255
Status Lists
Appendix
Status Lists
Use the Status listed in the following tables to check EJ1 status.
TC4/TC2
C0 Status
Note
(1) The values are displayed as follows: CT1 = channel 1 and CT2 = channel 2.
(2) The values are displayed as follows: OUT1 = channel 1, OUT2 = channel 2, OUT3 = channel 3, and
OUT4 = channel 4.
(3) The status is displayed as follows: OUT3 = channel 3 and OUT 4 = channel 4.
Bit position
Status
Bit description
Meaning
0
1
Bit 0
Heater Overcurrent
(See note 1.)
No error
Error
The heater current value exceeds
110.0 A.
Bit 1
Heater Current Hold
(See note 1.)
Updated
Hold
The heater current monitor has not been
updated because the control output ON
time is less than 100 ms.
Bit 2
Not used.
Bit 3
Not used.
Bit 4
Not used.
Bit 5
Not used.
Bit 6
Input error
No error
Error
An input error has occurred.
Bit 7
Not used.
Bit 8
Control output
(See note 2.)
OFF
ON
Control output status can be checked.
Bit 9
Control output
(See note 3.)
OFF
ON
Control output status can be checked.
Bit 10
HB alarm
OFF
ON
An alarm has occurred.
Bit 11
Not used.
Bit 12
Alarm Output 1
OFF
ON
An alarm 1 error has occurred.
Bit 13
Alarm Output 2
OFF
ON
An alarm 2 error has occurred.
Bit 14
Alarm Output 3
OFF
ON
An alarm 3 error has occurred.
Bit 15
Not used.
Bit 16
Event input 1
OFF
ON
Event input 1 status can be checked.
Bit 17
Event input 2
OFF
ON
Event input 2 status can be checked.
Bit 18
Not used.
Bit 19
Not used.
Bit 20
Write Mode
Backup
RAM write
Write mode can be confirmed.
Bit 21
EEPROM
RAM = EEPROM RAM
≠
EEPROM
Can confirm whether or not the setting is
registered in EEPROM.
Bit 22
ST
ST is stopped.
ST is executing.
ST Execute/Stop status can be checked.
Bit 23
AT Execute/Cancel
AT is stopped
AT execution in
progress
Can confirm AT Execute/Cancel.
Bit 24
RUN/STOP
Run
Stop
Run/stop can be confirmed.
Bit 25
Communications Writing
---
ON (enabled)
Communications Writing is always ON
(enabled).
Bit 26
Auto/Manual
Auto
Manual
Auto/manual can be confirmed.
Bit 27
SP Mode
LSP
RSP
SP mode can be confirmed.
Bit 28
Not used.
Bit 29
Not used.
Bit 30
SP Ramp
OFF
Ramp is executing. SP Ramp status can be checked.
Bit 31
Not used.
C0/80 0001
V1.2
V1.2
V1.2
V1.2
V1.2
V1.2
V1.2
V1.2
V1.2
Содержание EJ1 EtherCAT
Страница 2: ...EJ1 Modular Temperature Controllers User s Manual Revised July 2008 ...
Страница 3: ...iv ...
Страница 19: ...xx ...
Страница 213: ...188 Detailed Description of Services Section 6 4 ...
Страница 227: ...202 Detailed Description of Services Section 7 5 ...
Страница 251: ...226 Determining the Error from the Current Situation for Heater Burnout Alarm Errors Section 8 8 ...
Страница 303: ...278 Index ...
Страница 305: ......