_SM indb 8 16 10 18 18 54 48 AMP Air Conditioning www ampair co uk sales ampair co uk ...

Страница 147: ...PE2E8A ACXA73 04750 60 B ὒᕞࢩࣥࢢࣝኳᇙ60 LQGE LED2 LED1 SW1 SW2 A ADD CHK STOP TEST MODE PUMPDOWN RUN SM830252 01_欧州_Single_8 10HP_TD_SM indb 9 16 10 18 18 54 48 AMP Air Conditioning www ampair co uk sales ampair co uk ...

Страница 148: ...etting is made by a combination of this DIP switch and SW2 If 10 19 systems are set set switch 1 10s digit to ON If 20 29 systems are set set switch 2 20s digit to ON and set switch 1 10s digit to OFF If 30 systems are set set both switch 1 10s digit and switch 2 20s digit to ON For details see Table 4 1 PUMP DOWN 2P Black Refrigerant recovery Pin Short circuit this pin to perform refrigerant reco...

Страница 149: ...F OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF 10 11 12 13 14 15 16 17 18 19 0 1 2 3 4 5 6 7 8 9 ON ON ON ON ON ON ON ON ON ON OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF 20 21 22 23 24 25 26 27 28 29 0 1 2 3 4 5 6 7 8 9 OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF ON ON ON ON ON ON ON ON ON ON 30 0 ON ON Fig 1 System controller Remote controller Outdoor Indoor Outdoor Outdoor Outdoor Indoor Indoor Indoor SM830...

Страница 150: ...4 12 4 4 3 Outdoor Unit HIC Board U 200PE2E8A U 250PE2E8A ACXA73 04760 SM830252 01_欧州_Single_8 10HP_TD_SM indb 12 16 10 07 18 46 49 AMP Air Conditioning www ampair co uk sales ampair co uk ...

Страница 151: ...P001 Jumper wire Allows selection of the T10 terminal start stop signal Refer to the Remote Control Section Setting at time of shipment Pulse signal Jumper wire cut Static signal continuous signal Fan drive CN032 2P plug WHT This terminal sends the signal to the ventilation fan when a commercially available ventilation fan is operated by the FAN button on the wired remote controller Refer to the R...

Страница 152: ...E5 S 250PE2E5 X POWER LED D002 EEPROM IC010 EMG CN044 OC CN040 DISP CN063 CHK CN062 T10 CN061 EXCT CN073 JP001 FAN DRIVE CN032 60 B SM830252 01_欧州_Single_8 10HP_TD_SM indb 14 16 10 07 18 46 53 AMP Air Conditioning www ampair co uk sales ampair co uk ...

Страница 153: ...CB A7302060 S 100PU2E5A S 125PU2E5A OPTION CN060 T10 CN061 CHK CN062 DISP FAN DRIVE CN032 JP001 POWER LED D002 EXCT CN073 RC EEPROM IC010 SM830252 01_欧州_Single_8 10HP_TD_SM indb 15 16 10 07 18 46 54 AMP Air Conditioning www ampair co uk sales ampair co uk ...

Страница 154: ... MEMO 4 16 SM830252 01_欧州_Single_8 10HP_TD_SM indb 16 16 10 07 18 46 54 AMP Air Conditioning www ampair co uk sales ampair co uk ...

Страница 155: ... cycles OFF ON too frequently 5 33 5 6 Sensor Temperature Display Function Displayed regardless of operation and stop 5 34 5 7 Table of Thermistor Characteristics 5 35 5 8 How to Remove the Compressor 5 36 5 9 How to Remove the Electrical Component Box 5 37 5 10 Symptom Thermostat in OFF continues cycles OFF ON too frequently 5 38 SM830252 01_欧州_Single_8 10HP_TD_SM indb 1 16 10 12 20 02 21 AMP Air...

Страница 156: ...ic address setting start is prohibited Duplication of main unit in group control Automatic Address Alarm The total capacity of indoor units is too low Automatic Address Alarm The total capacity of indoor units is too high Automatic Address Alarm No indoor unit connected Disconnection of wiring between main unit and additional units Contact failure of wiring Faulty indoor unit control PCB Main or A...

Страница 157: ...M trouble F29 F31 F12 Primary current control Activation of compressor s protective device Primary current CT sensor failure H03 Compressor overcurrent trouble P16 Inverter compressor trouble P29 P22 Activation of high pressure switch Compressor discharge pressure trouble P04 P05 O2 sensor error O2 sensor detected Power supply failure Open phase detected AC power supply trouble Fan motor locked re...

Страница 158: ...its connected to that system matches the number that was set and regular communications are occurring Automatic address setting is in progress Blinking alternately Alarm display LED 1 blinks M times then LED 2 blinks N times The cycle then repeats M 2 P alarm 3 H alarm 4 E alarm 5 F alarm 6 L alarm N Alarm No Example LED 1 blinks 2 times then LED 2 blinks 16 times The cycle then repeats Alarm is P...

Страница 159: ...ature Sensor TD Trouble F08 F12 F31 Outdoor Unit Nonvolatile Memory EEPROM Trouble Compressor Inlet Suction Temperature Sensor TS Trouble Outdoor Air Temperature Sensor TO Trouble H01 H02 H03 H31 HIC Trouble Primary Current CT Sensor current sensor Failure L04 L10 L18 Outdoor Unit Capacity not Set or Invalid 4 way Valve Operation Failure L13 Indoor Unit Type Setting Error Outdoor Unit Address Dupl...

Страница 160: ...1 Check 4 way valve 2 Check 4 way valve wiring 3 Check outdoor unit control PCB P04 P22 P29 H31 High pressure protection error High pressure switched ON Alarm is output when switch opened Pre trip 4 times OFF Recovery at restart Recovery at restart Recovery at restart Recovery at restart Recovery at restart Recovery at restart Overload operation of refrigerant cycle Outdoor unit fan motor trouble ...

Страница 161: ...s are connected with correct combination written in catalog 3 1 3 3 3 6 Is the indoor outdoor control line connected to more than one outdoor unit Network wired 3 2 3 4 Correct the setting Is the Terminal resistor select switch CN TERMINAL on the outdoor control PC board set to just one unit 3 3 3 5 2 1 Power on 2 3 3 1 3 2 Correct the connection Yes Yes Yes Yes Yes Yes Yes No No No No No No No 3 ...

Страница 162: ... No No 4 1 Check the indoor unit addresses from the remote control s detailed settings mode Is it Not Set 99 or is the indoor unit s address duplicated 3 3 When the network of indoor outdoor operation line was wired was the SHORT setting of the terminal resistor switch CN TERMINAL on the outdoor control PC board set on multiple units four or more 2 2 Indoor outdoor control line 4 Indoor unit contr...

Страница 163: ...the other remote controller as the main 3 3 Replace wireless remote control parts including wiring 3 4 3 5 3 4 3 5 Yes No Indoor units control PC board 1 Indoor unit power 2 Indoor outdoor operation line Yes No The indoor unit is not turned on The DISP pin of the indoor unit is shorted The signal output control PC board optional control PC board inside the indoor unit has failed There is a short o...

Страница 164: ...he other remote controller as the main Replace wireless remote control parts including wiring 4 3 4 4 Is the LED blinking on the indoor unit s control PC board 4 5 Check all items under the section Check Prior to Auto Address Setting 5 1 The nonvolatile memory EEPROM on the indoor unit s control board is either not installed improperly installed or the nonvolatile memory is faulty Correct this or ...

Страница 165: ... connector is connected to PC board properly 1 1 Sensor is correctly installed at holder side 1 2 1 2 Reconnect and check Replace sensor Correct and see what happens 1 3 Yes No 1 Sensor 2 PC board 3 Operating status Yes No Resistance between connector pins on PC board is less than 1 k ohm 2 1 Replace PC board 2 2 Yes No Peripheral temperature of outdoor unit is over 46 C 3 1 Check noise 3 3 Correc...

Страница 166: ...nsor connector is connected to PC board properly 1 1 1 2 Reconnect and check Yes No 1 Sensor 2 PC board Replace PC board because of outdoor control PC board failure 2 1 Resistance between sockets is infinity or 0 ohm 1 2 Replace sensor 2 1 Yes No F08 Outdoor Air Temperature Sensor TO Trouble Error Detection Method 1 It is judged an error when open circuit or short circuit Error Diagnosis 2 Sensor ...

Страница 167: ...Nonvolatile Memory EEPROM Trouble Error Detection Method Error Diagnosis It is judged an error based on the criteria listed below When power initially turned ON for the first time nonvolatile memory EEPROM is not installed Read values after writing onto nonvolatile memory EEPROM is inconsistent 1 2 Does EEPROM exist on the control PC board 1 1 1 2 Install EEPROM Yes No 1 PC board Incorrect EEPROM ...

Страница 168: ...detected overcurrent trip current value 1 2 2 2 3 2 2 Loose electrical wire connection 2 1 Correct wiring 2 3 Has FUSE 1 FUSE 2 blown Check the electrical conduction with tester 2 2 Yes Yes No No Replace CR board 2 3 PC board wiring Check not only in the outdoor unit stop mode but in the drive mode Trip current value 3 phase model HP horse power Heating Cooling 8 HP 10 HP 23 0A 23 0A 21 5A 21 5A f...

Страница 169: ...pressor Discharge Temperature Sensor TD Disconnected Error Detection Method In case of outdoor temperature over 5 C For 10 minutes since started variation of discharge temperature is always detected within 2 C comparing with the temperature just before starting 1 In case of outdoor temperature less than 5 C For 30 minutes since started variation of discharge temperature is always detected within 2...

Страница 170: ...n the HIC and the outdoor CR board Check the wiring one by one with a tester if there is opened and grounding The heat dissipating surface on the back of the HIC is in good contact with the heat sink heat dissipating fins of the electrical box Check for looseness in the fastening screws and the condition of the heat conducting putty 1 2 Tighten screw s add putty Yes No 3 2 Refer to alarm code P16 ...

Страница 171: ...o 10 k V 1 k to 10 k W 1 k to 10 k HIC 5 k to 20 k U 20 k to V 20 k to W 20 k to HIC 20 k to C I H C I H Tester terminals Resistance value ohm C I H C I H U 20 k to 20 k to V 20 k to W 20 k to P U V W NU RE1 RE2 3 phase outdoor unit HIC PC board ACXA73 04760 U 200PE2E8A U 250PE2E8A Outdoor Unit Control HIC PCB SM830252 01_欧州_Single_8 10HP_TD_SM indb 17 16 10 12 20 02 35 AMP Air Conditioning www am...

Страница 172: ... check whether item code 81 outdoor capacity value shows 0 or unauthorized capacity is set on the detailed settings mode display of the outdoor EEPROM If the capacity value of the item code 81 with the outdoor maintenance remote controller is incorrect recorrect and set it again After setting the capacity value be sure to reset the power supply switches of both indoor and outdoor units L13 Indoor ...

Страница 173: ...CN HOT1 or CN HOT2 connector wired from the 4 way valve connector on the HIC PC board 2 2 The parts inside the 4 way valve might have fixed at the cooling side Replace the 4 way valve 2 3 2 3 See what happens Yes No P03 Compressor Discharge Temperature Trouble Error Detection Method Error Diagnosis 1 2 When the discharge temperature is over 106 C 1 1 1 2 2 1 2 2 Adjust the refrigerant amount Repla...

Страница 174: ... finished without fail 3 4 4 1 Replace the outdoor unit fan Correct connection and or wiring Yes No While heating is operating an alarm is occurred 3 5 3 6 4 1 Yes No 2 Service valve 3 Problem around the heat exchanger P04 High Pressure Trouble Error Detection Method Error Diagnosis It is judged an error if the internal circuit of the high pressure switch is dead The electronic circuitry of the hi...

Страница 175: ... or the control PC board 4 2 4 3 Repair the expansion valve of the indoor unit Yes No 3 Problem around the heat exchanger 4 Blockage in the refrigerant circuit Error occurs when the system is operating in cooling mode 5 1 5 3 5 2 Yes No An alarm is occurred with the high pressure at 3 80 MPa with the pressure measured either as displayed by the monitoring software or with a manifold gauge at which...

Страница 176: ... check again Is the alarm triggered again 3 2 Replace the outdoor unit HIC PC board 4 1 Yes No 3 Check the outdoor unit HIC PC board 2 Check the outdoor unit CR PC board There may be a instantaneous blackout failure If there is nothing abnormal see what happens 4 1 4 Final check P05 AC Power Supply Trouble Error Detection Method Error Diagnosis Instantaneous blackout Note The work involved in diag...

Страница 177: ... control PC board 3 3 As the second detection is not done restart and see what happens if there is no error Service valve inside the outdoor unit closed 4 Mini VRF System Alarm Codes Mini VRF SYSTEM Trouble Diagnosis 1 1 3 1 2 1 Yes No 1 System configuration Is the indoor EEPROM setting item code 0B on the indoor unit s control PC board set to 0001 2 1 After correcting the setting 3 1 4 1 Yes No 2...

Страница 178: ...is fully opened Compressor s discharge temperature exceeds 95 C Alarm occurs in the following cases 1 1 Yes No 1 Adjustment of refrigerant amount Recharge with additional refrigerant 1 2 1 2 Check leakage of refrigeration leak test See what happens Yes No Replace leaking part with a new one Insufficient gas level Check whether or not pressure level is normal SM830252 01_欧州_Single_8 10HP_TD_SM indb...

Страница 179: ... Correct 2 4 Yes No 2 3 Disconnected parts miswiring and or poor connections loose are observed in the connections of outdoor board s that are connected by wiring from the HIC board Correct 2 5 Yes No 2 4 Disconnected parts miswiring and or poor connections loose are observed in the connections of HIC boards connected by wiring from the CR board Correct 2 6 Yes No 2 5 Disconnected parts miswiring ...

Страница 180: ... high pressure saturation temperature is 43 C or less the secondary current of the inverter is high The frequency Hz ends up dropping due to the current 5 6 Replace the compressor See what happens Yes No Tends to have insufficient refrigerant charge in the system 5 5 Adjust the amount of refrigerant 5 6 Yes No 4 Check the situation 5 Check operation Dividing the outdoor EEPROM INV operation time b...

Страница 181: ...ter Excepting the parts of value is 0 short circuit it is acceptable if a small resistance value appears as a reference value unless the HIC board IPM Pass Fail Tests Tester terminals Resistance value ohm U 1 k to 5 k V 1 k to 5 k W 1 k to 5 k U 1 k to 5 k V 1 k to 5 k W 1 k to 5 k NU 5 k to 10 k U 100 k to V 100 k to W 100 k to P 100 k to P NU Tester terminals Resistance value ohm P NU U 100 k to...

Страница 182: ...motor s rotating signal cannot be detected normally 1 2 Are the connectors CN FM_UP and CN FM_LO firmly connected to the outdoor control PC board lock engaged 3 Turn the power on and run the unit again is P22 triggered again Or can you see or hear anything that is obviously wrong in its rotation Replace the outdoor control PC board If it fails to operate normally even after replacing the outdoor c...

Страница 183: ... not be loose Does it operate normally Yes No See what happens See what happens The results of the pass fail tests for the following HIC PC board IPM show it to be outside the range of the resistance of a conforming part Checking for looseness of compressor terminals by wiggling them has the adverse effect of loosening them so do not do it Evaluate them by discoloration of wire insulation near the...

Страница 184: ...r unit HIC PC board ACXA73 04760 U 200PE2E8A U 250PE2E8A Outdoor Unit Control HIC PCB P U V W NU RE1 RE2 SM830252 01_欧州_Single_8 10HP_TD_SM indb 30 16 10 12 20 02 41 AMP Air Conditioning www ampair co uk sales ampair co uk ...

Страница 185: ...up Control Error Error Detection Method Other indoor unit alarms within the group 1 Survey the indoor unit that alarms other than P31 in the indoor unit group and specify the causes of failure SM830252 01_欧州_Single_8 10HP_TD_SM indb 31 16 10 12 20 02 41 AMP Air Conditioning www ampair co uk sales ampair co uk ...

Страница 186: ...implified measurement method is used Set the tester to the 12 V range if the value displayed is approximately 4 V then the voltage is normal If the voltage is normal measure the resistance between connector pin 5 and pins 1 through 4 Resistance between pin 5 and pins 1 through 4 should be approximately 46 for all If the result is 0 or then replace the coil SM830195 00 indb 52 2011 09 30 15 41 52 S...

Страница 187: ...es See operational status 2 2 Yes No 2 2 Discharge temperature is over 80 C in stop mode and does not decrease Connect outdoor maintenance remote controller to RC socket on outdoor unit main control PC board and check alarm messages Replace discharge temperature sensor 2 3 Yes No 2 3 Demand value always stays low The value is lower than 70 Excluding 1 unlimited Connect outdoor maintenance remote c...

Страница 188: ...outdoor unit on the remote controller NOTE The temperature display appears as for units that are not connected If monitor mode is engaged while normal operation is in progress only the parts of the LCD display shown in the figure will change Other parts continue to display the same information as during normal operation Item code Meaning of Code Indoor unit data 02 Indoor unit intake temp 03 Indoo...

Страница 189: ... TS Sensor Heat Exchanger Temp C1 Sensor Heat Exchanger Temp C2 Sensor 2 Discharge Temp TD Sensor Resistance k Temperature C Resistance k Temperature C 0 10 20 30 40 50 60 70 80 90 100 110 0 40 60 80 100 120 140 160 180 200 20 Resistance k Temperature C SM830252 01_欧州_Single_8 10HP_TD_SM indb 35 16 10 12 20 02 42 AMP Air Conditioning www ampair co uk sales ampair co uk ...

Страница 190: ...emove the bolts 3 and then remove the washer and rubber spacer 6 Cut off the compressor side s suction tube because the suction tube is solid and unmovable See the diagram below 7 Remove the discharge side s brazing part 1 See the diagram below NOTE Protect the sensor part sheet metal rubber lead wire and clamper 8 Pull the compressor toward you 9 Remove the suction side s brazing part 1 of the cu...

Страница 191: ...cted to the electrical component box in the unit 4 Remove the fixture screws 4 as shown in the diagram and remove the electrical component box NOTE Be sure to remove the upper left side screw marked by in the diagram because that screw cannot be seen from the front side Inspection panel Outdoor unit before removal of front panel Electrical component box after removal Fixture screws 4 for electrica...

Страница 192: ...mode and does not decrease Connect outdoor maintenance remote controller to RC socket on outdoor unit main control PC board and check alarm messages Replace discharge temperature sensor 2 3 Yes No 2 3 Demand value always stays low The value is lower than 70 Excluding 1 unlimited Connect outdoor maintenance remote controller to RC socket on outdoor unit main control PC board and check alarm message...

Страница 193: ...6 3 6 4 Monitoring Operations Display of Indoor Unit and Outdoor Unit Sensor Temperatures 6 8 6 5 Monitoring the Outdoor Unit Alarm History Display of Outdoor Unit Alarm History 6 10 6 6 Settings Modes Setting the Outdoor Unit EEPROM 6 11 SM830252 01_欧州_Single_8 10HP_TD_SM indb 1 16 10 11 13 50 50 AMP Air Conditioning www ampair co uk sales ampair co uk ...

Страница 194: ...ons 1 Functions Button operations can be used to perform the following functions Start stop of all indoor units Switching between cooling and heating Test run of all indoor units High speed operation of indoor units Do not use with actual units This may damage the devices 2 Display The following can be displayed Alarm details display No of indoor outdoor units Unit Nos of connected indoor outdoor ...

Страница 195: ...ns Normal display functions Connect the special service checker wiring to the outdoor unit PCB The connection is shown in the figure below When connecting the special service checker wiring to the remote controller CZ RTC4 cut out the wire as shown in the figure below because the connector of the remote controller cannot be used directly Special service checker wiring Top case Back side CZ RTC4 2P...

Страница 196: ...ode of the indoor unit with the lowest unit No l All units test run Fig 6 2 Operation The Check button can be used to start and stop a test run for all indoor units Press and hold for 4 seconds to turn ON During the test run is displayed The status of test runs performed from the indoor unit remote controller is not displayed on the outdoor unit maintenance remote controller l Double speed Fig 6 3...

Страница 197: ...compressor 7 segment display Compressor 1 operating time 0 99999999 hours Outdoor unit power ON time 0 99999999 hours Compressor 1 operation count 0 65535 times Alarm history 1 most recent Display only Alarm code and unit No of unit where alarm occurred are displayed alternately 0 CCU 1 4 Outdoor unit Alarm history 2 Alarm history 3 Alarm history 4 Alarm history 5 Alarm history 6 Alarm history 7 A...

Страница 198: ... 1 8 1 appears when there is only 1 outdoor unit Locations where 1 2 and 3 are displayed as shown in Fig 6 4 01 No of connected indoor units 4 units connected Sample displays 02 Unit Nos 1 2 3 and 4 are connected Fig 6 4 Fig 6 5 Fig 6 6 A A LED 1 2 3 A SM830252 01_欧州_Single_8 10HP_TD_SM indb 6 16 10 11 13 50 53 AMP Air Conditioning www ampair co uk sales ampair co uk ...

Страница 199: ...it No 1 Display of unit Nos 1 and 2 Display of unit Nos 1 2 and 3 Display of unit Nos 1 2 3 and 4 NOTE The change of the colon display between unit Nos 1 20 to unit Nos 21 40 occurs automatically every 10 seconds However the display does not change if there are no higher number units connected To change the display to the higher number units before 10 seconds have passed press the Flap button n Th...

Страница 200: ...itor mode using the indoor unit remote controller 2 Press the button and select the indoor unit to monitor 3 Press the temperature setting and buttons and select the item code of the temperature to monitor The unit No of the selected indoor unit and the temperature data are displayed 4 To end monitoring press the Check button The display returns to the normal display NOTE The display does not blin...

Страница 201: ...data 0A Discharge temp TD 0b 0C 0d Intake temp TS 0E Outdoor unit heat exchanger temp C1 0F Outdoor unit heat exchanger temp C2 10 11 Outdoor air temp TO 12 13 Current value CTL2 14 Current value CTL1 15 Outdoor MV value MOV1 16 19 Frequency Depending on the model some items may not be displayed SM830252 01_欧州_Single_8 10HP_TD_SM indb 9 16 10 11 13 50 54 AMP Air Conditioning www ampair co uk sales...

Страница 202: ...Press the button and select the outdoor unit for which to monitor the alarm history 3 Press the temperature setting and buttons and select the item code for the alarm history The select outdoor unit address the item code and the alarm history alarm data are displayed The outdoor unit address is displayed as R C XX YY System XX Outdoor unit system address R C XX Outdoor unit system address YY Outdo...

Страница 203: ...tops blinking and remains lit During this mode is displayed blinking The outdoor unit address display section displays ALL the item code and number DN value in the table and the setting data 6 digits The setting data is displayed in 6 digits The display changes between the first 3 digits Fig C and the last 3 digits Fig D D C and D are displayed alternately C When the first 3 digits are displayed t...

Страница 204: ... cooling thermostat OFF 0 Invalid P 1 Measures against smell 1A Demand 1 current 0 0 40 40 45 45 75 75 P 130 130 1 No control 1B Demand 2 current 0 0 40 40 45 45 50 50 P 130 130 1 No control 1D Current control level 0 40 1 45 12 100 16 120 18 130 19 1 Invalid P 2B DP operation time for slime measures 20 20 minutes 30 30 minutes P 40 40 minutes 50 50 minutes 60 60 minutes For details see 5 Outdoor ...

Страница 205: ...Detailed Setting Items 7 7 7 5 Simple Setting Items 7 11 7 6 Detailed Setting Items 7 13 7 7 Remote Controller Servicing Functions 7 17 7 8 Test Run Function 7 19 7 REMOTE CONTROLLER FUNCTIONS SECTION 7 1 SM830252 01_欧州_Single_8 10HP_TD_SM indb 1 16 10 13 11 01 58 AMP Air Conditioning www ampair co uk sales ampair co uk ...

Страница 206: ...on the remote controller LCD display Fig 7 1 At this time the indoor unit fan or all indoor unit fans in the case of group control begins operating If group control is in effect press the button and select the address unit No of the indoor unit to set At this time the fan at the indoor unit begins operating If unit No is displayed the same setting will be made for all indoor units Press the temper...

Страница 207: ...le settings and restart Simple setting end screen appears on the LCD display Select YES and press the button Procedure of CZ RTC5A Fig 7 2 START 20 30 THU CZ RTC5A Maintenance func 1 Outdoor unit error data 2 Service contact 3 RC setting mode 4 Test run Sel Page Confirm 20 30 THU Maintenance func 5 Sensor info 6 Servicing check 8 Detailed settings Sel Page Confirm 20 30 THU 7 Simple settings Simpl...

Страница 208: ... Lo 0006 LL Lo Heating intake temperature shift 0000 No shift 0001 Shifts intake temperature 1 C down 0002 Shifts intake temperature 2 C down 0003 Shifts intake temperature 3 C down 0004 Shifts intake temperature 4 C down 0005 Shifts intake temperature 5 C down 0006 Shifts intake temperature 6 C down Electric heater installation 0000 No heater 0001 Heater installed Humidifying when heater thermost...

Страница 209: ...mple settings items can also be set at this time Press and hold the and buttons simultaneously for 4 seconds or longer If group control is in effect press the button and select the address unit No of the indoor unit to set At this time the fan at the indoor unit begins operating If unit No is displayed the same setting will be made for all indoor units Press the temperature setting buttons to sele...

Страница 210: ...o by pressing the or button and press the button The Exit detailed settings and restart Detailed setting end screen appears on the LCD display Select YES and press the button Maintenance func 1 Outdoor unit error data 2 Service contact 3 RC setting mode 4 Test run Sel Page Confirm 20 30 THU Maintenance func 5 Sensor info 6 Servicing check 8 Detailed settings Sel Page Confirm 20 30 THU 7 Simple set...

Страница 211: ...main unit 0099 Not set Cooling intake temperature shift 010 Shifts intake temperature 10 C down 009 Shifts intake temperature 9 C down 001 Shifts intake temperature 1 C down 0000 No intake temperature shift 0001 Shifts intake temperature 1 C up 0009 Shifts intake temperature 9 C up 0010 Shifts intake temperature 10 C up Automatic stop time after operation start 0000 Function disabled 0001 Stops au...

Страница 212: ...018 18 C Lower limit at shipment 0019 19 C 0029 29 C 0030 30 C Upper limit at shipment Upper limit Lower limit Auto heat cool 0017 17 C Lower limit at shipment 0018 18 C 0026 26 C 0027 27 C Upper limit at shipment Humidifier operation 0000 Normal 0001 Ignore heat exchanger temperature conditions Filter CN70 input switching 0000 Filter input differential pressure switch input 0001 Alarm input for t...

Страница 213: ...0013 Control temperature 13 C 0014 Control temperature 14 C 0025 Control temperature 25 C 0026 Control temperature 26 C Fan output switching 0000 Output linked with fan ON when indoor unit fan is operating 0001 Fan mode operation output Drain pump delayed start time 0000 No delayed start 0001 1 min delayed start 0002 2 min delayed start 0058 58 min delayed start 0059 59 min delayed start 0060 60 m...

Страница 214: ...tting 2 with standard ECONAVI panel 0006 Air flow blocking kit for 2 way air flow Timer function change prohibit 0000 Function disabled 0001 Function enabled Smudging control 0000 No smudging control Fan tap setting External static pressure of the rated air flow volume 0001 Type 200 60Pa Type 250 72Pa Setting at shipment 0002 140Pa 0003 270Pa Repeat timer switching 0000 Function disabled 0001 Func...

Страница 215: ...tes that there is no corresponding filter 7 5 Simple Setting Items 03 Central control address Set when using a central control device Used when setting the central control address manually from the remote controller Standard High fouling Standard High fouling High fouling Set when is selected for the degree of filter fouling item code 04 Operating mode priority change Note 1 NOTE There are other m...

Страница 216: ...ing heating Can be set when the body thermostat is used 07 Electric heater installation Set when cost distribution is performed using an AMY central control system or similar system and when an optional electric heater is installed This is unrelated to control of the electric heater 08 Humidifying when heater thermostat is OFF Normally humidifying does not occur when the thermostat is OFF during h...

Страница 217: ...1b Forced thermostat ON time Use this setting to change the time for forced operation at installation or servicing from 5 minutes to 4 minutes 1E Temperature shift for cooling heating change in auto heat cool mode Auto heat cool selects the operating mode automatically based on the difference between the room temperature and the temperature set on the remote controller This setting establishes a s...

Страница 218: ...ote controller The ventilation fan can operate linked with the start and stop of the indoor unit or can be operated even when the indoor unit is stopped Use a ventilation fan that can accept the no voltage A contact as the external input signal In the case of group control the fans are operated together They cannot be operated individually 32 Switching to remote controller sensor This setting is u...

Страница 219: ... reduction mode 46 DC flap swing mode Selects the swing operation mode for the flap 5d DC fan tap setting Sets the DC fan tap according to the purpose of use Change the settings data at the same time 5F Stop at time set for OFF timer after operation starts This setting enables a function that stops operation when the amount of time set for the OFF timer has passed after remote controller operation...

Страница 220: ...the example shown in the figure above DIP switch 1 is OFF DIP switch 2 is ON DIP switch 3 is OFF On Table 1 check out the Item code 5D setting data that corresponds to the intended application and the optional parts to be used 3 When setting the fan speed using a wired remote controller optional parts CZ RTC4 On Table 1 check out the Item code 5d setting data that corresponds to the intended appli...

Страница 221: ... settings Automatic address Automatic address setting based on command from the wired remote controller Automatic reset Entire system stops Address change Change of indoor unit address Press the button CZ RTC4 Press and hold the button for 4 seconds or longer Press and hold the and buttons for 4 seconds or longer Press and hold the and buttons for 4 seconds or longer Press and hold the and buttons...

Страница 222: ...ture display Temperature display from each sensor 5 Sensor info Servicing check display Alarm history display 6 Service check Simple settings Filter lifetime operating mode priority central control address and other settings 7 Simple settings Press the button Restart When settings are made from a remote controller the indoor unit where that remote controller is connected stops Detailed settings Sy...

Страница 223: ...AN operation modes The outdoor units will not operate for approximately 3 minutes after the power is turned ON and after operation is stopped If correct operation is not possible an error code is displayed on the remote controller LCD display To prevent continuous test runs this remote controller includes a timer function that cancels the test run after 60 minutes The operation is possible even if...

Страница 224: ...Service contact 3 RC setting mode 4 Test run Sel Page Confirm 20 30 THU Maintenance func 1 Outdoor unit error data 2 Service contact 3 RC setting mode 4 Test run Sel Page Confirm 20 30 THU Confirm Test run Change 20 30 THU Test run ON 3 Press the button TEST will be displayed on the LCD display 4 Press the button Test run will be started Test run setting mode screen appears on the LCD display TEST...

Страница 225: ...ect the item code to change Press the button to return to normal remote controller display 3 4 4 4 3 2 5 1 1 2 3 4 5 Sensor Temperature Display Function displayed regardless of whether unit is operating or stopped Item code Meaning of Code Indoor unit data 02 Indoor unit intake temp 03 Indoor unit heat exchanger temp E1 04 Indoor unit heat exchanger temp E2 05 06 07 08 09 Outdoor unit data 0A Disc...

Страница 226: ...ormation by pressing the or button Maintenance func 1 Outdoor unit error data 2 Service contact 3 RC setting mode 4 Test run Sel Page Confirm 20 30 THU Maintenance func 5 Sensor info 6 Servicing check 8 Detailed settings Sel Page Confirm 20 30 THU 7 Simple settings Sensor info Unit no Code no Data Sel Next 20 30 THU 01 02 00 0028 0026 0026 1 1 Sensor info Unit no Code no Data Scroll 20 30 THU 01 0...

Страница 227: ...e each menu If you wish to see the next screen instantly press the or button Select 7 Simple settings on the LCD display and press the button The Simple settings screen appears on the LCD display Select the Unit no by pressing the or button for changes The indoor unit fan operates only at the selected indoor unit Automatic address setting Checking indoor unit addresses Maintenance func 10 Set elec...

Страница 228: ... MEMO 7 24 SM830252 01_欧州_Single_8 10HP_TD_SM indb 24 16 10 13 11 02 06 AMP Air Conditioning www ampair co uk sales ampair co uk ...

Страница 229: ...oor Units Simultaneously Group Control 8 8 Using the Remote Controller 8 9 For Best Results 8 10 Addresses 8 9 8 11 8 12 8 13 8 14 8 14 8 11 Emergency Operation 8 12 Miscellaneous Settings 8 13 Before Requesting Service How to Install the Wireless Remote Controller Receiver 8 14 Common to All Models 8 15 CZ RWSC3 8 16 8 16 CZ RWSU3 8 20 8 17 Common to All Models 8 22 8 HOW TO INSTALL THE WIRELESS ...

Страница 230: ... and turn the power off if you sense unusual smells or other irregularities Do not swallow the battery Do not repair Contact your dealer before moving the system Moving and Repair Precautions Electric shock and damage to the system can result Continuing operation when the system is out of order can result in electric shock fire and damage to the system Contact your dealer Never repair the system b...

Страница 231: ... and stops the fan When the air conditioner is started or stopped the fan starts or stops at the same time appears on the display of the remote controller when the fan is operating 15 Sensor button Used this button to activate the temperature sensor on the remote controller instead of the one on the indoor unit The temperature sensor on the indoor unit is selected before shipment At this time on t...

Страница 232: ...e cleaned FILTER lamp NOTE If non cooling heating free type is being used it will beep twice and the operating lamp will light up on the display if the timer and standby lamps blink alternately a confl ict between the heating and cooling exists so the uncannot operate in the desired mode On models that do not have an Auto function even if Auto is selected it works in the same way When the local op...

Страница 233: ...TE 8 3 Setting the Current Time After changing the batteries and pressing reset be sure to reset the current time When reset is pressed the current time reverts to 1 Press for two seconds or more 2 Set the hour with of the If you press and hold the button the time changes quickly 3 Set the minutes with of the If you press and hold the button the time changes quickly 4 Pressing completes the time s...

Страница 234: ...y Disconnect the power to the indoor unit and contact the dealer where the product was purchased Auto Operation Only when identical refrigerant system inside all the indoor units or cooling heating free type are under control as one group It heats or cools automatically via the differences between the set temperature and the room temperature Dry Operation Depending on the indoor unit used the remo...

Страница 235: ...nges to a steady display indicating settings are complete After the timer setting is displayed for three seconds the display reverts to the current time Combining ON and OFF Timers Setting the ON and OFF timers respectively Checking the timer setting If you press either for the or the the scheduled time is displayed for four seconds When no timer setting has been made it displays Initial Setting C...

Страница 236: ...Heat Modes Cool Dry Modes Never try to manually move the flap up down wind direction plate that is operated by the remote controller When the unit stops the flap up down wind direction plate automatically faces downwards When the unit is in heating standby the flap up down wind direction plate faces upward Also bear in mind that the flap starts swinging after the heating standby mode is released b...

Страница 237: ...Use Press from the location you wish to mount the remote controller and make sure the signal is received properly Pull the remote controller forward to remove it Don t get the remote controller too far away from the receiver This may cause a malfunction Be sure to keep the remote controller in the same room as the receiver compatible wireress remote controller addresses can be set up to avoid cros...

Страница 238: ...ss Switch The position of the receiver s address switch does not matter For 1 2 and 3 set the switch on the left and for 4 5 and 6 to the right Please do not hold the Emergency Operation button of the indoor unit down while the indoor unit s display lamps are blinking one after another Make sure to operate while the indoor unit is stopped The address of indoor unit is set to ALL at the time of the...

Страница 239: ...1 Emergency Operation Start Stop CZ RWSC3 CZ RWSU3 Start press Emergency Operation of the receiver If the indoor temperature is 24 C or greater when the unit starts running it will act as a cooling mode If the indoor temperature is less than 24 C when the unit starts running it will act as a heating mode CZ RWSU3 is of receivers inside indoor unit Stop press Emergency Operation of the receiver aga...

Страница 240: ...lding down the buttons below every time is pressed the remote controller s display changes Whatever is being displayed when you release is set Setting Item Operation Button Setting Content Remote Controller Display Remote controller operation mode display setting when is pressed Press while pressing Heat Pump with Auto Heat Pump without Auto Dedicated air conditioner Clock display setting Press wh...

Страница 241: ...roller s operation mode display See Page 8 12 After putting the batteries in the remote controller even when it is operated the display does not change Press the Reset button on the remote controller See Page 8 5 The timer cannot be set Make the settings when the remote controller is in Operation Display See Page 8 7 If the problem persists even after you check the foregoing items stop the unit di...

Страница 242: ...e remote controllers When wiring remote controllers be sure to double check the terminal numbers of the indoor unit before connecting them so there are no mistakes in the wiring Damage will occur if high voltage e g supply voltage is applied 1 It is not possible to use more than one wireless remote controller kit with one indoor unit A receiver located separately can be used at the same time 2 If ...

Страница 243: ... Front side Rear side CZ RWSU3 Screw PCB cover Receiver PCB Main Sub selector switch for remote controllers 4 OFF Main ON Sub Set its address 1 to 3 All set at OFF when shipped from the factory ON 1 2 3 4 8 15 SM830252 01_欧州_Single_8 10HP_TD_SM indb 15 16 10 12 15 51 26 AMP Air Conditioning www ampair co uk sales ampair co uk ...

Страница 244: ...or death CAUTION This symbol refers to a hazard or unsafe practice which can result in personal injury or product or property damage WARNING Turn off the circuit breaker of the units before installation Ask your dealer or professionals for installation and electric work This receiver shall be installed in accordance with National Wiring Regulations Securely connect and fix the Do not allow the con...

Страница 245: ... and remove the burr with e l i f a Mount the top case Align the claws of the top case and then align the claws of the bottom case Mount the bottom case to the wall Connect the remote controller wiring Arrange the wires along the groove of the case Wood screw supplied Claw Hole for screw e h t x i f o t l l a W receiver Claw 2 places Top case Back side Remove the coating Approx 6 mm Remove the she...

Страница 246: ...in is recommended The remote controller and the receiver can be connected to any indoor unit for operation Note 1 2 1 2 R1 R2 R1 R2 R1 R2 R1 R2 RC wiring field supply No polarity Indoor unit Indoor unit Indoor unit Indoor unit 1 2 1 2 R1 R2 Terminals for RC wiring b u S r e v i e c e R b u S r e v i e c e R Wired RC Main Wired RC Main Indoor unit Using 1 indoor unit Using more than 1 indoor unit R...

Страница 247: ...erformed Temperature cannot be changed The test operation mode is automatically turned off in 60 minutes To prevent continuous test operation Outdoor units do not operate for approx 3 minutes after the power is turned on or operation is stopped Self diagnostics table and detected contents The Alarm Display as shown in the table below expresses the alarm contents displayed when the wired remote con...

Страница 248: ...the corner cover to remove it Corner cover Ceiling panel 3 Wire the receiver Hang the string of the receiver on the pin of the ceiling panel Receiver Pin String Pass the wiring from the wireless receiver section into the slit See Wiring for the Receiver Fix the wiring with the clamper supplied while leaving enough length of wiring to remove the receiver Slit Fix with the clamper supplied a Cut thi...

Страница 249: ...5 Setting Address Switches When more than 1 receiver is installed in the same room setting addresses prevents interference For how to change addresses of wireless remote controllers see the operating instructions of wireless remote controllers To change the receiver s address remove the cover from the receiver s PCB and set No 1 to No 3 of the 003 DIP switch on PCB Remote Controller Address Displa...

Страница 250: ...or related to the compressor H01 H31 Error in indoor settings L01 L03 L05 L09 Simultaneously Error in outdoor settings L04 L10 L31 Simultaneously Inconsistency in Air Heat Including an auto temp setting for a model without auto temp settings Alternately Oil Alarm Same as operation of outdoor protection device Alternately Test Run Simultaneously Sensor Button 2 Room Temperature Sensor Settings Comm...

Страница 251: ...F Setting Off Note 2 C 5 Time Display 24 Hour No Display AM PM 24 Hour 6 Ventilation Fan ON OFF Off No Display On OFF Note 3 7 Cool temp Max 05 35 C 30 8 Cool temp Min 05 35 C 18 9 Heat temp Max 05 35 C 26 Note 4 10 Heat temp Min 05 35 C 16 11 Dry temp Max 05 35 C 30 12 Dry temp Min 05 35 C 18 13 Auto temp Max 05 35 C 27 14 Auto temp Min 05 35 C 17 16 Address Setting Max Value 00 ALL only 01 31 06...

Страница 252: ...201610 SM830252 01_欧州_Single_8 10HP_TD_SM indb 1 16 10 11 12 56 31 AMP Air Conditioning www ampair co uk sales ampair co uk ...