![Omron E5C series Скачать руководство пользователя страница 318](http://html.mh-extra.com/html/omron/e5c-series/e5c-series_user-manual_742592318.webp)
7 User Calibration
7 - 8
E5@C Digital Temperature Controllers User’s Manual (H174)
• Input type 0:
• Input types 1, 2, 3, 4:
5. Execute calibration for the main input.
Press the
M
Key to display the count value for each input type.
The No. 2 display at this time shows the currently entered count value in
hexadecimal. Set the 6-dial as follows:
•
Input type 0:
390
Ω
•
Input type 1, 2, 3 or 4:
280
Ω
Allow the count value on the No. 2 display to fully stabilize, then press the
D
Key to
temporarily register the calibration settings.
If this count value is outside of the specified range, the No. 2 display will flash and
the count value will not be temporarily registered.
6. When the
M
Key is pressed, the status changes as shown to the left.
Set the 6-dial to 10
Ω
.
Allow the count value on the No. 2 display to fully stabilize, then press the
D
Key
to temporarily register the calibration settings.
If this count value is outside of the specified range, the No. 2 display will flash and
the count value will not be temporarily registered.
7. When the
M
Key is pressed, the status changes as shown to the left.
The data to be temporarily registered is not displayed if it is not complete.
Press the
U
Key. The No. 2 display changes to
yes
. Release the key and wait
two seconds or press the
M
Key. This stores the temporarily registered calibration
data to non-volatile memory.
To cancel the saving of temporarily registered calibration data to non-volatile
memory, press the
M
Key (while
no
is displayed in the No. 2 display) without
pressing the
U
Key.
8. The calibration mode is quit by turning the power OFF.
For Controllers that have a transfer output, you can continue by calibrating the
transfer output. For detailed setting methods, refer to 7-6 Calibrating the Transfer
Output.
p390
e20c
p280
e26b
p 10
4543
str
no
Содержание E5C series
Страница 2: ......
Страница 18: ...Conventions Used in This Manual 16 E5 C Digital Temperature Controllers User s Manual H174 ...
Страница 34: ...1 Introduction 1 10 E5 C Digital Temperature Controllers User s Manual H174 ...
Страница 98: ...3 Part Names and Basic Procedures 3 20 E5 C Digital Temperature Controllers User s Manual H174 ...
Страница 310: ...6 Parameters 6 94 E5 C Digital Temperature Controllers User s Manual H174 ...
Страница 326: ...7 User Calibration 7 16 E5 C Digital Temperature Controllers User s Manual H174 ...
Страница 364: ...A Appendices A 38 E5 C Digital Temperature Controllers User s Manual H174 ...
Страница 365: ...Index 1 E5 C Digital Temperature Controllers User s Manual H174 I Index ...
Страница 370: ...Index 6 E5 C Digital Temperature Controllers User s Manual H174 ...