Table 5-31 Threshold Values for Oracle Exadata Database Machine X2-2 (with
X4170 M2 and X4270 M2 servers) Half Rack with Single-phase, High-voltage PDU
PDU
Module/Phase
Info Low
Threshold
Pre Warning
Threshold
Alarm
Threshold
A
Module 1, phase
1
0
16
20
A
Module 1, phase
2
0
12
15
A
Module 1, phase
3
0
0
0
B
Module 1, phase
1
0
0
0
B
Module 1, phase
2
0
12
15
B
Module 1, phase
3
0
16
20
(page 5-36) lists the threshold values for Oracle Exadata Database
Machine Half Rack using a three-phase, high-voltage PDU.
Table 5-32 Threshold Values for Oracle Exadata Database Machine X2-2 (with
X4170 M2 and X4270 M2 servers) Half Rack with Three-phase, High-voltage PDU
PDU
Module/Phase
Info Low
Threshold
Pre Warning
Threshold
Alarm
Threshold
A and B
Module 1, phase
1
0
9
12
A and B
Module 1, phase
2
0
9
12
A and B
Module 1, phase
3
0
10
13
5.3.1.4.3 PDU Thresholds for Oracle Exadata Database Machine X2-2 (with X4170 M2
and X4270 M2 servers) Quarter Rack
The following tables list the threshold values for Oracle Exadata Database Machine
Quarter Rack:
•
(page 5-37) Threshold Values for Oracle Exadata Database Machine
X2-2 (with X4170 M2 and X4270 M2 servers) Quarter Rack with Single-phase,
Low-voltage PDU
•
(page 5-37) Threshold Values for Oracle Exadata Database Machine
X2-2 (with X4170 M2 and X4270 M2 servers) Quarter Rack with Three-phase,
Low-voltage PDU
•
(page 5-38) Threshold Values for Oracle Exadata Database Machine
X2-2 (with X4170 M2 and X4270 M2 servers) Quarter Rack with Single-phase,
High-voltage PDU
Chapter 5
Configuring the Power Distribution Units
5-36