234
Parameter List
Appendix
Note
(1) The values in the current bank will be used for all set values.
(2) The decimal point position is determined by the sensor selection.
Note
The decimal point position is determined by the sensor selection.
Variable
type
CompoWay/F
Modbus
Parameter name
Setting (monitor) range
De-
fault
Unit
Attrib-
utes
Target Unit
Category
Add-
ress
Address
TC4/
TC2
HFU
C1 (81)
(See
note.)
Can be
changed
during
operation.
Not used.
0003
---
Set Point - CH1
H' FFFFF831 to H' 0000270F (
−
1999 to 9999) (See note 2.) ---
EU
ch
●
---
0004
---
Alarm Value 1 - CH1
H' FFFFF831 to H' 0000270F (
−
1999 to 9999) (See note 2.) ---
EU
ch
●
---
0005
---
Alarm Upper Limit Value 1 - CH1 H' FFFFF831 to H' 0000270F (
−
1999 to 9999) (See note 2.) ---
EU
ch
●
---
0006
---
Alarm Lower Limit Value 1 - CH1 H' FFFFF831 to H' 0000270F (
−
1999 to 9999) (See note 2.) ---
EU
ch
●
---
0007
---
Alarm Value 2 - CH1
H' FFFFF831 to H' 0000270F (
−
1999 to 9999) (See note 2.) ---
EU
ch
●
---
0008
---
Alarm Upper Limit Value 2 - CH1 H' FFFFF831 to H' 0000270F (
−
1999 to 9999) (See note 2.) ---
EU
ch
●
---
0009
---
Alarm Lower Limit Value 2 - CH1 H' FFFFF831 to H' 0000270F (
−
1999 to 9999) (See note 2.) ---
EU
ch
●
---
Not used.
0103
---
Set Point - CH2
The rest are the same as channel 1.
···
···
···
0203
---
Set Point - CH3
···
···
···
0303
---
Set Point - CH4
···
···
···
8000
00C0
Present Bank Set Point - CH1
H' FFFFF831 to H' 0000270F (
−
1999 to 9999) (See note 2.) 0
EU
BANK
●
---
8001
00C1
Present Bank Set Point - CH2
H' FFFFF831 to H' 0000270F (
−
1999 to 9999) (See note 2.) 0
EU
BANK
●
---
8002
00C2
Present Bank Set Point - CH3
H' FFFFF831 to H' 0000270F (
−
1999 to 9999) (See note 2.) 0
EU
BANK
●
---
8003
00C3
Present Bank Set Point - CH4
H' FFFFF831 to H' 0000270F (
−
1999 to 9999) (See note 2.) 0
EU
BANK
●
---
Variable
type
CompoWay/F
Modbus
Parameter name
Setting (monitor) range
De-
fault
Unit
Attrib-
utes
Target Unit
Category
Add-
ress
Address
TC4/
TC2
HFU
C4 (84)
Monitor
0000
0000
Device A Status
See
Status Lists
on page 255.
---
---
Common
●
●
0001
0001
Device Error Status
See
Status Lists
on page 255.
---
---
Common
●
●
0002
0002
Configuration Error A Status
See
Status Lists
on page 255.
---
---
Common
●
●
0003
0003
Configuration Error B Status
See
Status Lists
on page 255.
---
---
Common
●
---
0004
0004
Internal Communications Error Status See
Status Lists
on page 255.
---
---
Common
●
---
0005
0005
I/O Error Status
See
Status Lists
on page 255.
---
---
Common
●
---
0006
0006
I/O Alarm A Status
See
Status Lists
on page 255.
---
---
Common
●
---
0007
0007
I/O Alarm B Status
See
Status Lists
on page 255.
---
---
Common
●
---
Not used.
0009
0009
I/O Notification A Status
See
Status Lists
on page 255.
---
---
Common
●
---
Not used.
000B
000B
Error Channel A Status
See
Status Lists
on page 255.
---
---
Common
●
---
Not used.
000F
000F
Basic Unit/Expand Unit Error
See
Status Lists
on page 255.
---
---
Common
●
---
0010
0010
Basic Unit/Expand Unit Alarm
See
Status Lists
on page 255.
---
---
Common
●
---
Not used.
0012
0012
Output Status
See
Status Lists
on page 255.
---
---
Common
●
---
0013
0013
Device B Status
See
Status Lists
on page 255.
---
---
Common
●
●
Not used.
0020
0020
Version
H' 00000000 to H' 0000FFFF
---
---
Common
●
●
Not used.
0100
0200
Process Value - CH1
H' FFFFF831 to H' 0000270F (
−
1999 to 9999) (See note.)
---
EU
ch
●
---
0101
0201
Channel Status - CH1
See
Status Lists
on page 255.
---
---
ch
●
---
0102
0202
Channel Alarm Status - CH1
See
Status Lists
on page 255.
---
---
ch
●
---
0103
0203
Internal SP - CH1
H' FFFFF831 to H' 0000270F (
−
1999 to 9999) (See note.)
---
EU
ch
●
---
0104
0204
Local SP Monitor - CH1
H' FFFFF831 to H' 0000270F (
−
1999 to 9999) (See note.)
---
EU
ch
●
---
0105
0205
Remote SP Monitor - CH1
H' FFFFF831 to H' 0000270F (
−
1999 to 9999) (See note.)
---
EU
ch
●
---
0106
0206
Bank No. Monitor - CH1
H' 00000000 to H' 00000003 (0 to 3)
---
---
ch
●
---
0107
0207
MV Monitor (Heating) - CH1
H' FFFFFFCE to H' 0000041A (
−
5.0 to 105.0)
---
%
ch
●
---
0108
0208
MV Monitor (Cooling) - CH1
H' FFFFFFCE to H' 0000041A (
−
5.0 to 105.0)
---
%
ch
●
---
Not used.
010B
020B
Decimal Point Monitor - CH1
H' 00000000 to H' 00000003 (0 to 3)
---
---
ch
●
---
Not used.
0200
0400
Process Value - CH2
The rest are the same as channel 1.
···
···
···
Note: The Remote SP Monitor - CH2 parameter is supported only by the TC4.
0300
0600
Process Value - CH3
Note: The Remote SP Monitor - CH3 parameter cannot be used.
TC4
---
··
·
··
·
··
·
0400
0800
Process Value - CH4
Note: The Remote SP Monitor - CH4 parameter cannot be used.
TC4
---
···
···
···
Содержание EJ1 EtherCAT
Страница 2: ...EJ1 Modular Temperature Controllers User s Manual Revised July 2008 ...
Страница 3: ...iv ...
Страница 19: ...xx ...
Страница 213: ...188 Detailed Description of Services Section 6 4 ...
Страница 227: ...202 Detailed Description of Services Section 7 5 ...
Страница 251: ...226 Determining the Error from the Current Situation for Heater Burnout Alarm Errors Section 8 8 ...
Страница 303: ...278 Index ...
Страница 305: ......