310
Explicit Messages
Appendix A
Setting and Monitoring the Operation Time
Note
(1) The Instance ID specifies the Slice I/O Unit’s unit number (1 to 63 decimal).
(2) Specifies operation time 1.
(3) Specifies operation time 2.
(4) Reads data for both operation time 1 and operation time 2 (operation times 1, 2, 3, and 4 for Units
with 8 inputs).
(5) Specifies input 3 (only for Units with 8 inputs).
(6) Specifies input 4 (only for Units with 8 inputs).
Explicit
message
Read/
write
Function Command
Response
Service
code
Class
ID
Instance
ID
Attribute
ID
Data size
Set Value
for Opera-
tion Time
Monitor
Read
Reads the monitor
set value for the
operation time (unit:
ms) specified by the
Attribute ID.
0E hex
8E hex
01 to 40
hex
*1
8B hex
*2
93 hex
*3
B4 hex
*5
BC hex
*6
---
2 bytes
0000 to FFFF
hex
(0 to 65,535
decimal)
Write
Writes the monitor
set value for the
operation time (unit:
ms) specified by the
Attribute ID.
10 hex
8E hex
01 to 40
hex
*1
8B hex
*2
93 hex
*3
B4 hex
*5
BC hex
*6
2 bytes
0000 to FFFF
hex
(0 to 65,535
decimal)
---
Present
Value for
Operation
Time Moni-
tor
Read
Reads the present
value for the opera-
tion time (unit: ms)
specified by the
Attribute ID.
0E hex
8E hex
01 to 40
hex
*1
8A hex
*2
92 hex
*3
B3 hex
*5
BB hex
*6
---
2 bytes
0000 to FFFF
hex
(0 to 65,535
decimal)
Monitor
Status for
Operation
Time Moni-
tor
Read
Reads the monitor
status for the opera-
tion time (unit: ms)
specified by the
Attribute ID.
0E hex
8E hex
01 to 40
hex
*1
87 hex
*4
---
2 bytes
0000 to FFFF
hex
(0 to 65,535
decimal)
Operation
Time Moni-
tor Peak
Value Read
Read
Reads the peak
value for the opera-
tion time (unit: ms)
specified by the
Attribute ID.
0E hex
8E hex
01 to 40
hex
*1
8C hex
*2
94 hex
*3
B5 hex
*5
BD hex
*6
---
2 bytes
0000 to FFFF
hex
(0 to 65,535
decimal)
Operation
Time Moni-
tor Peak
Value
Reset
Reset Resets to the
present value the
peak value for the
operation time (unit:
ms) specified by the
Attribute ID.
05 hex
8E hex
01 to 40
hex
*1
8C hex
*2
94 hex
*3
B5 hex
*5
BD hex
*6
2 bytes
0000 to FFFF
hex
(0 to 65,535
decimal)
---
Operation
Time Moni-
tor History
Read
Read
Reads the history of
the monitor status
for the operation
time (unit: ms) spec-
ified by the Attribute
ID.
0E hex
8E hex
01 to 40
hex
*1
8F hex
*2
97 hex
*3
B8 hex
*5
C0 hex
*6
---
1 byte
00 hex: Value
not exceeded
01 hex: Value
exceeded
Operation
Time Moni-
tor History
Reset
Reset Resets to 0 the his-
tory of the monitor
status for the opera-
tion time (unit: ms)
specified by the
Attribute ID.
05 hex
8E hex
01 to 40
hex
*1
8F hex
*2
97 hex
*3
B8 hex
*5
C0 hex
*6
---
---
Содержание SMARTSLICE GRT1-DRT
Страница 1: ...OPERATION MANUAL Cat No W455 E1 08 SmartSlice GRT1 Series Slice I O Units ...
Страница 3: ...SmartSlice GRT1 Series Slice I O Units Operation Manual Revised December 2018 ...
Страница 4: ...iv ...
Страница 6: ...vi ...
Страница 20: ...xx EC Directives 6 ...
Страница 62: ...42 Connecting Turnback Cables Section 3 3 ...
Страница 250: ...230 Maintenance Information Window Section 7 3 Maintenance Information Window ...
Страница 292: ...272 GRT1 CP1 L Positioning Unit Section 7 5 ...
Страница 300: ...280 GRT1 END End Unit Section 8 5 Dimensions 11 9 11 9 55 7 1 5 19 5 83 5 2 9 2 9 OMRON ...
Страница 322: ...302 Troubleshooting by Unit Section 9 5 ...
Страница 350: ...330 Explicit Messages Appendix A ...
Страница 354: ...334 Power Consumption and Weight Tables Appendix C ...
Страница 356: ...336 I O Current Consumption Table Appendix D ...
Страница 364: ...344 Revision History ...
Страница 365: ......