9: Distance from the center of the rear casters to the rear of the rack is 173.7
mm (6.83 inches)
•
10: Depth between the front and rear casters is 828.6 mm (32.62 inches)
•
11: Distance between the rear casters and the rear of the rack is 162.4 mm
(6.39 inches)
•
12: Distance from the center of rear casters to the side of the rack is 96.4 mm
(3.80 inches)
•
13: Width between the center of the rear casters is 407.2 mm (16.03 inches)
2.
Lower the leveling feet to the floor to share the load with the casters, as shown in
(page 4-8) using the SW 12 mm wrench.
Figure 4-4 Securing Oracle Exadata Rack Using the Leveling Feet
4.3.2.2 Stabilize Oracle Exadata Rack X7 with Leveling Feet
The rack contains four leveling feet that can be lowered to stabilize the rack.
The leveling feet can be used even when the rack is permanently secured to the floor.
The four leveling feet share the load with the casters. This increases the footprint of
the rack which improves stability and helps prevent rack movement.
To adjust the leveling feet, do the following:
1.
Locate the four leveling feet located at the bottom corners of Oracle Exadata
Rack. The following figure shows the location of the leveling feet on the bottom of
Oracle Exadata Rack. The image dimensions include the doors attached to the
rack.
Chapter 4
Placing Oracle Exadata Rack in Its Allocated Space
4-8