202
Temperature Input Units
Section 6-4
Setting Procedure (Example: DeviceNet Configurator)
1,2,3...
1. In the Network Configuration Window, double-click the icon of the Slice I/O
Terminal that is to be set. Alternatively, right-click the icon and select
Pa-
rameters - Edit
. The Edit Device Parameters Window will be displayed.
2. Select the Temperature Input Unit to be edited from the
I/O Module
Tab
Page.
3. Click the
Edit
Button on the
I/O Module
Tab Page. The Edit Unit Parame-
ters Window will be displayed.
4. Select the tab page for the input where the comparator function is to be set,
and select the
Comparator
Check Box in the
Function Choice
Area.
5. Click the
Comparator
Tab and set each of the alarm values. The example
here shows the setting for
Alarm Trip Point High (HH)
.
Note
When setting the Trip Point, adjust for each input’s decimal point position and
the 1/100 Display Mode (if it is being used). Always correct the Trip Point after
changing the display mode setting or changing to an input that has a different
decimal point position.
Содержание SMARTSLICE GRT1-DRT
Страница 1: ...OPERATION MANUAL Cat No W455 E1 08 SmartSlice GRT1 Series Slice I O Units ...
Страница 3: ...SmartSlice GRT1 Series Slice I O Units Operation Manual Revised December 2018 ...
Страница 4: ...iv ...
Страница 6: ...vi ...
Страница 20: ...xx EC Directives 6 ...
Страница 62: ...42 Connecting Turnback Cables Section 3 3 ...
Страница 250: ...230 Maintenance Information Window Section 7 3 Maintenance Information Window ...
Страница 292: ...272 GRT1 CP1 L Positioning Unit Section 7 5 ...
Страница 300: ...280 GRT1 END End Unit Section 8 5 Dimensions 11 9 11 9 55 7 1 5 19 5 83 5 2 9 2 9 OMRON ...
Страница 322: ...302 Troubleshooting by Unit Section 9 5 ...
Страница 350: ...330 Explicit Messages Appendix A ...
Страница 354: ...334 Power Consumption and Weight Tables Appendix C ...
Страница 356: ...336 I O Current Consumption Table Appendix D ...
Страница 364: ...344 Revision History ...
Страница 365: ......