4
Names of Parts
Section 1-1
Setting Switch 2
(SW2) Settings
EJ1
@
-TC Basic Units
Note
To use an HFU with distributed positioning, turn ON pin number 8 on SW2 on
the TC Unit connected at the left end of the Block.
Refer to
SECTION 2 Preparations
for information on wiring.
Note
Make sure power to the Unit is turned OFF before making settings for No. 6.
Settings can be made for No. 6 can be turned ON or OFF with the power ON.
EJ1
@
-HFU (Advanced
Unit)
SW2
Meaning
3
Set to ON when using the Modbus communications protocol for port B.
OFF: The setting for port B communications protocol is used.
ON: Modbus is used.
4 to 5
Set the baud rate of port B.
4 = OFF, 5 = OFF: Use the baud rate parameter setting for port B
(default: 9.6 kbps).
4 = ON, 5 = OFF: 19.2 kbps
4 = OFF, 5 = ON: 38.4 kbps
4 = ON, 5 = ON: 115.2 kbps
6
Set to ON to display the output status on the operation indicators.
OFF: The operation status is displayed (PWR, RUN, ERR, and ALM).
ON: The output status is displayed (outputs 1, 2, 3, and 4).
Note
Normally keep this pin set to OFF so that the operation status
can be checked.
7
ON: G3ZA Multi-channel Power Controller in operation
ON when using a G3PW Power Controller.
8
Use when an HFU is used and Units are distributed. (See note.)
V1.2
V1.2
V1.2
V1.1
HFU
TC4/2
EDU
TC4/2
TC4/2
TC4/2
TC4/2
TC4/2
EDU
EDU
Turn ON pin 8 on SW2.
Turn ON pin 8 on SW2.
SW2
Meaning
3 to 7
Not used (OFF)
8
• EJ1
@
-HFU
@
-NFLK
OFF: RS-485 is selected.
ON: RS-232C is selected.
• EJ1
@
-HFU
@
-NFL2
Not used (OFF).
Содержание EJ1 EtherCAT
Страница 2: ...EJ1 Modular Temperature Controllers User s Manual Revised July 2008 ...
Страница 3: ...iv ...
Страница 19: ...xx ...
Страница 213: ...188 Detailed Description of Services Section 6 4 ...
Страница 227: ...202 Detailed Description of Services Section 7 5 ...
Страница 251: ...226 Determining the Error from the Current Situation for Heater Burnout Alarm Errors Section 8 8 ...
Страница 303: ...278 Index ...
Страница 305: ......