Table 1-14 (Cont.) Environmental Requirements for Oracle Exadata Storage
Expansion Rack with Exadata Storage Server with Sun Fire X4270 M2 Servers
Environmental
Component
Oracle Exadata
Storage Expansion
Full Rack
Oracle Exadata
Storage Expansion
Half Rack
Oracle Exadata
Storage Expansion
Quarter Rack
Air flow front-to-back
(subject to actual data
center environment)
Maximum:
Approximately 1,980
CFM
Typical:
Approximately 1,390
CFM
Maximum:
Approximately 1,090
CFM
Typical:
Approximately 760
CFM
Maximum:
Approximately 530
CFM
Typical:
Approximately 375
CFM
IP Addresses
43 for Ethernet
network, assuming
single cluster
18 for InfiniBand
network
25 for Ethernet
network, assuming
single cluster
9 for InfiniBand
network
14 for Ethernet
network, assuming
single cluster
4 for InfiniBand
network
Network drops
Minimum of 2 network
drops
Minimum of 2 network
drops
Minimum of 2 network
drops
External connectivity
12 InfiniBand ports
12 InfiniBand ports
12 InfiniBand ports
1.1.17 General Environmental Requirements for Single Servers
The environmental requirements for single servers are shown in the following tables.
Table 1-15 Environmental Requirements for X7-2 Single Servers
Environmental
Component
Exadata Storage
Server X7-2 -
Extreme Flash
Exadata Storage
Server X7-2 - High
Capacity
Database Server
X7-2
Weight
28.1 kg (62 lbs)
33.1 kg (73 lbs)
20.4 kg (45 lbs)
Acoustic levels
78 db(A)
78 db(A)
78 db(A)
Power
Maximum: 0.6 kVA
Typical: 0.4 kVA
(varies based on
application load)
Maximum: 0.6 kVA
Typical: 0.4 kVA
(varies based on
application load)
Maximum: 0.665 kW
(0.678 kVA)
Typical: 0.466 kW
(0.475 kVA) (varies
based on application
load)
Cooling
Maximum: 1,866 BTU/
hour (1,969 kJ/hour)
Typical: 1,307 BTU/
hour (1,378 kJ/hour)
Maximum: 2,006 BTU/
hour (2,117 kJ/hour)
Typical: 1,404 BTU/
hour (1,482 kJ/hour)
Maximum: 2,269 BTU/
hour (2,394 kJ/hour)
Typical: 1,588 BTU/
hour (1,676 kJ/hour
Air flow front-to-back
(subject to actual data
center environment)
Maximum:
Approximately 86
CFM
Typical:
Approximately 60
CFM
Maximum:
Approximately 93
CFM
Typical:
Approximately 65
CFM
Maximum:
Approximately 105
CFM
Typical:
Approximately 74
CFM
Chapter 1
General Environmental Requirements
1-26