186
Detailed Description of Services
Section 6-4
• LSP Change and RSP Change
Sets SP Mode (LSP (local SP)/RSP (remote SP).
An operation error will occur if autotuning is already being performed for a
specified channel.
• Reset Error
Clears the following errors: heater burnout latch, HS alarm latch, heater
overcurrent latch, heater overcurrent, and operation during error (selec-
tion B).
• Alarm Latch Cancel
Cancels alarm latches. This command is enabled when the alarm latch
function is used.
• Save RAM Data
Writes the settings for parameters that can be changed during operation
to EEPROM.
• Parameter Initialization
Returns the current set values to their default values. The setting is not
saved to EEPROM, however, so Save RAM Data 2 should be executed if
required.
Execute Save RAM Data 2 only when control operations are stopped for
all channels.
• Save RAM Data 2
Writes settings (except read-only settings) to EEPROM.
Execute Save RAM Data 2 only when control operations are stopped for
all channels.
• Register Unit Configuration
Registers or resets the G3ZA Unit Configuration. Refer to
4-7-4 Using
G3ZA Multi-channel Power Controllers
for details on Unit configuration
registration.
Execute Save RAM Data 2 only when control operations are stopped for
all channels.
2.
Response Codes
Response code
Error name
Cause
1001
Command too long
The command is too long.
1002
Command too short The command is not long enough.
1100
Parameter error
The command code or related information is
wrong.
0402
Operation error
(0402)
The command cannot be executed because
the model or version is not the same.
2201
Operation error
(2201)
The command cannot be executed during
operation.
2202
Operation error
(2202)
The command cannot be executed because
operation is stopped.
2203
Operation error
(2203)
• The command cannot be executed in nor-
mal mode.
• The command cannot be executed in man-
ufacturer mode.
7011
Operation error
(7011)
The command cannot be executed due to a
device error.
7012
Operation error
(7012)
The command cannot be executed due to a
configuration error.
7013
Operation error
(7013)
The command cannot be executed because
the operation command cannot be received.
Execute retries until the 7013 response code
is reset.
Содержание EJ1 EtherCAT
Страница 2: ...EJ1 Modular Temperature Controllers User s Manual Revised July 2008 ...
Страница 3: ...iv ...
Страница 19: ...xx ...
Страница 213: ...188 Detailed Description of Services Section 6 4 ...
Страница 227: ...202 Detailed Description of Services Section 7 5 ...
Страница 251: ...226 Determining the Error from the Current Situation for Heater Burnout Alarm Errors Section 8 8 ...
Страница 303: ...278 Index ...
Страница 305: ......