173
FINS-mini Text
Section 6-3
6-3-4
Communications Data
Note
Refer to
Parameter List
on page 233.
6-3-5
List of FINS-mini Command Services
For details on each service, refer to
6-4 Detailed Description of Services
.
Note
G3ZA set values can be read from the Basic Unit connected to the G3ZA. The
Basic Unit has variables for use with the G3ZA. The G3ZA set values can be
read and written by reading and writing these variables.
Setting (monitor) value
Communications data
(See note.)
Negative values
Decimal point
Hexadecimal
Double word (8 digits)
Word
(4 digits)
2's complement
The decimal point is removed and the result is
converted to hexadecimal.
Example: 105.0
→
1050
→
0000041A (8 digits)
105.0
→
1050
→
041A
(4 digits)
MRC SRC
Name of service
Processing
TC4/TC2
HFU
01
01
Read from variable
area
Reads a set value.
Supported Supported
01
02
Write to variable
area
Writes a set value.
Supported Supported
01
04
Composite read
from variable area
Reads more than one non-con-
secutive set value.
Supported Supported
01
13
Composite write to
variable area
Writes more than one non-con-
secutive set value.
Supported Supported
01
10
Composite registra-
tion read
Reads in order the contents of
addresses specified for compos-
ite read registration of set val-
ues.
Supported Supported
01
11
Composite read reg-
istration
Specifies the addresses to be
read for a composite read of set
values.
Supported Supported
01
12
Composite read reg-
istration confirma-
tion
Reads the contents of the regis-
tration for composite read of set
values.
Supported Supported
05
03
Controller attribute
read
Reads the model and communi-
cations buffer size.
Supported Supported
06
01
Controller status
read
Reads the operating status.
Supported Supported
08
01
Echoback test
Performs an echoback test.
Supported Supported
30
05
Operation com-
mands
Executes RUN/STOP, AT exe-
cute/AT cancel, and other opera-
tions.
Supported Supported
Содержание EJ1 EtherCAT
Страница 2: ...EJ1 Modular Temperature Controllers User s Manual Revised July 2008 ...
Страница 3: ...iv ...
Страница 19: ...xx ...
Страница 213: ...188 Detailed Description of Services Section 6 4 ...
Страница 227: ...202 Detailed Description of Services Section 7 5 ...
Страница 251: ...226 Determining the Error from the Current Situation for Heater Burnout Alarm Errors Section 8 8 ...
Страница 303: ...278 Index ...
Страница 305: ......