248
Parameter List
Appendix
Note
Parameters with the following mark are supported only by version 1.1 Temperature Controllers:
Refer to
Functional Upgrades
on page xxvi for details on upgraded functionality.
Variable
type
CompoWay/F
Modbus
Parameter name
Setting (monitor) range
De-
fault
Unit
Attrib-
utes
Target Unit
Category
Add-
ress
Address
TC4/
TC2
HFU
E1 (A1)
Can be
changed
while
stopped.
0100
0340
Control Output 1 Assignment
H' 00000000: Disabled (0)
H' 00000001: Temperature Controller error (1)
47
---
IO
●
---
H' 00000002: All channels All alarm OR (2)
H' 00000003: All channels All alarm AND (3)
H' 00000004: All channels Alarm 1 OR (4)
H' 00000005: All channels Alarm 2 OR (5)
H' 00000006: All channels Alarm 3 OR (6)
H' 00000007: All channels Alarm 1 AND (7)
H' 00000008: All channels Alarm 2 AND (8)
H' 00000009: All channels Alarm 3 AND (9)
H' 0000000A: All channels Input error OR (10)
H' 0000000B: All channels RSP Input error OR (11)
●
Not used.
H' 0000000D: All channels HB (Heater Burnout) alarm
OR (13)
H' 0000000E: All channels HS (Heater Short) alarm OR
(14)
H' 0000000F: All channels OC (Heater Overcurrent)
alarm OR (15)
Not used.
H' 00000020: CH1 Alarm 1 (32)
H' 00000021: CH1 Alarm 2 (33)
H' 00000022: CH1 Alarm 3 (34)
H' 00000023: CH1 All alarm OR (35)
H' 00000024: CH1 All alarm AND (36)
H' 00000025: CH1 Input error (37)
H' 00000026: CH1 RSP Input error (38)
Not used.
H' 00000028: CH1 HB (Heater Burnout) alarm (40)
H' 00000029: CH1 HS (Heater Short) alarm (41)
H' 0000002A: CH1 OC (Heater Overcurrent) alarm (42)
H' 0000002B: CH1 PV (43)
H' 0000002C: CH1 SP (44)
H' 0000002D: CH1 Local SP (45)
H' 0000002E: CH1 Remote SP (46)
H' 0000002F: CH1 Control output (heating) (47)
H' 00000030: CH1 Control output (cooling) (48)
Not used.
H' 0000003A: ch1 Transfer Output (Heating)
(58)
TC2
H' 0000003B: ch1 Transfer Output (Cooling)
(59)
Not used.
●
H' 00000040: Channel 2: The same as channel 1. (64)
···
H' 00000060: Channel 3: The same as channel 1. (96)
TC4
··
·
H' 00000080: Channel 4: The same as channel 1. (128)
···
0101
0341
Control Period 1
H' 00000000 to H' 00000063 (0 to 99)
(0.5 s period when set to 0.)
2
s
IO
●
---
0102
0342
Linear Output 1 Type
H' 00000000: 4 to 20mA (0)
H' 00000001: 0 to 20mA (1)
0
---
IO
TC2
---
0103
0343
Output Scaling Upper Limit 1
H' FFFFF831 to H' 0000270F (
−
1999 to 9999)
100
---
IO
●
---
0104
0344
Output Scaling Lower Limit 1
H' FFFFF831 to H' 0000270F (
−
1999 to 9999)
0
---
IO
●
---
0105
0345
Decimal Point C1
H' 00000000: **** (No decimal point) (0)
H' 00000001: ***.* (1)
H' 00000002: **.** (2)
H' 00000003: *.*** (3)
0
---
IO
●
---
0106
0346
Minimum output ON/OFF
width 1
H' 00000000 to H' 000001F4 (0.0 to 50.0)
1.0
%
IO
●
---
Not used.
0200
0540
Control Output 2 Assignment
The rest are the same as from Control Output 1
Assignment to Decimal Point C1.
TC4: 79
TC2: 79
···
···
···
0300
0740
Control Output 3 Assignment
TC4: 111
TC2: 32
···
···
···
0400
0940
Control Output 4 Assignment
TC4: 143
TC2: 64
···
···
···
V1.1
V1.1
V1.1
V1.2
V1.1
Содержание EJ1 EtherCAT
Страница 2: ...EJ1 Modular Temperature Controllers User s Manual Revised July 2008 ...
Страница 3: ...iv ...
Страница 19: ...xx ...
Страница 213: ...188 Detailed Description of Services Section 6 4 ...
Страница 227: ...202 Detailed Description of Services Section 7 5 ...
Страница 251: ...226 Determining the Error from the Current Situation for Heater Burnout Alarm Errors Section 8 8 ...
Страница 303: ...278 Index ...
Страница 305: ......