Unitronics 

 

 

Jazz

®

 

User Guide 

JZ20-T10/JZ20-J-T10

 

 

6 Digital Inputs including 2 HSC, 

         4 Transistor Outputs  

JZ20-T18/JZ20-J-T18

 

 

6 Digital Inputs including 2 HSC, 2 Analog/Digital Inputs,  

2 Analog Inputs, 8 Transistor Outputs 

JZ20-J-T20HS 

 

 

 

6 Digital Inputs including 3 HSC/Shaft-encoder,  

2 Analog/Digital Inputs, 2 Analog Inputs,  

10 Transistor Outputs  

 

General Description 

 

The products listed above are micro-PLC+HMIs, rugged programmable logic controllers that comprise 
built-in operating panels. 

Detailed Installation Guides containing the I/O wiring diagrams for these models, technical specifications, 
and additional documentation are located in the Technical Library in the Unitronics website:   

https://unitronicsplc.com/support-technical-library/

 

  

Alert Symbols and General Restrictions 

When any of the following symbols appear, read the associated information carefully. 

Symbol 

Meaning 

Description 

 

Danger 

The identified danger causes physical and property damage. 

 

Warning 

The identified danger could cause physical and property damage. 

Caution

 

Caution 

Use caution. 

 Before using this product, the user must read and understand this document.  

 All examples and diagrams are intended to aid understanding, and do not guarantee operation. 

Unitronics accepts no responsibility for actual use of this product based on these examples. 

 Please dispose of this product according to local and national standards and regulations. 

 Only qualified service personnel should open this device or carry out repairs. 

 

 Failure to comply with appropriate safety guidelines can cause severe injury or property 

damage. 

 

 Do not attempt to use this device with parameters that exceed permissible levels. 

 To avoid damaging the system, do not connect/disconnect the device when power is on. 

 

Environmental Considerations 

 

 

 Do not install in areas with: excessive or conductive dust, corrosive or flammable gas,  

moisture or rain, excessive heat, regular impact shocks or excessive vibration, in  
accordance with the standards given in the product’s technical specification sheet. 

 Do not place in water or let water leak onto the unit. 

 Do not allow debris to fall inside the unit during installation. 

 

 

Ventilation: 10mm space required between controller’s top/bottom edges & enclosure walls. 

 Install at maximum distance from high-voltage cables and power equipment. 

 

 

 

 

 

Содержание JZ20-T10

Страница 1: ...on Before using this product the user must read and understand this document All examples and diagrams are intended to aid understanding and do not guarantee operation Unitronics accepts no responsibi...

Страница 2: ...r for communication and cloning Integral USB Port This may be used for programming purposes Note the USB port and an Add on module cannot be physically connected at the same time Add on during install...

Страница 3: ...ing Controllers offering a terminal block with pitch of 5mm 26 12 AWG wire 0 13 mm2 3 31 mm2 Controllers offering a terminal block with pitch of 3 81mm 26 16 AWG wire 0 13 mm2 1 31 mm2 1 Strip the wir...

Страница 4: ...known to be non hazardous Please note that it is recommended to back up all data retained in RAM in order to avoid losing data when changing the battery while the power is switched off Date and time i...

Страница 5: ...al inputs If I0 I1 I4 are set as high speed counters without reset I2 I3 I5 can function as normal digital inputs 4 The following information concerns JZ20 T18 JZ20 J T18 and JZ20 J T20HS in addition...

Страница 6: ...ust be connected Input wiring I0 I7 npn sink Input wiring I0 I7 pnp source Input wiring I0 I5 pnp source I6 I7 npn sink JZ20 J T20HS Note The inputs are arranged in two groups You can wire one group a...

Страница 7: ...T20HS Unitronics 7 HSC input wiring npn sink HSC input wiring pnp source Shaft encoder wiring npn sink Shaft encoder wiring pnp source Digital Outputs Outputs Power Supply JZ20 T10 JZ20 J T10 JZ20 T1...

Страница 8: ...l source Analog Input wiring current JZ20 T18 JZ20 J T18 JZ20 J T20HS only 2 or 3 wire AN0 AN1 4 wire AN0 AN1 Analog Input wiring voltage Note If either I6 or I7 is wired as an npn digital input the r...

Страница 9: ...Logic 1 npn sink 17 28 8VDC for Logic 0 0 5VDC for Logic 1 I0 I5 I6 I7 Input current 3 7mA 24VDC 1 2mA 24VDC Response time 10mSec typical 20mSec typical Input cable length Up to 100 meters unshielded...

Страница 10: ...ency 50Hz resistive load 0 5Hz inductive load 3kHz with resistance load 4k only O0 O2 in JZ20 J T20HS Short circuit protection Yes Short circuit indication Yes On voltage drop 0 5VDC maximum Power sup...

Страница 11: ...d in the operating panel faceplate to custom label the keys and logo picture An extra logo slide is included A complete set of blank slides is available by separate order Program Ladder code memory 48...

Страница 12: ...er to Page 2 Mounting Panel mounting Insert into cut out 117 x 89mm WxH 4 606 x 3 504 DIN rail mounting Snap unit onto the DIN rail The information in this document reflects products at the date of pr...