5.3.1.5.2 PDU Thresholds for Oracle Exadata Database Machine X2-2 (with X4170 and
X4275 servers) Half Rack
The following tables list the threshold values for Oracle Exadata Database Machine
Half Rack:
•
(page 5-41) Threshold Values for Oracle Exadata Database Machine
X2-2 (with X4170 and X4275 servers) Half Rack with Single-phase, Low-voltage
PDU
•
(page 5-41) Threshold Values for Oracle Exadata Database Machine
X2-2 (with X4170 and X4275 servers) Half Rack with Three-phase, Low-voltage
PDU
•
(page 5-42) Threshold Values for Oracle Exadata Database Machine
X2-2 (with X4170 and X4275 servers) Half Rack with Single-phase, High-voltage
PDU
•
(page 5-42) Threshold Values for Oracle Exadata Database Machine
X2-2 (with X4170 and X4275 servers) Half Rack with Three-phase, High-voltage
PDU
(page 5-41) lists the threshold values for Oracle Exadata Database
Machine Half Rack using a single-phase, low-voltage PDU.
Table 5-41 Threshold Values for Oracle Exadata Database Machine X2-2 (with
X4170 and X4275 servers) Half Rack with Single-phase, Low-voltage PDU
PDU
Module/Phase
Info Low
Threshold
Pre Warning
Threshold
Alarm
Threshold
A
Module 1, phase
1
0
21
24
A
Module 1, phase
2
0
13
17
A
Module 1, phase
3
0
0
0
B
Module 1, phase
1
0
0
0
B
Module 1, phase
2
0
13
17
B
Module 1, phase
3
0
21
24
(page 5-41) lists the threshold values for Oracle Exadata Database
Machine Half Rack using a three-phase, low-voltage PDU.
Table 5-42 Threshold Values for Oracle Exadata Database Machine X2-2 (with
X4170 and X4275 servers) Half Rack with Three-phase, Low-voltage PDU
PDU
Module/Phase
Info Low
Threshold
Pre Warning
Threshold
Alarm
Threshold
A and B
Module 1, phase
1
0
19
24
Chapter 5
Configuring the Power Distribution Units
5-41