![Oracle EXADATA X5-2 Скачать руководство пользователя страница 234](http://html1.mh-extra.com/html/oracle/exadata-x5-2/exadata-x5-2_installation-and-configuration-manual_1646081234.webp)
Table 5-3 Threshold Values for Oracle Exadata Database Machine X4-2 Full
Rack with Single-phase, High-voltage PDU
PDU
Module/Phase
Info Low
Threshold
Pre Warning
Threshold
Alarm
Threshold
A
Module 1, phase
1
0
18
23
A
Module 1, phase
2
0
16
20
A
Module 1, phase
3
0
18
23
B
Module 1, phase
1
0
18
23
B
Module 1, phase
2
0
16
20
B
Module 1, phase
3
0
18
23
(page 5-22) lists the threshold values for Oracle Exadata Database
Machine X4-2 Full Rack using a three-phase, high-voltage PDU.
Table 5-4 Threshold Values for Oracle Exadata Database Machine X4-2 Full
Rack with Three-phase, High-voltage PDU
PDU
Module/Phase
Info Low
Threshold
Pre Warning
Threshold
Alarm
Threshold
A and B
Module 1, phase
1
0
18
21
A and B
Module 1, phase
2
0
18
21
A and B
Module 1, phase
3
0
16
21
5.3.1.2.2 PDU Thresholds for Oracle Exadata Database Machine X4-2 Half Rack
The following tables list the threshold values for Oracle Exadata Database Machine
X4-2 Half Rack:
•
(page 5-23) Threshold Values for Oracle Exadata Database Machine
X4-2 Half Rack with Single-phase, Low-voltage PDU
•
(page 5-23) Threshold Values for Oracle Exadata Database Machine
X4-2 Half Rack with Three-phase, Low-voltage PDU
•
(page 5-23) Threshold Values for Oracle Exadata Database Machine
X4-2 Half Rack with Single-phase, High-voltage PDU
•
(page 5-24) Threshold Values for Oracle Exadata Database Machine
X4-2 Half Rack with Three-phase, High-voltage PDU
(page 5-23) lists the threshold values for Oracle Exadata Database
Machine X4-2 Half Rack using a single-phase, low-voltage PDU.
Chapter 5
Configuring the Power Distribution Units
5-22