270
GRT1-CP1-L Positioning Unit
Section 7-5
The Range 0 Tab Page is used to set a comparison range for the counter
value. The range has a lower limit (LL0) and an upper limit (UL0). The digital
output can be controlled according to the counter value in respect to this
range. Range 0 controls the digital output 0 (OUT0).
Click the
Range 0
Tab in the Edit Unit Parameters Window. The
Range 0
Tab
Page will be displayed.
■
Operation
The output will be controlled according to the relationship between the
counter value and the range settings as follows:
• If UL0 > LL0, digital output 0 will be ON when LL0
≤
Counter value
≤
UL0,
and will be OFF otherwise.
• If UL0 < LL0, digital output 0 will be OFF when UL0
≤
Counter value
≤
LL0, and will be ON otherwise.
• If UL0 = LL0, digital output 0 will be ON when LL0 = Counter value = UL0,
and will be OFF otherwise.
The following figures illustrate the first two cases.
Case 1: UL0 > LL0
UL0
LL0
CNT
OUT0
Содержание SMARTSLICE GRT1-DRT
Страница 1: ...OPERATION MANUAL Cat No W455 E1 08 SmartSlice GRT1 Series Slice I O Units ...
Страница 3: ...SmartSlice GRT1 Series Slice I O Units Operation Manual Revised December 2018 ...
Страница 4: ...iv ...
Страница 6: ...vi ...
Страница 20: ...xx EC Directives 6 ...
Страница 62: ...42 Connecting Turnback Cables Section 3 3 ...
Страница 250: ...230 Maintenance Information Window Section 7 3 Maintenance Information Window ...
Страница 292: ...272 GRT1 CP1 L Positioning Unit Section 7 5 ...
Страница 300: ...280 GRT1 END End Unit Section 8 5 Dimensions 11 9 11 9 55 7 1 5 19 5 83 5 2 9 2 9 OMRON ...
Страница 322: ...302 Troubleshooting by Unit Section 9 5 ...
Страница 350: ...330 Explicit Messages Appendix A ...
Страница 354: ...334 Power Consumption and Weight Tables Appendix C ...
Страница 356: ...336 I O Current Consumption Table Appendix D ...
Страница 364: ...344 Revision History ...
Страница 365: ......