SVC 820-Tankless Gas Trouble Shooting Manual Page |
69
69
35 – Error Code Diagnostic Chart
Check resistance for all Thermistors at
Molex Connector “R”
NO
YES
YES
NO
Is the resistance
for all
Thermistors OK?
Go to appropriate Sensor Error Code to
diagnose:
1.
Inlet: Error Code 31
2.
Heat Exchanger: Error Code 32
3.
Outlet: Error Code 33
4.
Ambient: Error Code 34
Did the unit
lockout on Error
Code 35?
Attempt to operate the unit again
Replace Control Board
The water heater appears to be operating
normally
Ambient Thermistor Data Table
64DV; 84DV; 95DV: 7K – 23K Ohms
64X; 84X; 95X: 2K – 72K Ohms
H95DV; H95X: 2K – 72K Ohms