Table 1-18 Environmental Requirements for X4-8, X5-8, and X6-8 Single
Servers
Environmental Component
Database Server X5-8 and
X6-8
Database Server X4-8
Weight
93.4 kg (206 lbs)
93.4 kg (206 lbs)
Acoustic levels
81 db(A)
81 db(A)
Power
Maximum: 3.5 kVA
Typical: 2.4 kVA (varies based
on application load)
Maximum: 3.7 kVA
Typical: 2.6 kVA (varies based
on application load)
Cooling
Maximum: 11,601 BTU/hour
(12,239 kJ/hour)
Typical: 8,121 BTU/hour
(8,568 kJ/hour)
Maximum: 12,284 BTU/hour
(12,959 kJ/hour)
Typical: 8,599 BTU/hour
(9,072 kJ/hour)
Air flow front-to-back (subject
to actual data center
environment)
Maximum: Approximately 537
CFM
Typical: Approximately 376
CFM
Maximum: Approximately 569
CFM
Typical: Approximately 398
CFM
1.2 Space Requirements
Oracle Exadata Database Machine X7-2 and X7-8
The Oracle Exadata X7-2 and X7-8 racks use a different rack than its predecessors.
The space requirements are as follows:
•
Height: 2000 mm (78.74 inches)
•
Width: 600 mm (23.62 inches)
•
Depth: 1235 mm with doors attached, from handle to handle (48.6 inches)
The minimum ceiling height for the cabinet is 2914 mm (114.72 inches), measured
from the true floor or raised floor, whichever is higher. This includes an additional 914
mm (36 inches) of space required above the rack height for maintenance access, as
described in
(page 1-34). The space surrounding the cabinet must not
restrict the movement of cool air between the air conditioner and the front of the
systems within the cabinet, or the movement of hot air coming out of the rear of the
cabinet.
Oracle Exadata Racks up to Oracle Exadata Database Machine X6-8
All Oracle Exadata Racks up to Oracle Exadata X6-8 use the same rack, and have the
same space requirements. The space requirements are as follows:
•
Height: 1998 mm (78.66 inches)
•
Width: 600 mm with side panels (23.62 inches)
•
Depth: 1200 mm (47.24 inches)
The minimum ceiling height for the cabinet is 2912 mm (114.65 inches), measured
from the true floor or raised floor, whichever is higher. This includes an additional 914
mm (36 inches) of space required above the rack height for maintenance access, as
described in
(page 1-34). The space surrounding the cabinet must not
Chapter 1
Space Requirements
1-28