Verify the PDB
Set 'clear_fault_action' to 'true'
->
3.
Verify that the PDB is no longer considered faulty, then return to this procedure.
See
“Determine if the PDB Is Faulty” on page 237
4.
Verify that the PDB is reporting temperatures.
->
show /SYS/PDB/T_IN_PS value
/SYS/PDB/T_IN_PS
Properties:
value = 23.500 degree C
->
Related Information
■
■
“Determine if the PDB Is Faulty” on page 237
246
Netra Server X5-2 Service Manual • October 2016