3 - 9
3 Part Names and Basic Procedures
E5@C Digital Temperature Controllers User’s Manual (H174)
3-3
P
a
rt
N
a
mes,
P
a
rt
F
u
n
c
tio
n
s, an
d Setting
Le
v
e
ls
3
3-3-3 Setting Le
v
els
On the E5
@
C, the parameters are classified into levels according to their applications. These levels are
called setting levels. The setting levels consist of some basic setting levels and other setting levels.
The following figure gives an overall image of the setting levels. The setting levels consist of the basic
setting levels (shaded below) and the other setting levels (not shaded).
The Initial Setting Level, Communications Setting Level, Advanced Function Setting Level, and Calibra-
tion Level can be used only when control is stopped. If you change to any of these levels, control will
stop.
*1
To use a key procedure to move to Manual Control Level, set the Auto/Manual Select Addition parameter to
ON and set the PF Setting parameter to
a-m
(Auto/Manual).
*2
The No. 1 display will flash when the keys are pressed for 1 s or longer.
*3
Set the PF Setting parameter to
pfdp
(monitor/setting items).
3-3-3
Setting Levels
Moving between Setting Levels
Press
O
Key once
(models with communications only).
Communications
Setting Level
Advanced Function
Setting Level
Power ON
Advanced settings
Initial Setting Level
Operation Level
Adjustment Level
Communications settings
O
Key for
at least 1 s
Press the
O
Key once.
O
Key for
at least 3 s
*2
O
Key for at least 1 s
or
S
Key for at least 1 s
Press
S
Key.
Press
S
Key.
*3
Protect Level
Calibration Level
Manual Control
Level
Press the
O
Key once.
O
Key for at least 1 s
Operation in progress
Stopped
Used for SP, alarm
values, and other basic
settings and monitoring.
Used to change
adjustment parameters
(PID constants, control
hysteresis, etc.).
Used to set protection
for operations.
Used to set the input
type and other basic
settings.
Used to set the MV
manually.
Only when Manual Mode was
used just before power OFF
O
+
M
Keys
for at least 1 s
Press
O
+
M
Keys
for at least 3 s.
*2
Level changes
automatically.
Enter the password (1201) for
the Move to Calibration Level
parameter.
Release protection and then
enter the password (−169)
for the
amoV
(Move to
Advanced Function Setting
Level) parameter.
000
O
Key for at
least 3 s while
a-m
is
displayed.
*2
S
Key for at least 1 s
*1
Monitor/Setting
Item Level
Used to display
specified monitor
and setting items.
Press the
O
Key once.
Содержание E5C series
Страница 2: ......
Страница 18: ...Conventions Used in This Manual 16 E5 C Digital Temperature Controllers User s Manual H174 ...
Страница 34: ...1 Introduction 1 10 E5 C Digital Temperature Controllers User s Manual H174 ...
Страница 98: ...3 Part Names and Basic Procedures 3 20 E5 C Digital Temperature Controllers User s Manual H174 ...
Страница 310: ...6 Parameters 6 94 E5 C Digital Temperature Controllers User s Manual H174 ...
Страница 326: ...7 User Calibration 7 16 E5 C Digital Temperature Controllers User s Manual H174 ...
Страница 364: ...A Appendices A 38 E5 C Digital Temperature Controllers User s Manual H174 ...
Страница 365: ...Index 1 E5 C Digital Temperature Controllers User s Manual H174 I Index ...
Страница 370: ...Index 6 E5 C Digital Temperature Controllers User s Manual H174 ...