Reracking
Considerations
Yes
No
N/A
Comment
Does the target
rack meet the
following
minimum load
capacity?
•
19 kg (41.89
lb) / RU
•
785 kg
(1730.63 lb)
total
Is the rack a four-
post rack
(mounting at both
front and rear)?
Note: Two-post
racks are not
compatible.
Does the target
rack's horizontal
opening and unit
vertical pitch
conform to
ANSI/EIA 310-
D-1992 or IEC
60297
standards?
Does the target
rack have
RETMA rail
support?
Note: Oracle
Exadata Rack
requires 19
inches (483 mm)
for RETMA rail
spacing width.
The minimum
rack width of 600
mm (23.63
inches) is
recommended to
accommodate
the PDU and
cable harnesses
on the side. If the
rack is less than
600 mm wide,
then it must have
additional depth
to accommodate
mounting behind
the server CMAs.
Appendix A
Reracking Checklists
A-20