223
Temperature Input Units
Section 6-4
9. Click the
Fix Lower Adjusting Value
Button. The lower limit adjustment
value will be stored in the Unit.
10. Adjust the upper limit value (upper adjusting value). Refer to the following
table for the appropriate resistance to input from the six-dial resistance box
to the Temperature Input Unit’s input terminals. Wait at least 1 minute for
the input to stabilize.
11. Click the
Fix Upper Adjusting Value
Button. The upper limit adjustment
value will be stored in the Unit.
12. If it is necessary to restore the upper and lower limit adjustment values to
the default settings, click the
Default Setting
Button. The settings will be
returned to the factory settings.
Model
Input type
Upper limit
adjustment input
resistance
GRT1-TS2P
PT100 (
−
200 to 850
°
C)
390
Ω
PT100 (
−
200 to 200
°
C)
180
Ω
GRT1-TS2PK
PT1000 (
−
200 to 850
°
C)
3,900
Ω
PT1000 (
−
200 to 200
°
C)
1,800
Ω
Содержание SMARTSLICE GRT1-DRT
Страница 1: ...OPERATION MANUAL Cat No W455 E1 08 SmartSlice GRT1 Series Slice I O Units ...
Страница 3: ...SmartSlice GRT1 Series Slice I O Units Operation Manual Revised December 2018 ...
Страница 4: ...iv ...
Страница 6: ...vi ...
Страница 20: ...xx EC Directives 6 ...
Страница 62: ...42 Connecting Turnback Cables Section 3 3 ...
Страница 250: ...230 Maintenance Information Window Section 7 3 Maintenance Information Window ...
Страница 292: ...272 GRT1 CP1 L Positioning Unit Section 7 5 ...
Страница 300: ...280 GRT1 END End Unit Section 8 5 Dimensions 11 9 11 9 55 7 1 5 19 5 83 5 2 9 2 9 OMRON ...
Страница 322: ...302 Troubleshooting by Unit Section 9 5 ...
Страница 350: ...330 Explicit Messages Appendix A ...
Страница 354: ...334 Power Consumption and Weight Tables Appendix C ...
Страница 356: ...336 I O Current Consumption Table Appendix D ...
Страница 364: ...344 Revision History ...
Страница 365: ......