(page 5-38) Threshold Values for Oracle Exadata Database Machine
X2-2 (with X4170 M2 and X4270 M2 servers) Quarter Rack with Three-phase,
High-voltage PDU
(page 5-37) lists the threshold values for Oracle Exadata Database
Machine Quarter Rack using a single-phase, low-voltage PDU.
Table 5-33 Threshold Values for Oracle Exadata Database Machine X2-2 (with
X4170 M2 and X4270 M2 servers) Quarter Rack with Single-phase, Low-voltage
PDU
PDU
Module/Phase
Info Low
Threshold
Pre Warning
Threshold
Alarm
Threshold
A
Module 1, phase
1
0
10
13
A
Module 1, phase
2
0
6
8
A
Module 1, phase
3
0
0
0
B
Module 1, phase
1
0
0
0
B
Module 1, phase
2
0
6
8
B
Module 1, phase
3
0
10
13
(page 5-37) lists the threshold values for Oracle Exadata Database
Machine Quarter Rack using a three-phase, low-voltage PDU.
Table 5-34 Threshold Values for Oracle Exadata Database Machine X2-2 (with
X4170 M2 and X4270 M2 servers) Quarter Rack with Three-phase, Low-voltage
PDU
PDU
Module/Phase
Info Low
Threshold
Pre Warning
Threshold
Alarm
Threshold
A and B
Module 1, phase
1
0
12
15
A and B
Module 1, phase
2
0
11
14
A and B
Module 1, phase
3
0
5
7
(page 5-38) lists the threshold values for Oracle Exadata Database
Machine Quarter Rack using a single-phase, high-voltage PDU.
Chapter 5
Configuring the Power Distribution Units
5-37